Page 83 - Basic PD Theory
P. 83
References
Proof testing
The proof test is a go-no go test that involves application of a DC test voltage that is 1.7 times the AC proof value of twice V L-L
+ 1 kV. This test is generally used for a new winding or after major maintenance has been done on a winding and there is a
potential for severe damage.
Maintenance Testing
The maintenance test is conducted at approximately 75% of the proof test voltage and may be used as more of a predictable
testing tool. Often, a maintenance test can be done by applying the voltage in a step, or ramp method. The hope is by
monitoring the current you can predict the point of failure before breakdown occurs. Though not always possible, this
deflection point is sometimes observed by a sudden change in the current that results in the presence of a “knee” on the current
vs. voltage plot. A knee is an observed phenomenon and often difficult to define mathematically, some folks say a doubling
between voltage intervals describes the knee. If the current avalanches, there is obviously a problem. This test is not normally
performed on salient pole rotor windings.
Total current
The voltage can be applied in the following methods: Ramp test
• Ramp Tests - steady increase in voltage
• Fixed-interval step test - <3% change at 1
minute intervals
• Graded-time interval step test - remove effects Step test
of absorption current on the slope of the V/I
curve
Applied Voltage
Figure 60. The "knee" in the leakage current during a direct voltage test.
7. Alternating Voltage Hipot
Like the direct voltage Hipot test, this test is a go or no-go test. It is strictly a test to determine if IEEE Std 432:
the winding will survive an over-voltage stress typical of a bus fault, or is sealed from moisture Guide for Insulation
ingress. It is a destructive test by design in that if a failure occurs the machine is not suitable for Maintenance for Rotating
return to service until the failure is repaired. The ac hipot stresses the endwinding similarly to Electrical Machinery (5 hp to
that induced during normal operation. Recommended levels are as follows: less than 10,000 hp)
2 * V L-L + 1kV for acceptance of a new winding
1.5 * V L-L for maintenance (some prefer 130% before maintenance and 120% after)
Finds: severe cracks
8. Wedge Tap Test
If it is suspected that the coil wedges are loose then a wedge tap test should be perform to verify this. Tap each wedge at a
number of locations along its length with a ball peen hammer or other metal object and put a finger on the wedge near where it
is struck. If the wedge is tight there will be a “pinging” sound and no wedge vibration will be felt. If the wedge is loose there will
be a dull “thud” sound and wedge vibration will be felt. The recommended acceptance criteria for this test is:.
No two adjacent wedges in the same slot should be loose
www.irispower.com
78 | P ag e