              6.  User Instructions


                        Once  fully  configured,  GuardII+  automatically  collects  and  stores  measurement  data,
                     produces Alerts, and collects/updates Modbus information; however, if a particular feature is
                     not used, then the ability of the monitor to operate to its fullest extent may be compromised.
                     For example, if the Alert Relay is not connected, or the Alert Thresholds are not set, then the
                     entire Alert function will not work; the only way to tell if the measurement data indicates a
                     potential problem is by downloading and analyzing the data or monitoring the Modbus data
                     registers.
                                     NOTE:
                                     While this manual describes what needs to be done in the IAM software to
                                     use a GuardII+ SM system, the complete details on how to use IAM are in
                                     the IAM Help files.

              6.1.  First-Time Configuration

                        GuardII+ monitoring technologies require configuration before they can be used.  When a
                     GuardII+ is started up for the first time, or when a new monitoring technology is added, the
                     Error


                         indicator will blink green; this means that one or more technologies need to be configured.
                     Any monitoring technologies that are not configured will not take measurements.
















                                            Figure 6-1 Front Panel Error Indicator
                                     NOTE:
                                     In cases where the GuardII+ is left partially configured (for example, the
                                     PD system is configured, but the SM system is not), then any monitoring
                                     technology that is configured will function normally.

              6.2.  IAM Preparation

                        Before the GuardII+ can be configured, there is some preparatory work to do.