Page 86 - 2018_IFGC
P. 86

GAS PIPING INSTALLATIONS



             where the  piping  is encased in a conduit of wrought iron,    adapter risers that are installed in accordance
             plastic pipe, steel pipe, a piping or encasement system listed  with the manufacturer’s instructions.
             for installation beneath buildings, or other approved conduit  2. Plastic pipe shall be permitted to terminate with a
             material designed to withstand the superimposed loads. The     wall head adapter within buildings where the
             conduit shall be protected from corrosion in accordance with   plastic pipe is inserted  in a  piping material  for
             Section 404.11 and shall be installed in accordance with Sec-  fuel gas use in buildings.
             tion 404.14.1 or 404.14.2.
                                                                         3. Plastic  pipe shall be permitted under  outdoor
               404.14.1 Conduit with one end terminating outdoors.          patio, walkway and driveway slabs provided that
               The conduit shall extend into an occupiable portion of the   the burial depth complies with Section 404.12.
               building and, at the point where the conduit terminates in
               the building, the space between the conduit  and the  gas  404.17.2 Connections. Connections  made outdoors and
               piping shall be sealed to prevent the possible entrance of  underground between metallic and plastic piping shall be
               any gas leakage. The conduit shall extend not less than 2  made only with transition fittings conforming to ASTM
               inches (51 mm) beyond the point where the pipe emerges  D2513 Category I or ASTM F1973.
               from the floor. Where the end sealing is capable of with-  404.17.3 Tracer. A yellow insulated copper tracer wire or
               standing the full pressure of the gas pipe, the conduit shall  other  approved conductor, or a product specifically
               be designed for the same pressure as the pipe. Such con-  designed for that purpose,  shall be installed adjacent to
               duit shall extend not less than 4 inches (102 mm) outside  underground nonmetallic piping. Access shall be provided
               of the building, shall be vented above grade to the out-  to the tracer wire or the tracer wire shall terminate above
               doors and shall be installed so as to prevent the entrance of  ground at each end of the nonmetallic piping. The tracer
               water and insects.                                    wire size shall be not less than 18 AWG and the insulation
                                                                     type shall be suitable for direct burial.
               404.14.2 Conduit with both ends terminating indoors.
               Where the conduit originates and terminates within the  404.18 Pipe cleaning. The use of a flammable or combusti-
               same building, the conduit shall originate and terminate in  ble gas to clean or remove debris from a piping system shall
               an accessible portion of  the building and  shall  not  be  be prohibited.
               sealed. The conduit shall extend not less than 2 inches (51  404.19 Prohibited  devices. A device shall not be placed
               mm) beyond the point where the pipe emerges from the  inside the  piping  or fittings  that will  reduce the cross-sec-
               floor.                                             tional area or otherwise obstruct the free flow of gas.
             404.15 Outlet closures. Gas outlets that do not connect to  Exceptions:
             appliances shall be capped gas tight.
                                                                       1. Approved gas filters.
               Exception: Listed and labeled flush-mounted-type quick-  2. An approved fitting or device where the gas piping
               disconnect devices and listed and labeled gas convenience  system has been sized to accommodate the pressure
               outlets shall be installed in accordance with the manufac-  drop of the fitting or device.
               turer’s instructions.
                                                                  404.20 Testing of piping. Before any system of piping is put
             404.16 Location of outlets. The unthreaded portion of piping  in service or concealed, it shall be tested to ensure that it is
             outlets shall extend not less than l inch (25 mm) through fin-  gas tight. Testing, inspection and purging of piping systems
             ished ceilings and walls and where extending through floors
                                                                  shall comply with Section 406.
             or outdoor patios and slabs, shall be not less than 2 inches (51
             mm) above them. The outlet fitting or piping shall be securely
             supported. Outlets shall not be placed behind doors. Outlets        SECTION 405 (IFGS)
             shall be located in the room or space where the appliance is  PIPING BENDS AND CHANGES IN DIRECTION
             installed.
                                                                  405.1 General. Changes in direction of pipe shall be permit-
               Exception: Listed and labeled flush-mounted-type quick-
                                                                  ted to be made by the use of fittings, factory bends or field
               disconnect devices and listed and labeled gas convenience  bends.
               outlets shall be installed in accordance with the manufac-
               turer’s instructions.                              405.2 Metallic pipe. Metallic pipe bends shall comply with
                                                                  the following:
             404.17 Plastic  pipe.  The  installation of plastic pipe shall
             comply with Sections 404.17.1 through 404.17.3.         1. Bends shall be made only with bending tools and pro-
                                                                       cedures intended for that purpose.
               404.17.1 Limitations. Plastic pipe shall be installed out-
                                                                     2. Bends shall be smooth and free from buckling, cracks
               doors underground  only. Plastic  pipe shall not  be  used
                                                                       or other evidence of mechanical damage.
               within or under any building or slab or be operated at pres-
               sures greater than 100 psig (689 kPa) for natural gas or 30  3. The longitudinal weld of the pipe shall be near the neu-
               psig (207 kPa) for LP-gas.                              tral axis of the bend.
                  Exceptions:                                        4. Pipe shall not be bent through an arc of more than 90
                                                                       degrees (1.6 rad).
                    1. Plastic pipe shall be permitted to terminate above
                       ground outside of buildings  where  installed  in  5. The inside radius of a bend shall be not less than six
                       premanufactured anodeless risers or service head  times the outside diameter of the pipe.



             2018 INTERNATIONAL FUEL GAS CODE ®                                                                   73
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   81   82   83   84   85   86   87   88   89   90   91