FUEL GAS


                       SECTION G2442 (618)                                      hood in the same room or space or the
                FORCED-AIR WARM-AIR FURNACES                                    combustion  chamber  of  any  atmo-
                                                                                spheric  burner  appliance  in  the  same
         G2442.1  (618.1)  General.  Forced-air  warm-air  furnaces
         shall be tested in accordance with ANSI Z21.47/CSA 2.3 or              room or space.
         UL 795 and shall be installed in accordance with the manu-     3. Rooms or spaces containing solid fuel-burning
         facturer’s instructions.                                         appliances, provided that return-air inlets are

         G2442.2  (618.2)  Dampers.  Volume  dampers  shall  not  be      located not less than 10 feet (3048 mm) from
         placed in the air inlet to a furnace in a manner that will reduce  the firebox of such appliances.
         the required air to the furnace.                        6. A closet, bathroom, toilet room, kitchen, garage, boiler
         G2442.3 (618.3) Prohibited sources. Outdoor or return air  room, furnace room or unconditioned attic.
         for forced-air heating and cooling systems shall not be taken  Exceptions:
         from the following locations:
                                                                        1. Where return air intakes are located not less
           1. Closer than 10 feet (3048 mm) from an appliance vent        than 10 feet (3048 mm) from cooking appli-
              outlet, a vent opening from a plumbing drainage system      ances and serve only the kitchen area, taking
              or the discharge outlet of an exhaust fan, unless the out-  return air from a kitchen area shall not be pro-
              let is 3 feet (914 mm) above the outside air inlet.         hibited.
           2. Where  there  is  the  presence  of  objectionable  odors,  2. Dedicated  forced-air  systems  serving  only  a
              fumes or flammable vapors; or where located less than       garage shall not be prohibited from obtaining
              10 feet (3048 mm) above the surface of any abutting         return air from the garage.
              public way or driveway; or where located at grade level
              by a sidewalk, street, alley or driveway.          7.  A  crawl  space  by  means  of  direct  connection  to  the
                                                                   return side of a forced-air system. Transfer openings in
           3. A  hazardous  or  insanitary  location  or  a  refrigeration  the crawl space enclosure shall not be prohibited.
              machinery  room  as  defined  in  the  International
              Mechanical Code.                                G2442.4 (618.4) Screen. Required outdoor air inlets shall be
                                                              covered with a screen having  / -inch (6.4 mm) openings.
                                                                                      1
           4. A room or space, the volume of which is less than 25                     4
              percent  of  the  entire  volume  served  by  such  system.  G2442.5 (618.5) Return-air limitation. Return air from one
              Where  connected  by  a  permanent  opening  having  an  dwelling unit shall not be discharged into another dwelling unit.
              area  sized  in  accordance  with  this  code,  adjoining  G2442.6 (618.6) Furnace plenums and air ducts. Where a
              rooms or spaces shall be considered to be a single room  furnace is installed so that supply ducts carry air circulated by
              or space for the purpose of determining the volume of  the furnace to areas outside of the space containing the fur-
              such rooms or spaces.                           nace, the return air shall be handled by a duct(s) sealed to the
                Exception: The minimum volume requirement shall  furnace casing and terminating outside of the space contain-
                not apply where the amount of return air taken from  ing the furnace.
                a room or space is less than or equal to the amount
                of supply air delivered to such room or space.
                                                                            SECTION G2443 (619)
           5. A room or space containing an appliance where such a         CONVERSION BURNERS
              room or space serves as the sole source of return air.
                                                              G2443.1  (619.1)  Conversion  burners.  The  installation  of
                Exception: This shall not apply where:        conversion burners shall conform to ANSI Z21.8.
                   1. The appliance is a direct-vent appliance or an
                     appliance not requiring a vent in accordance
                     with Section G2425.8.                                  SECTION G2444 (620)
                   2. The room or space complies with the follow-              UNIT HEATERS
                     ing requirements:                        G2444.1  (620.1)  General.  Unit heaters  shall  be  tested  in
                                                              accordance with ANSI Z83.8/CSA 2.6 and shall be installed
                       2.1. The  return  air  shall  be  taken  from  a
                           room  or  space  having  a  volume  in accordance with the manufacturer’s instructions.
                           exceeding  1  cubic  foot  for  each  10  G2444.2 (620.2) Support. Suspended-type unit heaters shall
                           Btu/h (9.6 L/W) of combined input rat-  be supported by elements that are designed and constructed to
                           ing  of  all  fuel-burning  appliances  accommodate  the  weight  and  dynamic  loads.  Hangers  and
                           therein.                           brackets shall be of noncombustible material.
                       2.2. The  volume  of  supply  air  discharged  G2444.3 (620.3) Ductwork. Ducts shall not be connected to
                           back  into  the  same  space  shall  be  a unit heater unless the heater is listed for such installation.
                           approximately equal to the volume of
                           return air taken from the space.   G2444.4  (620.4)  Clearance.  Suspended-type  unit heaters
                                                              shall be installed with clearances to combustible materials of
                       2.3. Return-air  inlets  shall  not  be  located  not less than 18 inches (457 mm) at the sides, 12 inches (305
                           within  10  feet  (3048  mm)  of  a  draft  mm) at the bottom and 6 inches (152 mm) above the top where

         612                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®