Page 50 - Parker - Energy Products Division - Multitube (Instrument and Heat Trace Tubing Products)
P. 50

Process Control & Analyzer Systems                                               Catalog Number 4200-M-2

                                                                                          Back to Table of Contents







            Electrical Specifications:

              Heater type       12 W./ft.           18 W./ft.
               Insulation       Kapton ®            Kapton ®
             Bus wire size      12 AWG              12 AWG
               Heating       Average 48” (121.9 cm) for high temperature
             zone length**        Kapton® insulated heater wires




               Part         Power         Voltage   Maximum Circuit   Current A/ft (A/m)
              Number     Consumption                 Length*** ft (m)
              Series      W/ft (W/m)

                                                          180             0.100
                             12             120          (54.9)          (0.3281)
                CH
                            (39.3)          240           360             0.050
                                                         (109.7)          (0.164)
                                                          147             0.150
                             18.0           120          (44.8)           (0.49)
                CH
                            (58.95)         240           294             0.075
                                                         (89.6)           (0.246)

            ***Based on 10% power drop.
            For recommended temperature controller, see 4012-01145 (G.P. areas) and
            4012-01147 (Hazardous locations) in Section F.


                                                              Ground Fault Equipment Protection Devices (GFEPDs):
                 Approvals:                                   The IEEE standard (515-1989) for heating cables requires
                 Ordinary Locations                           the use of GFEPDs with a nominal 30 milliampere trip level
                 FM – Factory Mutual Approved                 for “piping systems in classified areas, those areas requiring
                                                              a high degree of maintenance, or which may be exposed to
                 Hazardous (Classified) Locations
                                                              physical abuse or  corrosive atmospheres.”
                 FM – Factory Mutual Approved
                 Class I, Division 2, Groups B, C and D
                 Class II, Division 2, Groups F and G
                 Class III, Division 1 and 2



            **Installation Note:
            Caution: Cutting beyond heating zone indentation will result
            in an unheated section of the heater wire for the balance of the
            heating zone length. The bus wires MUST NOT be connected
            together on the termination end!