Modular inserts Description Type Part No. P.U.
revos flex hc 2M Modular inserts revos flex
Male insert FLE STC 2 35 1 78.016.0253.0 10
Female insert FLE BUC 2 35 1 78.006.0253.0 10
Contacts mm / AWG, gedreht Ø 6 mm
2
Male insert, Ag 16 / 6 05.546.2721.8 20
Female insert, Ag 16 / 6 02.126.7421.8 20
Male insert, Ag 25 / 4 05.546.2821.8 20
Female insert, Ag 25 / 4 02.126.7521.8 20
Male insert, Ag 35 / 2 05.546.2921.8 20
Female insert, Ag 35 / 2 02.126.7621.8 20
Technical data
Rated voltage (EN 60664-1) 1000 V
Rated impulse voltage 8.0 kV
Degree of pollution 3
Overvoltage category III
Rated current ( amb = 40 °C) & 35 mm Leiter 150 A
2
Continuity resistor < 1 mΩ
8
Insulation resistor > 10 Ω
Material
Insulating housing PA
Colour black
Flammability UL 94 V-0
Contacts
Contact surface silver plated
Rated cross-section 16 / 25 / 35 mm 2
Numbers of poles 2
Mating cycles 500
Temperature range -40 °C … + 120 °C
Description Type Part No. P.U.
Zubehör
Crimping tool 95.000.1000.0 1
Crimping die for 16 mm 2 05.502.4600.0 1
Crimping die for 25 mm 2 05.502.4700.0 1
Crimping die for 35 mm 2 05.502.4800.0 1
Eyelet for PE connection 05.581.4027.6 10
Klauke type 60/22-L pneumatic crimping tool can also be used.
Dimensions
Male insert Female insert General requirements
• Due to reduced cross sections at PE
contacts of frames, the PE contact has to be
additionally protected against short circuits
by using a protection circuit offering a
sufficiently short breaking time (< 0,25 s).
• Parts to be used as connectors, not as plug
devices (connector with breaking capcity).
Do not mate under current or voltage!
Deratingkurve nach IEC 60512 Teil 3
revos FLEX Hochstrommodul 78.006/016.0253.0 1000 V / 150 A
Derating curve 190
according to IEC 60512 sec. 3 180
170
revos flex 160
High current module 78.006/016.0253.0 150
1000 V / 150 A 140
130
120
Current [A] 110 Upper temperature limit
Strom [A]
100
2-pole / 16 mm 2 90
2-pole / 25 mm 2 80 70
2-pole / 35 mm 2 60 50
2 x 3-pole / 16 mm 2 40
30
2 x 3-pole / 25 mm 2 20
10
2 x 3-pole / 35 mm 2 0
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
Ambient temperature [°C]
Umgebungstemperatur [°C]
Juli 2013 Datenübernahmen von Amphenol Jan Breitenbach/QP-LAB