Page 8 - Industrial Technology EXTRA 22nd February 2021
P. 8

the VX25 add-on unit series to keep electrical and   profile in the AX, as well as the mounting rail and
       pneumatic components separate from each other.   system chassis, they can be mounted there easily
       Think of rail systems, mounting profiles, system   and quickly. The plastic cable hose makes it easy to
       chassis and mounting rails.          establish a reliable connection with flexible current
         Non-electrical parts and appliances that do not   conductors. This also fulfills the requirement that
       belong directly to the electrical equipment cannot   “sufficient mechanical strength must be provided,
       simply be placed within the housing containing the   without compromising proper functioning”.
       switchgear. Solenoid valves must therefore be kept
       separate from other electrical components by  Cable entry and protection class
       placing them in a separate compartment made with   In addition to cable routing, the cable entry into a
       rail systems. System chassis, which are used in the   switch and control panel is also important.
       door of the VX25 to make optimal use of cabinet   Maintaining the IP protection class is paramount.
       space, can sometimes also be used for the AX wall   The IP value says something about how well a
       and floor cabinet series. The same applies to   cabinet can keep out threats such as dust and
       different mounting profiles.         water. The latest standard does not allow openings
                                            in the enclosure (such as those for the passage of
       Cable routing at moving parts        cables) to impair the degree of protection.
       The IEC standard states that: “connections to   At the same time, openings for on-site cable
       appliances mounted on doors or other moving parts   entry must be easy to open again. The VX25 wall
       are made using flexible current conductors (…),   cabinet has sliding metal bottom plates, which
       allowing regular movement of the part.”  Pipes must   create an opening for cables. Additional provisions
       be secured to the fixed and moving part.    are therefore required for correct and safe cable
         Because cable hose holders have the same hole   entry. An elastic clamping profile seals the opening.
       pattern as the cabinet frame of the VX25, the door   This creates a flexible cable entry that guarantees