Page 82 - Basic PD Theory
P. 82

References


               4.  Partial Discharge
               Similar to the  on-line test, the off-line partial discharge test is sensitive to delamination and
               semicon/grading coating problems.  Tests are usually taken at line-to-ground voltage.  Because the     IEEE Std 1434:
                                                                                             Guide to the Measurement
               voltage stress is higher than normal on the majority of the coils there is  no direct comparison   of Partial Discharges in
               between off-line and on-line testing.  It is often possible with off-line testing to identify the exact   Rotating Machinery
               problem spot and therefore repair it.
                       Sensors:  capacitive couplers
                 RF probe (TVA probe)                                           TVA - Tennessee Valley Authority
                 acoustic probe
                 visual enhancement cameras – “Corona Scopes”

                                       Finds:  moisture and delaminated insulation

               5.  Surge Test

               Most of the insulation testing described thus far has been for testing the integrity of the groundwall insulation.  Because of the
               high frequency surges that exist when a generator is started, the turn insulation of the line end coil     IEEE Std 522: Guide
               can be subjected to extremely high electric stress.   During the manufacturing process a surge test   for Testing Turn-to-Turn
               is often used to locate defects prior to impregnation.  Some companies also use the test as a   Insulation on Form-Wound
               maintenance tool.  The test procedure is to apply a high-frequency surge to two similar specimens   Stator Coils for Alternating-
               and compare the results or to  observe the surge waveform for changes in frequency as the   Current Rotating Electric
               applied voltage is increased.   At high frequency, the majority of the surge will be dropped across   Machines
               the capacitance of the insulation between the first and second turns.  A noticeable difference between the resultant waveforms
               would be an indication of a problem.   Any misconnection affecting the magnetic field patterns within the winding, such as a coil
               reversal, phase-to-phase short, or coil-to-coil short, would cause large irregularities.  Not as observable because of the small
               change in frequency, < 0.1%, are turn-to-turn shorts.   Since it is difficult to detect turn-to-turn shorts, only people truly familiar
               with the patterns of the generator being tested should be relied upon for interpretation.
               The surge test is essentially a go/no-go test similar to a hipot test of the turn insulation.
               For new windings the test is normally performed at the peak voltage value calculated from the above figure and with a rise time
               of 0.1 to 0.2 µs.  For a 11 kV motor this would be:
                           √2/√3*11*3.5 = 31 kV
               For motors that have been in service, a surge with the same rise time, but with a peak value of 75% of that for a new winding is
               normally used, i.e., for a 6.6 kV motor this would be 23.25 kV

                                              Finds:  turn insulation problems

               6.  Direct High Voltage Testing
               After a winding has passed the IR/PI test and deemed suitable for high potential testing, you may     IEEE Std 95:
               want to perform a high direct voltage test.  This involves subjecting the winding to a high direct   Recommended Practice for
               voltage to see if it will survive over-voltage stress.  The hope is that if there is a crack or weak spot   Insulation Testing of Large
               in the  insulation it will  “pop”  during the test where there is substantial energy stored in the   AC Rotating Machinery
               winding capacitance but little “follow” current from the test  supply and therefore minimal   with High Direct-Voltage
               damage.  It will also “fail” during a scheduled outage when repairs are easier to perform.  There are two general procedures for
               high potential testing:  a proof test used for a new winding or after major repairs and a maintenance test used for routine testing.
                                              Finds:  severe cracks





                                                                                 www.irispower.com

                                                                                  77 | P ag e
   77   78   79   80   81   82   83   84   85   86   87