Page 82 - Icon Ridge Sanitary-Heating-Air Catalog
P. 82
Building Services
Valve Insulation Universal
The clever valve insulation for virtually all common European
slanted seat and KFR types
• Made of closed-cell foamed polyethylene with additional firm mesh
effect made of PE
• Easy and rapid assembly: shift, fold and securely closed by means of
closing clips
• Equipped with universal recess
• Warm remains warm – cold remains cold!
• Avoids formation of condensation water
• A non-insulated valve emits as much heat or absorbs as much
heat as several meters of tube
• Offers a rapid and easy mountable closing of gaps in professionally
installed and exemplarily insulated cold water bearing drinking water
pipes, hot water bearing service water pipes, heating pipes as well
as industrial piping networks
Fields of application:
• DIN 1988 TRWI: Protection against heating up, formation of
condensation water and sound transmission of drinking water pipes
• EnEV Annex 5: Requirements to limit the heat emission of heat
distribution and heat water pipes as well as of fittings
Installation under non- Insulated valve: According to the energy saving
insulated conditions: The temperature on the outer skin regulation of insulated installations:
The heat loss at the valve is of the shell almost complies with Piping and valves are exemplarily insulated
greatest due to the flow resistance. the environmental temperature. and this way conforming to the law.
Technical Data
Thermal conduct./calcul. value: at 10°C ISO 2581 W/mk 0,035
Article No. Article Description QTY at 40°C ISO 2581 W/mk 0,040
8729 1 15 VALVE INSULATION 1/2" DN15 e 10 Noise insulation: DIN 4109 dB
8729 1 20 VALVE INSULATION 3/4" DN20 e 10 Fire protection: Ü-No Z-23.14-1141 PE foam
8729 1 25 VALVE INSULATION 1" DN25 e 10 is quality controlled DIN 4102 B1
8729 1 32 VALVE INSULATION 1 1/4" DN32 e 10 Water vapor permeability: ISO 1663 g/m² 1,1 (5,0 mm)
8729 1 40 VALVE INSULATION 1 1/2" DN40 e 5 Water vapor diffusion factor: µ > 4000
8729 1 50 VALVE INSULATION 2" DN50 e 5 Use temperature: DIN 1988 -80°C to +100°C
Included in delivery:
• 2x Closing clips
• 1x Valve insulation
Installation Instructions:
1. Put the opened valve isolation against the valve, 2. Close the insulation shell. 3. Close the closed valve
which needs to be isolated and check if it is fitting. insulation using the clips
included in the delivery.
Technical data subject to change.
Availability subject to country specific rules and regulations. www.iconridge.com Source: Theo Förch GmbH & Co. KG 82