VENTILATION




                    With the exception of smoking lounges, the ventila-   b.“Warm air” is air warmer than space temperature.
                  tion rates in Table 403.3.1.1 are based on the absence   c. “Ceiling” includes any point above the breathing zone.
                  of smoking in occupiable spaces. Where smoking is  d. “Floor” includes any point below the breathing zone.
                  anticipated in a space other than a smoking lounge, the   e. Zone air distribution effectiveness of 1.2 shall be permitted for systems
                                                                    with  a floor supply of cool  air  and ceiling return,  provided that  low-
                  ventilation system serving the space shall be designed
                                                                    velocity displacement ventilation achieves unidirectional flow and
                  to provide ventilation over and above that required by  thermal stratification.
                  Table 403.3.1.1 in accordance with accepted engineer-   f. Zone air distribution effectiveness of 1.0 shall be permitted for systems
                  ing practice.                                     with a ceiling supply of warm air, provided that supply air temperature is
                                                                    less than 15°F above space temperature and provided that the 150-foot-
                    Exception: The occupant load is not required to be
                                                                                                1
                                                                    per-minute supply air jet reaches to within 4 / 2  feet of floor level.
                    determined based on the estimated maximum occu-
                    pant load  rate indicated  in Table 403.3.1.1 where     403.3.1.1.1.3  Zone  outdoor  airflow.  The zone
                    approved statistical data document the accuracy of      outdoor airflow rate (V ), shall be determined in
                                                                                               oz
                    an alternate anticipated occupant density.              accordance with Equation 4-2.
                    403.3.1.1.1  Zone  outdoor  airflow. The  minimum       V   =  V bz                (Equation 4-2)
                                                                                  -------
                    outdoor airflow required to be supplied to each zone     oz   E z
                    shall be determined as a function of occupancy clas-
                    sification and space air distribution effectiveness in  403.3.1.1.2  System  outdoor  airflow.  The outdoor
                    accordance with Sections 403.3.1.1.1.1  through      air required to be supplied by each ventilation sys-
                    403.3.1.1.1.3.                                       tem shall be determined in accordance with Sections
                       403.3.1.1.1.1  Breathing  zone  outdoor  airflow.  403.3.1.1.2.1 through 403.3.1.1.2.3.4 as a function
                       The outdoor airflow rate required in the breath-  of system type and zone outdoor airflow rates.
                       ing zone (V ) of the occupiable space or spaces      403.3.1.1.2.1  Single  zone  systems.  Where one
                                bz
                       in a zone shall be determined in accordance with     air handler supplies a mixture of outdoor air and
                       Equation 4-1.                                        recirculated return air to only one zone, the sys-
                                                                            tem outdoor  air intake flow rate  (V ) shall be
                                                                                                          ot
                       V bz  =  R P +  R A z      (Equation 4-1)            determined in accordance with Equation 4-3.
                                z
                                    a
                              p
                                                                            V   =  V                   (Equation 4-3)
                       where:                                                ot    oz
                       A = Zone floor area: the net occupiable floor
                        z
                            area of the space or spaces in the zone.        403.3.1.1.2.2 100-percent outdoor air systems.
                                                                            Where one air handler supplies only outdoor air
                       P = Zone population: the number of people in         to one or more zones, the system outdoor  air
                        z
                            the space or spaces in the zone.                intake flow rate (V ) shall be determined using
                                                                                            ot
                       R = People outdoor air rate: the  outdoor            Equation 4-4.
                        p
                            airflow rate required per person from
                            Table 403.3.1.1.                                V ot  =  Σ all zones V oz  (Equation 4-4)
                       R = Area outdoor air rate: the outdoor airflow
                        a
                            rate required  per unit area from Table         403.3.1.1.2.3  Multiple  zone  recirculating  sys-
                            403.3.1.1.                                      tems. Where one air handler supplies a mixture
                       403.3.1.1.1.2  Zone  air  distribution  effective-   of outdoor air and recirculated return air to more
                       ness. The zone air distribution effectiveness (E )   than one zone, the system outdoor air intake flow
                                                             z
                       shall be determined using Table 403.3.1.1.1.2.       rate (V ) shall be determined in accordance with
                                                                                 ot
                                                                            Sections 403.3.1.1.2.3.1 through 403.3.1.1.2.3.4.
                              TABLE 403.3.1.1.1.2
                    ZONE AIR DISTRIBUTION EFFECTIVENESS a,b,c,d               403.3.1.1.2.3.1  Primary  outdoor  air  frac-
                     AIR DISTRIBUTION CONFIGURATION       E z                 tion.  The primary outdoor air fraction (Z )
                                                                                                                  p
                                                                              shall be determined for each zone in accor-
             Ceiling or floor supply of cool air         1.0 e
                                                                              dance with Equation 4-5.
             Ceiling or floor supply of warm air and floor return  1.0              V
                                                                                     oz
             Ceiling supply of warm air and ceiling return  0.8 f             Z =   -------            (Equation 4-5)
                                                                                p
                                                                                    V
             Floor supply of warm air and ceiling return  0.7                        pz
                                                                              where:
             Makeup air drawn in on the opposite side of the room   0.8
             from the exhaust or return                                       V = Primary  airflow: The airflow  rate
                                                                               pz
                                                                                   supplied to the  zone from  the  air-
             Makeup air drawn in near to the exhaust or return loca-  0.5          handling unit at which the outdoor air
             tion
                                                                                   intake is located. It includes outdoor
             For SI: 1 foot = 304.8 mm, 1 foot per minute = 0.00506 m/s,           intake air and recirculated air from that
                  °C = [(°F) – 32]/1.8.                                            air-handling unit but does not include
              a. “Cool air” is air cooler than space temperature.                  air transferred or air recirculated to the