Page 89 - Viledon - Air and Liquid Filtration
P. 89

Gas phase filters

                                                   Systems | ChemControl Recirculation Units

















          Application                                         Viledon  CRU: The ‘recirculating air filtration’ system
                                                                   ®
          Many industrial processes generate contaminant gases that can cause corrosion.   The Viledon  ChemControl Recirculation Unit (CRU) is a system fully based on
                                                                     ®
          Even minor damage to electronic components can have serious consequences,   recirculated air filtration. This makes it an ideal addition for rooms that are
          e. g. fault signals, unplanned downtime, high repair costs. The Viledon    supplied with filtered air and maintained at positive pressure using a Viledon
                                                                                                            ®
                                                    ®
                                           ®
          ChemControl Recirculation Unit (CRU) and the Viledon  ChemControl   ChemControl Deep-Bed Pressurization Unit (CDBPU).
          Recirculation Pressurization Unit (CRPU) are multi-stage filtration systems that
          reliably provide complete protection against corrosion.  Viledon  CRPU: The ‘outside air + recirculating air filtration’ system for
                                                                   ®
                                                              overpressure generation
          In both systems, Viledon  Compact pocket filters are used in the pre-filtration
                         ®
                                           ®
          stage. Positioned before and after the fan, the Viledon  ChemControl Modules   Using an admixture of outside air, the Viledon  ChemControl Recirculation
                                                                                         ®
          with pellets eliminate harmful gases. Viledon  MaxiPleat cassette filters ensure   Pressurization Unit (CRPU) can maintain a slight positive pressure within the room
                                     ®
          secure fine filtration. Integrated pressure gauges allow for reliable monitoring   to be protected. At moderate concentrations of corrosive gases, the Viledon
                                                                                                           ®
                                                                                             ®
          onsite.                                             CRPU can be operated without the use of a Viledon  ChemControl Deep-Bed
                                                              Pressurization Unit.






           Delivery notes
           Please consult your local Viledon ®  partner for further information.






           Viledon  CRU*
               ®
           Article       Nominal     Dimensions   Weight   Number of    Number of   Number of fine   Power consumption
                         volume flow  (H × W × D)  [kg]    modules per stage  pre-filters  filters  average
                          3
                         [m  / h]    [mm]                                                        [kW]
           1800 DW       1,800       2,600 × 750 × 750  550  4          1           1            0.8
           1800 DW stainless steel**  1,800  2,600 × 750 × 750  580  4  1           1            0.8
           3600 DW       3,600       2,600 × 1,500 × 750  650  8        2           2            1.3
           3600 DW stainless steel**  3,600  2,600 × 1,500 × 750  680  8  2         2            1.3
           Viledon  CRPU*
               ®
           Article       Nominal     Dimensions   Weight   Number of    Number of   Number of fine   Power consumption
                         volume flow  (H × W × D)  [kg]    modules per stage  pre-filters  filters  average
                                                                                                 [kW]
                                     [mm]
                         [m  / h]
                          3
         Subject to technical changes.  1800 DW  1,800  2,600 × 750 × 750  560  4 4 8 8  1 1 2 2  1 1 2 2  0.8    89
           1800 DW stainless steel**
                                                                                                 0.8
                                                  590
                         1,800
                                     2,600 × 750 × 750
           3600 DW
                         3,600
                                     2,600 × 1,500 × 750
                                                  660
                                                                                                 1.3
                                                                                                 1.3
                                     2,600 × 1,500 × 750
                         3,600
                                                  690
           3600 DW stainless steel**
          *   Standard casing: double wall casing ensuring low noise, manufactured using alumina corners and panels with plastisol coating.
          **  Stainless steel casing also available as single wall (SW) model.
   84   85   86   87   88   89   90   91   92   93   94