Page 87 - Viledon - Air and Liquid Filtration
P. 87
Gas phase filters
Pellets | CCP Pellets
Application CCP 510
®
Viledon ChemControl Pellets are used in different areas for the prevention of Used especially for removal of gaseous halogens from airstreams. Capture
corrosion caused by acidic gases. Special pellets are used for ammonia and chlorine, bromine and iodine by adsorption and absorption. Highly porous
chlorine. structure of activated alumina impregnated with active ingredients.
Paper and chemical pulp industry Computer center CCP 610
Petrochemistry Labs Used for the filtration of airborne contaminant gases e. g. hydrocarbons, VOCs,
Mining Microelectronics chlorine and nitrogen dioxide. Consist of virgin activated carbon with very high
Chemical industry Fertilizer inner surface area to achieve excellent adsorption capacities. Very low resistance
Pharmaceutical industry
to airflow and long service life.
CCP 104 CCP 810
Used for the prevention of corrosion caused by acidic gases. Remove contami- Blended pellets used for filtration of gaseous contaminants. 50:50 mix of CCP
nant gases by adsorption, absorption and chemisorption. Contain a minimum of 108 and CCP 610 provides excellent adsorption, absorption and chemisorption.
4 % potassium permanganate to eliminate contaminants via oxidation reaction to CCP 830
inactive solids.
Blended pellets used for filtration of gaseous contaminants. 50:50 mix of CCP
CCP 108
210 and CCP 610 provides excellent adsorption, absorption and chemisorption.
Used for the prevention of corrosion caused by acidic gases. Remove contami- CCP 840
nant gases by adsorption, absorption and chemisorption. Contain a minimum of
8 % potassium permanganate to eliminate contaminants via oxidation reaction to Blended pellets used for filtration of gaseous contaminants. 50:50 mix of CCP
inactive solids. 310 and CCP 610 provides excellent adsorption, absorption and chemisorption.
CCP 210 CCP 903
Designed to remove or destroy airborne acidic gases by oxidation. Especially Specifically used for removal of gaseous ammonia from airstreams. They capture
high reactivities and removal capabilities, even at high contaminant concentra- ammonia by means of adsorption and absorption inside their zeolite structure.
tions. Contain a mix of sodium and potassium permanganate at minimum 10 % Please note:
by weight. All application information provided are subject to on-site conditions, specific application requirements and
potential alternating effects by combining several ChemControl Pellets in multi-stage units. Please consult
CCP 310 your local Viledon ® partner for further information.
Ideal for filtration of acidic gases in highly corrosive environments. Very effective Delivery notes
in removing hydrogen sulfide, sulfur dioxide and chlorine. Porous structure based
Other ChemControl Pellets are available on request – especially custom formulations with
on activated alumina impregnated with activated carbon. impregnations for specific gaseous contaminants.
Article Diameter Face Ambient Removal capacity Removal capacity Removal capacity Removal capacity Moisture content Crush strength
[mm] velocity temperature for Cl 2 of own for H 2 S of own for NH of own for SO 2 of own (approx.) (minimum)
3
[m / s] [C°] weight [%] weight [%] weight [%] weight [%] [%] [kg]
CCP 104 3.80 0.3 – 2.5 −20 ... +50 7 4 20 2
CCP 108 3.80 0.3 – 2.5 −20 ... +50 14 7 20 2
CCP 210 3.80 0.3 – 2.5 −20 ... +50 25 12 20 2
CCP 310 3.80 0.3 – 2.5 −20 ... +50 10 15 10 20 2
CCP 510 3.80 0.3 – 2.8 −20 ... +50 15 15 2 2
4 × 8
Subject to technical changes. CCP 810 3.80 | 4 × 8 0.3 – 2.9 −20 ... +50 4 3.75 7 15.53 10 3 7.5 2 2 2 3 87
−20 ... +50
10
CCP 610
3
0.3 – 2.5
−20 ... +50
3.80
CCP 830
0.3 – 2.1
6
12
0.3 – 2.1
3.80 |4 × 8
CCP 840
−20 ... +50
10
CCP 903
−20 ... +50
0.3 – 2.7
3.80
www.freudenberg-filter.com