GAS PIPING INSTALLATIONS



         410.2 MP regulators. MP pressure regulators shall comply  410.5  Flashback arrestor check valve.  Where fuel  gas is
         with the following:                                  used with oxygen in any hot work operation, a listed protective
           1. The MP regulator shall be approved and shall be suit-  device that serves  as a  combination  flashback arrestor and
              able for the inlet and outlet gas pressures for the appli-  backflow check valve shall be installed at an approved location
              cation.                                         on both the fuel gas and oxygen supply lines. Where the pres-
                                                              sure of the piped fuel gas supply is insufficient to ensure such
           2. The MP regulator shall maintain a reduced outlet pres-  safe operation, approved equipment shall be installed between
              sure under lock-up (no-flow) conditions.
                                                              the gas meter and the appliance that increases pressure to the
           3. The capacity of the MP regulator, determined by pub-  level required for such safe operation.
              lished ratings of its manufacturer, shall be adequate to
              supply the appliances served.
                                                                             SECTION 411 (IFGC)
           4. The MP pressure regulator shall be provided with
              access. Where located indoors, the regulator shall be   APPLIANCE AND MANUFACTURED
              vented to the outdoors or shall be equipped with a leak-      HOME CONNECTIONS
              limiting device, in either case complying with Section  411.1 Connecting appliances. Except as required by Section
              410.3.                                          411.1.1, appliances shall be connected to the piping system
           5. A tee fitting with one opening capped or plugged shall  by one of the following:
              be installed between the MP regulator and its upstream  1. Rigid metallic pipe and fittings.
              shutoff valve. Such  tee fitting shall be positioned  to  2. Corrugated stainless steel tubing (CSST) where
              allow connection of a pressure-measuring instrument  installed in accordance with the manufacturer’s instruc-
              and to serve as a sediment trap.                     tions.
           6. A tee fitting with one opening capped or plugged shall  3. Semirigid metallic tubing and metallic fittings. Lengths
              be installed not less than 10 pipe diameters downstream  shall not exceed 6 feet (1829 mm) and shall be located
              of the MP regulator outlet. Such tee fitting shall  be  entirely in the same room as the appliance. Semirigid
              positioned to allow connection of a pressure-measuring  metallic tubing shall not enter a motor-operated appli-
              instrument. The tee fitting is not required where the MP  ance through an unprotected knockout opening.
              regulator serves  an appliance  that has a  pressure test
              port on the gas control inlet side and the appliance is  4. Listed and labeled appliance connectors in compliance
              located in the same room as the MP regulator.        with ANSI Z21.24/CGA 6.10 and installed in accor-
                                                                   dance with the manufacturer’s instructions and located
           7. Where connected to  rigid piping,  a union shall be  entirely in the same room as the appliance.
              installed within 1 foot (304 mm) of either side of the
              MP regulator.                                      5. Listed and labeled  quick-disconnect devices used  in
                                                                   conjunction with listed and labeled appliance connec-
         410.3 Venting of regulators. Pressure regulators that require  tors.
         a vent shall be vented directly to the outdoors. The vent shall
         be designed to prevent the entry of insects, water and foreign  6. Listed and labeled convenience outlets used in conjunc-
         objects.                                                  tion with listed and labeled appliance connectors.
                                                                 7. Listed and labeled  outdoor appliance connectors in
           Exception: A vent to the outdoors is not required for regu-
           lators equipped with  and  labeled for  utilization with  an  compliance with ANSI Z21.75/CSA 6.27 and installed
           approved vent-limiting device installed in accordance with  in accordance with the manufacturer’s instructions.
           the manufacturer’s instructions.                      8. Listed outdoor gas hose connectors in compliance with
                                                                   ANSI Z21.54 used to connect portable outdoor appli-
           410.3.1 Vent piping. Vent  piping for relief vents and
           breather vents  shall be constructed of materials allowed  ances. The gas hose connection shall be made only in
           for gas piping in accordance with Section 403. Vent piping  the outdoor area where the appliance is used, and shall
           shall be not smaller than the vent connection on the pres-  be to  the  gas piping  supply  at an appliance shutoff
           sure-regulating device. Vent  piping serving relief  vents  valve, a  listed  quick-disconnect device or listed  gas
           and combination relief and breather vents shall be run  convenience outlet.
           independently to the outdoors and shall serve only a single  9. Gas hose connectors for use in laboratories and educa-
           device vent. Vent  piping serving only breather vents is  tional facilities in accordance with Section 411.4.
           permitted to be connected  in a manifold arrangement  411.1.1 Commercial cooking appliances. Commercial
           where sized in accordance with an approved design that  cooking appliances installed on casters and appliances that
           minimizes backpressure in the event of diaphragm rupture.  are moved for cleaning and sanitation  purposes shall  be
           Regulator vent piping shall not exceed the length specified  connected to the piping system with an appliance connec-
           in the regulator manufacturer’s instructions.         tor listed as complying with ANSI Z21.69/CSA 6.16. The
         410.4 Excess flow valves.  Where automatic  excess flow  commercial cooking appliance connector installation shall
         valves are installed, they shall be listed in accordance with  be configured in accordance  with the manufacturer’s
         ANSI Z21.93/CSA 6.30 and shall be sized and installed in  instructions. Movement of appliances with casters shall be
         accordance with the manufacturer’s instructions.        limited by a restraining device installed in accordance with
                                                                 the connector and appliance manufacturer’s instructions.