Page 81 - Wago_Rail-MountedTerminalBlockSystems_Volume1_2015_US.pdf
P. 81
1
S
79
Fuse plug with pull-tab Using pluggable fuse holders with rail-mounted terminal The following features of the fuse plug ensure quick and
blocks for control circuit protection is highly advantageous safe use:
for the user, as the function and the wiring are accom- · Optional LED indicates blown fuse 1
800 V / I N 10 A plished by two separate parts: · Markable fuse plug for clear coordination to the correct
Plug width 10.4 mm / 0.409 in · No additional cost for assembly and wiring carrier terminal block
· No risk of accidental contact with live parts during · Two touch-proof test slots
disconnection of fuse plug · High density with only 7.5 mm width of terminal block
· If exchanging a defective fuse, the fuse plug is and fuse plug width 7.4 (10.4) mm
completely separated from the carrier terminal block. · Instead of a fuse, a shorting link may be used as a
This provides changeout away from current carrying disconnect plug
parts.
· The fuse plug can be removed by service personnel,
avoiding unintentional reclosing of the circuit by another
person
· Quick replacement a fuse by using a prepared
“stand-by plug.”
Miniature fuses
Series Overload and Short circuit
Item No. Individual Group Individual Group
short circuit protection
protection only
72 mm/2.83 in 2006-911 7.5 argmt. Fused disconnect terminal blocks argmt.
argmt.
argmt.
2.5 W
1.6 W
2.5 W
1.6 W
2006-921
1.6 W
2.5 W
7.5
2.5 W
1.6 W
2006-931 7.5 1.6 W 1.6 W 2.5 W 2.5 W
Pack.
Item No. Unit 2006-931
Fuse plug with pull-tab, gray, /099-... 10.4 2.5 W 2.5 W 2.5 W 2.5 W
2006-931
with indicator lamp 93,3 mm/3.79 in /1099-... 10.4 2.5 W 2.5 W 2.5 W 2.5 W
Both nominal voltage and current are given by the LED or Fuse plug dimensions
fuse. Leakage current in case of blown fuse: LED 2mA,
for miniature fuses 1/4“ x 11/4“
12 - 30 V 2006-931/1099-541 25
30 - 65 V 2006-931/1099-542 25
120 V 2006-931/1099-867 25
230 V 2006-931/1099-836 25
380 - 500 V 2006-931/1099-859 25
0,1 7,5
NL1N L2 NL3
Item-Specific Accessories
Open side of terminal block left
Intermediate plate, 2.9 mm thick
orange 2006-1696 100 (4x25) When using the 10.4 mm wide plug,
gray 2006-1695 100 (4x25) please note:
The extra width of the plug (10.4 mm compared to
7.5 mm for carrier terminal blocks) must be compensated
for by intermediate plates (2.9 mm) when building an
assembly of carrier terminal blocks equipped with fuse
plugs.