Page 723 - Mechatronics with Experiments
P. 723

PROGRAMMABLE LOGIC CONTROLLERS  709
                             is hard-wired instead of programmed in the PLC. A hard-wired seal-in circuit includes the
                             following components:

                                1. a START button which is a momentary contact switch,
                                2. a STOP button,
                                3. a relay or starter coil from the output device (i.e., coil of a starter used to start a
                                  motor)
                             When the START button makes a momentary contact, it energizes the coil of the relay
                             (or starter). Then the contacts from that coil maintain the flow of current since it is wired
                             in parallel with the START button even when the START button no longer makes contact
                             since it is a momentary button. The power flow is cutoff (stopped) any time the STOP
                             button is pressed. This is called the three-wire control. If for some reason the power is lost
                             to the circuit, the START button must be momentarily pressed again in order to start the
                             motor again. This is good for safety, but requires human intervention if the power flow in
                             the circuit is interrupted. In other words, the re-start of the cycle is not automatic.


                      9.4 PLC CONTROL SYSTEM APPLICATIONS

                             9.4.1 Closed Loop Temperature Control System
                             Figure 9.10 shows a closed loop temperature control system in an oven using a PLC. The
                             PLC based control system uses a temperature sensor (i.e., a thermocouple interfaced to the
                             PLC using a thermocouple sensor interface module), a proportional valve which regulates
                             the fuel into the furnace proportional to the displacement of the valve spool, a fuel supply
                             line (i.e., gas line from utility supply), and a display to inform the operator of the process
                             variables in real-time (i.e., the desired temperature setting, actual temperature, fuel rate).
                             The PLC controls the valve with an analog output module. If the current capacity of the
                             analog drive is not large enough to drive the valve, then there would be a current amplifier
                             between the analog output module and the valve. The closed loop control algorithm is




                                                      PLC


                             Display/HMI

                                        Temperature sensor  Control
                                                           signal






                                             Furnace




                                                           Fuel
                                                   Valve
                                                                   FIGURE 9.10: Example temperature control
                                                                   system with a PLC using a PID module.
   718   719   720   721   722   723   724   725   726   727   728