Page 34 - dust collection systems
P. 34

vertically as a nearly direct replacement for standard bags
               and cages in existing baghouses





               Types of Cleaning Controls





               Normal pressure drop for a bag filter will fall in the range of 2

               1/2 to 6 inches of w.c. (water column) after the elements

               (filter bags) are broken in. The differential pressure reading

               will increase as the elements get dirty and the filter must

               eventually be cleaned or airflow will fall to unacceptable

               levels.





               Bag filters are available with “continuous” or "clean on

               demand" cleaning control. Continuous cleaning type bag

               filters are cleaned with pre-timed pulses of compressed air

               regardless of cleaning need. However, clean on demand

               filters are cleaned based on the pressure drop monitored

               across the filter bags.





               A typical automatic clean on demand system for a pulse jet

               baghouse consists of a differential pressure gauge

               (Switch/Gage, a 2-in-1 instrument combining differential

               pressure gage with low- and high-pressure switches) and a

               programmable controller. The differential pressure gauge

               measures the difference in pressure between the dirty air

               side and clean air side of the bags in the baghouse. The
   29   30   31   32   33   34   35   36   37   38   39