Page 454 - McD_6118-AEW-XX-XX-NBS-A-001_Neat
P. 454

P12 Fire stopping systems

            GENERAL

  130 FIRE STOPPING SYSTEM TO INDIVIDUAL SERVICES PENETRATIONSas applicable
        • Fire resistance: site specific.
        • Penetration seal: Pipe collar - insulated wrap.
             - Size: site specific.
        • Capping sealant: Fire resisting silicone.
             - Colour: site specific.

  160 LINEAR GAP SEALINGas applicable
        • Fire resistance: site specific.
        • Gap width or height (nominal): site specific.
        • Gap filler: Mineral wool.
        • Capping sealant: Fire resisting silicone.
             - Colour: site specific.

            PRODUCTS

  305 PRODUCT CERTIFICATION
        • Certification: For products specified generically, submit evidence of compliance
            with the specification.
        • Acceptable evidence: Agrément certificate.

  360 MINERAL WOOL RIGID BATTS
        • Standard: To BS EN 13162.
        • Manufacturer: Contractor's choice .
             - Product reference: Submit proposals.
        • Recycled content: Submit proposals.

            EXECUTION

  620 WORKMANSHIP GENERALLY
        • Gaps: Seal gaps between building elements and services, to provide fire resistance
            and resist the passage of smoke.
        • Adjacent surfaces: Prevent overrun of sealant or mortar on to finished surfaces.

  650 INSTALLING FIRE STOP LAMINATE
        • Fitting of strips: Compress strips and fit into gap, so that, as they decompress, the
            strips wedge themselves in the void.
        • Shrink wrapping: Do not remove.
        • Joints:
             - Ends of strips: Fit intumescent 'end piece' at both ends of run of stop laminate.
             - Joints between strips: Fit two intumescent 'end pieces' at each butt joint.

RotF generic (intermediate) NBS 2014  6118-AEW-XX-XX-NBS-A-01