Page 329 - 2018_IRC
P. 329

WALL CONSTRUCTION



                                               T               HORIZONTAL TOP
                                                               LINTEL REINFORCEMENT
                                                               AS REQUIRED

                                                               MINIMUM NO. 3
                                                               STIRRUP AS REQUIRED
                                                               “C” STIRRUPS ARE
                     D    d  BAR  d BOTTOM BAR                 ACCEPTABLE
                            TOP                               CONCRETE WEB (HIDDEN)

                                                              VERTICAL CONCRETE CORE
            1
           1 / IN.                                             FORM — STAY-IN-PLACE
             2
          MINIMUM                                              OR REMOVABLE
            1
           2 / IN.
             2
          MAXIMUM                              HORIZONTAL BOTTOM LINTEL REINFORCEMENT AS REQUIRED*
                         (a) SINGLE FORM HEIGHT SECTION CUT THROUGH VERTICAL CORE OF A WAFFLE-GRID LINTEL








                                              T
                                                                HORIZONTAL TOP
            1
           1 / IN.                                              LINTEL REINFORCEMENT
             2
          MINIMUM                                               AS REQUIRED*
            1
           2 / IN.
             2
          MAXIMUM                                              MINIMUM NO. 3
                                                               STIRRUP AS REQUIRED
                                                               “C” STIRRUPS ARE
                                                               ACCEPTABLE
                             BAR   BAR
                     D   d      d                             CONCRETE WEB (HIDDEN)
                             TOP   BOTTOM
                                                               FORM — STAY-IN-PLACE
                                                               OR REMOVABLE
                                                               VERTICAL CONCRETE CORE

             1
            1 / IN.                                            HORIZONTAL BOTTOM
              2
           MINIMUM                                             LINTEL REINFORCEMENT
             1
            2 / IN.                                            AS REQUIRED*
              2
          MAXIMUM
                         (b) DOUBLE FORM HEIGHT SECTION CUT THROUGH VERTICAL CORE OF A WAFFLE-GRID LINTEL
                                           *FOR BUNDLED BARS, SEE SECTION R608.8.2.2.
                         NOTE: CROSS HATCHING REPRESENTS THE AREA IN WHICH FORM MATERIAL SHALL BE REMOVED,
                               IF NECESSARY, TO CREATE FLANGES CONTINUOUS THE LENGTH OF THE LINTEL. FLANGES SHALL
                               HAVE A MINIMUM THICKNESS OF 3 IN., AND A MINIMUM WIDTH OF 5 IN. AND 7 IN. IN 6 IN. NOMINAL
                               AND 8 IN. NOMINAL WAFFLE-GRID WALLS, RESPECTIVELY. SEE NOTE a TO TABLES R608.8(6)
                               AND R608.8(10).


         For SI: 1 inch = 25.4 mm.
                                                      FIGURE R608.8(3)
                                              LINTELS FOR WAFFLE-GRID WALLS




         304                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.