Page 48 - 2018_IMC
P. 48

CHAPTER 4

                                                      VENTILATION




             User note:
                About this chapter: Chapter 4 intends to provide an indoor atmosphere that protects the health and well-being of building occupants. Both
                mechanical and natural ventilation are addressed. Mechanical ventilation provides what is considered to be acceptable indoor air quality.
                Mechanical ventilation minimizes adverse health effects and provides an atmosphere that generally is not objectionable to occupants.



                               SECTION 401                             1612 of the  International  Building  Code for  utilities
                                 GENERAL                               and attendant equipment.
             401.1  Scope. This  chapter shall govern  the ventilation of  401.5 Intake opening protection. Air intake openings that
             spaces within a building intended to be occupied. Mechanical  terminate outdoors shall be protected with corrosion-resistant
             exhaust systems, including exhaust systems serving clothes  screens, louvers or grilles. Openings in louvers, grilles and
             dryers and cooking appliances; hazardous exhaust  systems;  screens shall be sized in accordance with Table 401.5, and
             dust, stock and refuse conveyor systems; subslab soil exhaust  shall be protected against local weather conditions. Louvers
             systems; smoke control systems; energy recovery ventilation  that protect air intake openings in structures located in hurri-
             systems and other systems  specified in Section 502  shall  cane-prone regions, as defined in the International Building
             comply with Chapter 5.                               Code, shall comply  with AMCA 550.  Outdoor air  intake
             401.2 Ventilation required. Every occupied space shall be  openings located in exterior walls shall meet the provisions
             ventilated by natural means in accordance with Section 402  for exterior wall opening protectives in accordance with the
             or by mechanical means in accordance with Section 403.  International Building Code.
             Where the air infiltration rate in a dwelling unit is less than 5        TABLE 401.5
             air changes per hour when tested with a blower door at a pres-  OPENING SIZES IN LOUVERS, GRILLES
             sure  of 0.2-inch water  column (50 Pa) in accordance  with  AND SCREENS PROTECTING AIR INTAKE OPENINGS
             Section R402.4.1.2 of the International Energy Conservation                     MINIMUM AND MAXIMUM
             Code, the dwelling unit shall be ventilated by mechanical  OUTDOOR OPENING TYPE  OPENING SIZES IN LOUVERS,
                                                                                                              a
                                                                                             GRILLES AND SCREENS
             means in accordance with Section  403. Ambulatory care  Intake openings in
                                                                                                            1
                                                                                               1
             facilities and Group I-2 occupancies  shall be ventilated by  residential occupancies   Not <  / inch and not >  /  inch
                                                                                                4
                                                                                                             2
             mechanical means in accordance with Section 407.
                                                                   Intake openings in other   1
             401.3 When required. Ventilation shall be provided during  than residential occupancies   >  /  inch and not > 1 inch
                                                                                               4
             the periods that the room or space is occupied.
                                                                  For SI: 1 inch = 25.4 mm.
             401.4  Intake  opening  location. Air intake openings shall  a. For rectangular openings, the table requirements apply to the shortest side.
             comply with all of the following:                      For round openings, the table requirements apply to the  diameter. For
               1. Intake openings shall be located not less than 10 feet  square openings, the table requirements apply to any side.
                  (3048 mm) from lot lines or buildings on the same lot.  401.6  Contaminant  sources. Stationary local  sources pro-
                                                                  ducing airborne particulates, heat, odors, fumes, spray,
               2. Mechanical and gravity outdoor  air intake  openings
                  shall be located not less than 10 feet (3048 mm) hori-  vapors, smoke or gases in such quantities as to be irritating or
                  zontally from any hazardous or noxious contaminant  injurious to health shall be provided with an exhaust system
                  source, such as vents, streets, alleys, parking lots and  in accordance with Chapter 5 or a means of collection and
                  loading docks, except as specified in Item 3 or Section  removal of the contaminants. Such exhaust shall discharge
                  501.3.1. Outdoor air intake openings shall be permitted  directly to an approved location at the exterior of the build-
                  to be located less than 10 feet (3048 mm) horizontally  ing.
                  from streets, alleys, parking lots and loading docks pro-
                  vided that the openings are located not less than 25 feet
                  (7620 mm) vertically above such locations.  Where                 SECTION 402
                  openings front on a street or public way, the distance       NATURAL VENTILATION
                  shall be measured from the closest edge of the street or  [BG]  402.1  Natural  ventilation.  Natural  ventilation of an
                  public way.                                     occupied space shall be through windows, doors, louvers or
               3. Intake  openings shall  be located  not less than 3 feet  other openings to the outdoors. The operating mechanism for
                  (914 mm) below contaminant sources where such   such openings shall be provided with ready access so that the
                  sources are located within 10 feet (3048 mm)  of the  openings are readily controllable by the building occupants.
                  opening.                                        [BG] 402.2 Ventilation area required. The minimum open-
               4. Intake  openings on structures in flood hazard  areas  able area to the outdoors shall be 4 percent of the floor area
                  shall be at or above the elevation required by Section  being ventilated.

             2018 INTERNATIONAL MECHANICAL CODE                                                                  31
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   43   44   45   46   47   48   49   50   51   52   53