Page 60 - Parker - Energy Products Division - Multitube (Instrument and Heat Trace Tubing Products)
P. 60

Process Control & Analyzer SystemsProcess Control & Analyzer Systems             Catalog Number 4200-M-2
       Process Control & Analyzer Systems
                                                                                          Back to Table of Contents



            4031-0001 Electrical Connection Kit for CL and

            4031-0001B Electrical Connection Kit for CH
            Series Constant Wattage Temptrace









            Each Kit contains:
               1 Connection Box            1 Bracket Assembly
               1 Connection Box Gasket     2 Connector unions
               1 Connection Box Cover      2 Heating cable grommets
               1 Mounting Bracket          2 Plastic cable ties
               1 3/4" Locknut              2 Non-insulated butt splice (12-10 AWG)
               1 3/4" Pipe Plug            3 Non-insulated butt splice (16-14 AWG)
               1 "Electric Trace" caution sticker     2 Heater termination boots
               1 2.8 oz Black RTV Sealant     1 Roll 3/4" wide temperature tape


            Description: Parker electrical connection kits are universal all-in-
            one connection kits for making the electrical connections (input
            power, splice, input power splice, and termination) for Parker
            electric trace tubing bundles. The kits contain all the necessary
            components and hardware to make one input connection, one
            splice connection or one input power splice connection as well as
            two termination connections. The connection kits are designed for
            use in ordinary locations and Class I, Division 2, Groups B, C, and
            D; Class II, Division 2, Groups F and G; Class III, Divisions 1 and 2
            hazardous locations.
            Approvals:
            FM – Factory Mutual Approved
            Ordinary Locations
            Hazardous (Classified) Locations
                                                                                      Assembled Input Power
                                                                                      Connection Kit
            Class I, Division 2, Groups B, C and D
            Class II, Division 2, Groups F and G
            Class III, Division 1 and 2
            Ground Fault Equipment Protection Devices (GFEPDs):
            The IEEE standard (515-1989) for heating cables requires the
            use of GFEPDs with a nominal 30 milliampere trip level for
            “piping systems in classified ares, those areas requiring a high
            degree of maintenance, or which may be exposed to physical
            abuse or corrosive atmospheres.”


            Refer to Section G for detailed installation instructions.