P. 370

WALL CONSTRUCTION









                                                     BLOCKING AT GABLE END                 PROVIDE SCREWS FROM
                                                     BRACE. 2 BAYS MINIMUM.                SHEATHING TO BLOCKING
                                                                                           6 IN. MAXIMUM ON CENTER






                                                       NO. 8 SCREWS, SPACING
                                                       TO MATCH DIAPHRAGM
                                                       BOUNDARY. SEE
                                                       TABLE R804.3
                                                                     43 MIL MINIMUM FULL DEPTH BLOCKING, TWO BAYS MINIMUM
                                                                     AT EACH TENSION TIE. PROVIDE 43 MIL MINIMUM CLIP ANGLE
                                                                     EACH END WITH NOT LESS THAN 4 NO. 8 SCREWS EACH LEG.
                                                                     SEE ALTERNATE BLOCKING CONNECTION BELOW
                   B
                                                                                                         FLAT OR
                                                                                                         FULL DEPTH
                                                                                                         BLOCKING
                                                                                                         AT STRAP

                           WITH

                           MINIMUM  MATERIAL  REMOVED  MIN.  IN.  TENSION TIE. SEE TABLE R608.9(12) FOR SPACING. 54 MIL ×
                                                               2 IN. × 6 FT LENGTH MINIMUM GRADE 50 STRAP UNDER OR
                                                               ON TOP OF CEILING SHEATHING. EXTEND STRAP UNDER AND
                           IN.  WEB  7                         ATTACH TO TRACK WITH MINIMUM 4 NO. 8 SCREWS. ATTACH
                                                               STRAP TO FIRST TWO BLOCKS WITH MINIMUM 12 NO. 8 SCREWS.
                           8                                   NO. 8 SCREWS AT 6 IN. ON CENTER FOR BALANCE OF STRAP.
                                                               TENSION TIE LRFD CAPACITY 1600 LB
                    SECTION


                                                                                           5
                43 MIL MINIMUM TRACK                           ½ IN. MINIMUM ANCHOR BOLT TYPICAL, /8 IN. WHERE REQUIRED.
                                                               SEE TABLE R608.9(12) FOR SIZE AND SPACING.
                 4IN. ×3IN.×3×43MIL
                  MINIMUM CLIP ANGLE
                  WITH 6 NO. 8 SCREWS                       TENSION TIE
                       VERTICAL LEG                                                JOISTS
                                                            STRAP UNDER
                                                            BLOCKING
                                                              BLOCKING


                   ANCHOR BOLT WITH
                 ½ × 4 × 4 STEEL PLATE
                   WASHER. SEE TABLE                                          ALTERNATE END
                R608.9(12) FOR SPACING                                        CONNECTION WITH
                                                                              BENT BLOCKING
                                                                              WEB AND 4
                                                                              NO. 8 SCREWS
                                                                              EACH END
                    DETAIL B – PLAN VIEW



             For SI: 1 mil = 0.0254 mm, 1 inch = 25.4 mm, 1 pound-force = 4.448 N.


                                                         FIGURE R608.9(12)
                                COLD-FORMED STEEL ROOF TO TOP OF CONCRETE WALL, FRAMING PARALLEL


             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               345