Page 69 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 69

1
                                                                                                               S

                                                                                                                    67
                                             Both 2006-8671 and 2006-8661 TOPJOB  S disconnect
                                                                      ®
                                             terminal blocks have been specially designed for use in
                                             photovoltaic and wind power systems, where voltages                    1
                                             exceeding 1,000 V (IEC) and 600 V (UL) are required
                                             (e.g., generator junction boxes).
                                             ·  Ideal for high voltages in renewable energy
                                              applications
                                             ·  Disconnect terminal blocks with two alternative
                                              disconnect options:
                                              with orange knife disconnect (2006-8671)
                                              with orange disconnect plug (2006-8661)
                                             ·  This 2006 Series terminal blocks are approved for
                                              30 A/1,500 VDC (IEC) or 1,000 VDC (UL)  1 Conductor sizes: 0.5 mm² – 10 mm² “s + f-st”;
                                             ·  With a terminal block width of 15 mm, the maximum   Push-in conductor sizes: 1 mm² – 10 mm² “s”
                                              cross-section for solid and fine-stranded conductors is   and 1.5 mm² – 6 mm²
          Disconnect/test terminal block with knife disconnect   10 mm² (AWG 8) and 6 mm² (AWG 10) for ferruled   “insulated ferrule, 12 mm”
          (2006-8671) in disconnect position  conductors.                       2 AC/DC 1000 V  = rated voltage
                                             ·  Equipped with test slots          DC 1500 V
                                             ·  Compatible with through terminal blocks of the same   12 kV = rated surge voltage
                                              profile and all other TOPJOB  S terminal blocks  3 = pollution degree
                                                               ®
                                                                                  (see Section 14)
                                                                                3 Strip length, see packaging or instructions.
                                                                                4 Protective warning marker must be applied individual-
                                                                                  ly.














          Carrier terminal block (2006-8661) with receptacle for  Orange disconnect plug (2006-8401) in operating posi-  Orange disconnect plug (2006-8401) in parked position
          orange disconnect plug             tion























          Commoning a 15 mm wide terminal block via push-in type                Cover seals unused conductor entry.
          jumper bars: 1 to 3 (2006-433) and 1 to 5 (2006-435).
















          Test slots on both terminal block sides allow for direct mea-         Alternatively, measurement can also be performed using
                                                                                     ®
          surement.                                                             TOPJOB  S connectors (2006-511) from terminal block 1
                                                                                to 2. Spacer modules (2006-549) must be used to com-
                                                                                pensate for the 15 mm terminal block width.
   64   65   66   67   68   69   70   71   72   73   74