Page 638 - 2018_IRC
P. 638

FUEL GAS



             the unit heater has an internal draft hood or 1 inch (25 mm)       SECTION G2446 (622)
             above the top of the sloping side of the vertical draft hood.    VENTED ROOM HEATERS
               Floor-mounted-type  unit heaters  shall  be  installed  with  G2446.1  (622.1)  General.  Vented room  heaters  shall  be
             clearances to combustible materials at the back and one side  tested in accordance with ANSI Z21.86/CSA 2.32, shall be
             only of not less than 6 inches (152 mm). Where the flue gases  designed and equipped as specified in Section G2432.2 and
             are vented horizontally, the 6-inch (152 mm) clearance shall be  shall  be  installed  in  accordance  with  the  manufacturer’s
             measured from the draft hood or vent instead of the rear wall of  instructions.
             the unit heater. Floor-mounted-type unit heaters shall not be
             installed on combustible floors unless listed for such installa-
             tion.                                                              SECTION G2447 (623)
                                                                               COOKING APPLIANCES
               Clearances for servicing all unit heaters shall be in accor-
             dance with the manufacturer’s installation instructions.  G2447.1  (623.1)  Cooking  appliances.  Cooking  appliances
                                                                  that are designed for permanent installation, including ranges,
               Exception: Unit heaters listed for reduced clearance shall  ovens, stoves, broilers, grills, fryers, griddles, hot plates and
               be permitted to be installed with such clearances in accor-  barbecues, shall be tested in accordance with ANSI Z21.1 or
               dance with their listing and the manufacturer’s instructions.  ANSI Z21.58/CSA 1.6 and shall be installed in accordance
                                                                  with the manufacturer’s instructions.
                           SECTION G2445 (621)                    G2447.2  (623.2)  Prohibited  location.  Cooking  appliances
                        UNVENTED ROOM HEATERS                     designed,  tested,  listed  and  labeled  for  use  in  commercial
                                                                  occupancies  shall  not  be  installed  within  dwelling  units  or
             G2445.1 (621.1) General. Unvented room heaters shall be  within any area where domestic cooking operations occur.
             tested  in  accordance  with  ANSI  Z21.11.2  and  shall  be
             installed in accordance with the conditions of the listing and  Exceptions:
             the manufacturer’s instructions.                          1. Appliances that are also listed as domestic cooking
                                                                         appliances.
             G2445.2  (621.2)  Prohibited  use.  One  or  more  unvented
             room heaters shall not be used as the sole source of comfort  2. Where the installation is designed by a licensed Pro-
             heating in a dwelling unit.                                 fessional Engineer, in compliance with the manufac-
             G2445.3 (621.3) Input rating. Unvented room heaters shall   turer’s installation instructions.
             not have an input rating in excess of 40,000 Btu/h (11.7 kW).  G2447.3 (623.3) Domestic appliances. Cooking appliances
             G2445.4  (621.4)  Prohibited  locations.  The  location  of  installed within dwelling units and within areas where domes-
             unvented room heaters shall comply with Section G2406.2.  tic  cooking  operations  occur  shall  be  listed  and  labeled  as
                                                                  household-type appliances for domestic use.
             G2445.5  (621.5)  Room  or  space  volume.  The  aggregate
             input rating of all unvented appliances installed in a room or  G2447.4  (623.4)  Range  installation.  Ranges  installed  on
                                                           3
             space shall not exceed 20 Btu/h per cubic foot (207 W/m ) of  combustible floors shall be set on their own bases or legs and
             volume of such room or space. Where the room or space in  shall be installed with clearances of not less than that shown
             which  the  appliances  are  installed  is  directly  connected  to  on the label.
             another room or space by a doorway, archway or other open-  G2447.5  (623.7)  Vertical  clearance  above  cooking  top.
             ing of comparable size that cannot be closed, the volume of  Household  cooking  appliances  shall  have  a  vertical  clear-
             such adjacent room or space shall be permitted to be included  ance above the cooking top of not less than 30 inches (760
             in the calculations.                                 mm) to combustible material and metal cabinets. A minimum
                                                                  clearance of 24 inches (610 mm) is permitted where one of
             G2445.6 (621.6) Oxygen-depletion safety system. Unvented
             room heaters  shall  be  equipped  with  an  oxygen-depletion-  the following is installed:
             sensitive safety shutoff system. The system shall shut off the  1. The underside of the combustible material or metal cab-
             gas supply to the main and pilot burners when the oxygen in  inet above the cooking top is protected with not less than
             the surrounding atmosphere is depleted to the percent con-  1 / -inch  (6.4  mm)  insulating  millboard  covered  with
                                                                        4
             centration specified by the manufacturer, but not lower than  sheet metal not less than 0.0122 inch (0.3 mm) thick.
             18 percent. The system shall not incorporate field adjustment  2. A metal ventilating hood constructed of sheet metal not
             means capable of changing the set point at which the system  less than 0.0122 inch (0.3 mm) thick is installed above
             acts to shut off the gas supply to the room heater.
                                                                                                                  1
                                                                       the  cooking  top  with  a  clearance  of  not  less  than  / 4
             G2445.7  (621.7)  Unvented  decorative  room  heaters.  An  inch (6.4 mm) between the hood and the underside of
             unvented decorative room heater shall not be installed in a  the  combustible material  or  metal  cabinet.  The  hood
             factory-built fireplace unless the  fireplace system has been  shall have a width not less than the width of the appli-
             specifically tested, listed and labeled for such use in accor-  ance and shall be centered over the appliance.
             dance with UL 127.
                                                                     3. A  listed  cooking  appliance  or  microwave  oven  is
               G2445.7.1 (621.7.1) Ventless firebox enclosures. Vent-  installed over a listed cooking appliance and in compli-
               less firebox enclosures used with unvented decorative room  ance with the terms of the manufacturer’s installation
               heaters shall be listed as complying with ANSI Z21.91.  instructions for the upper appliance.

             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               613
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.