P. 368

WALL CONSTRUCTION



                              WHERE CEILING DIAPHRAGM IS NOT PROVIDED,      WHERE CEILING DIAPHRAGM IS NOT PROVIDED,
                             DIAPHRAGM BOUNDARY FASTENING SHALL BE IN       NO. 8 SCREWSAT 6 IN. ON CENTER FROM SHEATHING
                           ACCORDANCE WITH TABLE R804.3. WHERE CEILING      TO RAFTERS WITH TENSION TIESATTACHED.
                           DIAPHRAGM IS PROVIDED, DIAPHRAGM FASTENING       WHERE CEILING DIAPHRAGM IS PROVIDED,
                                  SHALL BE IN ACCORDANCE WITH AISI S230     SCREWS SHALL BE INACCORDANCE WITHAISI S23O.
                          WHERE CEILING DIAPHRAGM IS PROVIDED,
                                   CONTINUOUS STRAP SHALL BE                            3 NO. 8 SCREWS MIN.
                                 IN ACCORDANCE WITH AISI S230                           8 NO. 8 SCREWS EACH
                                                                                        TENSION TIE LOCATION WHERE
                         WHERE CEILING DIAPHRAGM IS NOT                                 NO CEILING DIAPHRAGM IS
                     PROVIDED, 43 MIL MINIMUM BREAK SHAPE                               PROVIDED. SEE SECTION R608.10
                          EACH RAFTER BAY. WHERE CEILING
                      DIAPHRAGM IS PROVIDED BREAK SHAPE
                    SHALL BE IN ACCORDANCE WITH AISI S230
                                                                                            TENSION TIE. SEE TABLE
                 WHERE CEILING DIAPHRAGM IS NOT                                             R608.9(11) FOR SPACING.
                     PROVIDED, 10d COMMON NAILS
                   HORIZONTAL, SPACING TO MATCH
                 DIAPHRAGM BOUNDARY FASTENING    A
               SHALL BE IN ACCORDANCE WITH TABLE
               R602.3(1). WHERE CEILING DIAPHRAGM
                       IS PROVIDED, SEE AISI S230                                NO. 8 SCREWS AT 6 IN. ON CENTER
                                                                                 FROM SHEATHING TO JOISTS WITH
                                          WITH  MIN.                             TENSION TIES ATTACHED.

                                          MIN  WEBMATERIAL  REMOVED  IN.       CEILING DIAPHRAGM WHERE REQUIRED W/43
                                                                               MIL ANGLE, NO. 8 SCREWS TO STEEL, 10d
                                          8IN.  7                              NAILS TO WOOD SILL. SEE TABLE R804.3 FOR
                                                                               DIAPHRAGM BOUNDARY FASTENER SPACING
                                                                               WOOD 2 × 6 MINIMUM SILL PLATE TYPICAL,
                                                                               3 × 6 WHERE REQUIRED BY TABLE R608.9(11)
                                  SECTION
                                                                               ½ IN. DIAMETER ANCHOR BOLT TYPICAL,
                                                                               5 /8 IN. WHERE REQUIRED. SEE TABLE
                                                                               R608.9(11) FOR SIZE AND SPACING
                                                             WOOD SILL
                                                                               CEILING JOIST ABOVE WITH 3- 10d ×
                                                           MINIMUM
                                                                                1½ IN. COMMON NAILS TO WOOD SILL
                                         RAFTER                                TENSION TIE. 4 IN. × 3 IN. × 3 IN. ×
                                         ABOVE             IN.                 43 MIL MINIMUM CLIP ANGLE WITH
                                                           3                   6 NO. 8 SCREWS VERTICAL LEG AND
                                                                               6- 10d × 1½ IN. COMMON NAILS IN
                                                                               HORIZONTAL LEG TENSION TIE
                                                                               LRFD CAPACITY1280 LB

                                                                4IN.
                                                                            ANCHOR BOLT WITH ¼ × 3 × 3
                                                                            STEEL PLATE WASHER





                                                              EQ. EQ.







                              DETAIL A – PLAN VIEW


             For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound-force = 4.448 N.


                                                         FIGURE R608.9(11)
                              COLD-FORMED STEEL ROOF TO TOP OF CONCRETE WALL, FRAMING PERPENDICULAR

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               343