Page 71 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 71

TOPJOB  S
                    ®
          Implementing a Current and Voltage Transformer Circuit                                                    1
          Disconnect link in operating position I                                                                   69

                                                   Conductor entry                 Jumper slot for 2007-844x circuit jumper
                                                   Test socket                                                      1
                                                                                   2007-844x circuit jumper
                                                   Jumper slot for 282-43x jumper  1




                                                                                   2



          Terminal blocks required:          In operating position, the measuring device is connected to the transformer, the circuit jumper is inserted and the discon-
          2 x disconnect/test terminal block   2007-8821   nect link is in position I.
          1 x circuit jumper, orange   2007-8442
          optional with locking covers or interlocking links

          Disconnect link in shorting position II
                                                   Conductor entry                 Jumper slot for 2007-844x circuit jumper
                                                   Test socket
                                                                                   2007-844x circuit jumper
                                                   Jumper slot for 282-43x jumper  1




                                                                                   2



                                             The transformer is not disconnected from the measuring device yet, the shorting path is activated by moving the discon-
                                             nect link into shorting position II and the transformer is safely shorted.


          Measuring, disconnect link in measuring position III / test current measurement

                                                   Conductor entry                 Jumper slot for 2007-844x circuit jumper
                                                   Test socket
                                                   Jumper slot for 282-43x jumper  2007-844x circuit jumper

                                                                                   1
                                                                                                      ~

                                                                                   2



                                             The measuring device/relay is electrically disconnected from the transformer. If required, an external voltage can be
                                             applied to the measuring device/relay via the test socket.



          Measurement testing via both test sockets
                                                   Conductor entry                 Jumper slot for 2007-844x circuit jumper
                                                   Test socket
                                                   Jumper slot for 282-43x jumper  1
                                                                                   2007-844x circuit jumper







                                                             A                     2
          Terminal block 1: Disconnect link in operating position I   Measurement testing: First insert the reference current meter (A) into the test socket, then move the disconnect link into
          Terminal block 2: Disconnect link in measuring position III  measurement position III (test current measurement).



                                                              fine-stranded,                     fine-stranded,
                           fine-stranded,                     with ferrule                       with pin terminal
                           tip-bonded                         (gastight crimped)                 (gastight crimped)