Page 51 - 2018_IMC
P. 51

VENTILATION




                          zone by  other means. For design         403.3.1.2  Exhaust  ventilation.  Exhaust airflow rate
                          purposes,  V shall  be the zone design   shall be provided in accordance with the requirements
                                    pz
                          primary airflow rate, except for zones   of Table 403.3.1.1. Outdoor air introduced into a space
                          with variable air volume supply and V pz  by an exhaust system shall be considered as contribut-
                          shall be the lowest expected primary     ing to the outdoor airflow required by Table 403.3.1.1.
                          airflow rate to the zone when it is fully  403.3.1.3 System operation. The minimum flow rate
                          occupied.                                of outdoor air that the ventilation system must be capa-
                     403.3.1.1.2.3.2 System ventilation efficiency.  ble of supplying during its operation shall be permitted
                     The system ventilation efficiency (E ) shall be  to be based on the rate per person indicated in Table
                                                  v
                     determined using Table 403.3.1.1.2.3.2 or     403.3.1.1 and the actual number of occupants present.
                     Appendix A of ASHRAE 62.1.
                                                                   403.3.1.4 Variable air volume system control. Vari-
                         TABLE 403.3.1.1.2.3.2                     able air volume air distribution  systems, other  than
                   SYSTEM VENTILATION EFFICIENCY a,b
                                                                   those designed to supply only 100-percent outdoor air,
                  Max (Z p )                 E v
                                                                   shall be provided with controls to regulate the flow of
                    0.15                    1                     outdoor air. Such control system shall be designed to
                    0.25                    0.9                   maintain the flow rate of outdoor air at a rate of not less
                                                                   than that required by Section 403.3 over the entire
                    0.35                    0.8
                                                                   range of supply air operating rates.
                    0.45                    0.7
                                                                   403.3.1.5  Balancing.  The  ventilation air distribution
                    0.55                    0.6
                                                                   system shall be provided with means to adjust the sys-
                    0.65                    0.5                   tem to achieve not less than the minimum ventilation
                    0.75                    0.4                   airflow  rate  as required by Sections  403.3 and
                                                                   403.3.1.2. Ventilation systems shall be balanced by an
                   > 0.75                    0.3
                                                                   approved method. Such balancing shall verify that the
         a. Max (Z ) is the largest value of Z  calculated using Equation 4-5 among all
                               p
               p                                                   ventilation system is capable of supplying and exhaust-
           the zones served by the system.
                                                                   ing the airflow rates required by Sections 403.3 and
         b. Interpolating between table values shall be permitted.
                     403.3.1.1.2.3.3  Uncorrected  outdoor  air    403.3.1.2.
                     intake.  The uncorrected outdoor  air  intake  403.3.2 Group R-2, R-3 and R-4 occupancies, three sto-
                     flow rate (V ) shall be determined in accor-  ries  and  less. The design  of local exhaust systems and
                               ou
                     dance with Equation 4-6.                    ventilation systems for outdoor air in Group R-2, R-3 and
                     V ou  =  D all zones R P +  all zones R A z  R-4  occupancies three stories  and less  in height above
                                      z
                                                 a
                                    p
                                                                 grade plane shall comply with Sections 403.3.2.1 through
                                              (Equation 4-6)     403.3.2.5.
                                                                   403.3.2.1 Outdoor air for dwelling units. An outdoor
                                                                   air ventilation system consisting of a  mechanical
                     where:
                                                                   exhaust system, supply system or combination thereof
                     D = Occupant diversity: the ratio of  the     shall be installed for each dwelling unit. Local exhaust
                          system population  to  the sum of  the   or  supply systems, including  outdoor air ducts con-
                          zone   populations,  determined  in      nected to the return side of an air handler, are permitted
                          accordance with Equation 4-7.
                                                                   to serve as such a system. The outdoor air ventilation
                             P                                     system shall be designed to provide the required rate of
                              s
                     D =  ------------------------  (Equation 4-7)  outdoor air continuously during the period that the
                           all zones P z                          building is occupied. The minimum continuous outdoor
                     where:                                        airflow  rate shall be determined in accordance with
                                                                   Equation 4-9.
                     P = System population: The total number of
                      s
                          occupants in the area served  by the
                          system. For design purposes, P  shall be  Q OA =  0.01A floor  7.5 N + +  br  1  (Equation 4-9)
                                                   s
                          the maximum number of  occupants
                          expected to be concurrently in all zones  where:
                          served by the system.                    Q
                     403.3.1.1.2.3.4 Outdoor air intake flow rate.  OA   = outdoor airflow rate, cfm
                     The outdoor air intake flow rate (V ) shall be  A floor  = floor area, ft 2
                                                  ot
                     determined in accordance with Equation 4-8.   N br  = number of bedrooms; not to be less than one
                           V                                         Exception: The outdoor air ventilation system is not
                            ou
                     V ot  =  --------        (Equation 4-8)         required to  operate  continuously where the system
                            E
                             v
                                                                     has controls that enable operation for not less than 1
                                                                     hour of each 4-hour period. The average outdoor air-
         34                                                                  2018 INTERNATIONAL MECHANICAL CODE 
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   46   47   48   49   50   51   52   53   54   55   56