Page 55 - Parker - Energy Products Division - Multitube (Instrument and Heat Trace Tubing Products)
P. 55

Process Control & Analyzer Systems
                                                     Process Control & Analyzer Systems
            Catalog Number 4200-M-2
               Back to Table of Contents







            Accessories                                          Ground Fault Equipment Protection Devices
            Accessories are available for electrical connections,   (GFEPDs):
            bundle splicing and end terminations. Accessories for   The IEEE standard (515-1989) for heating cables
            mineral insulated bundles, consult the factory.      requires the use of GFEPDs with a nominal 30
                                                                 milliampere trip level for “piping
            Ordering: For information about how to specify and   systems in classified areas, those areas requiring
            order, see How-to-Order section.                     a high degree of maintenance, or which may
                                                                 be exposed to physical abuse or corrosive
            NOTE: It is absolutely necessary to seal the ends against  atmospheres.”
            contamination from moisture and/or corrosive liquids. Parker
            Hannifin cannot assume any liability for product damage
            caused by moisture from unsealed ends.

            Electrical Specifications:
            Heater Type ..........Series resistance, order to length
            Operating Voltage .....................120/208/240 VAC
            MI Cable Construction ..Alloy 825 outer sheath, nickel
            clad copper bus wires, magnesium oxide insulation
            and nichrome heating element.
            Maximum Exposure Temperature (heater cable only):
            1200° F (650° C) power off 1000° F (538° C) power
            on (30 watts/ft. load)
            Area classification... General purpose, Class I,
            Division 2, Groups A, B, C and D.
            For recommended temperature controller, see 4012-
            01145 (G.P.areas) and 4012-01147 (Hazardous
            locations)






                 Approvals:


                 FM – Factory Mutual Approved
                 Ordinary Locations
                 Hazardous (Classified) Locations

                 Class I, Division 2, Groups B, C and D
                 Class II, Division 2, Groups F and G
                 Class III, Division 1 and 2


















                                                                                       Parker Hannifin Corporation
 51                                                          52                        Energy Products Division
   50   51   52   53   54   55   56   57   58   59   60