Page 715 - 2018_IRC
P. 715

GENERAL REQUIREMENTS



         E3404.12 Field-applied hazard markings. Where caution,      2,  The  width  of  the  working  space  shall  be  the
         warning, or danger signs or labels are required by this code,   width  of  the  equipment  enclosure  or  not  less
         the labels shall meet the following requirements:               than 30 inches (762 mm), whichever is greater.
           1. The marking shall warn of the hazard using effective   3.  Enclosure  doors  and  hinged  panels  shall  be
              words, colors, symbols or any combination thereof.         capable of opening not less than 90 degrees.
           2. Labels shall be permanently affixed to the equipment or  4.  The space in front of the enclosure shall comply
              wiring method.                                             with  the  depth  requirements  of  Table
                                                                         110.26(A)(1)  of  NFPA  70.  The  maximum
           3. Labels shall not be hand written except for portions of
              labels  or markings  that are  variable, or that  could  be  height of the working space shall be the height
              subject to changes. Labels shall be legible.               necessary to install the equipment in the limited
                                                                         space. A horizontal ceiling structural member or
           4. Labels shall be of sufficient durability to withstand the  access  panel  shall  be  permitted  in  this  space.
              environment involved. [110.21(B)]                          [110.26(A) (1), (2), (3), (4)]
         E3404.13 Identification of disconnecting means. Each dis-  Exceptions:
         connecting means shall be legibly marked to indicate its pur-
         pose, except where located and arranged so that the purpose  1. In  existing  dwelling  units,  service  equipment  and
         is evident. The marking shall have the durability to withstand  panelboards  that  are  not  rated  in  excess  of  200
         the environment involved. [110.22(A)]                       amperes shall be permitted in spaces where the height
                                                                     of the working space is less than 6.5 feet (1981 mm).
                                                                     [110.26(A)(3) Exception No. 1]
                          SECTION E3405                            2. Meters that are installed in meter sockets shall be per-
            EQUIPMENT LOCATION AND CLEARANCES                        mitted to extend beyond the other equipment. Meter
         E3405.1 Working space and clearances. Access and work-      sockets shall not be exempt from the requirements of
         ing space shall be provided and maintained around all electri-  this section. [110.26(A)(3) Exception No. 2]
         cal  equipment  to  permit  ready  and  safe  operation  and  E3405.3  Indoor  dedicated  panelboard  space.  The  indoor
         maintenance of such equipment in accordance with this sec-  space  equal  to  the  width  and  depth  of  the  panelboard  and
         tion and Figure E3405.1. (110.26)                    extending from the floor to a height of 6 feet (1829 mm) above
                                                              the panelboard, or to the structural ceiling, whichever is lower,
         E3405.2 Working clearances for energized equipment and
         panelboards. Except as otherwise specified  in Chapters  34  shall be dedicated to the electrical installation. Piping, ducts,
         through 43, the dimension of the working space in the direction  leak protection apparatus and other equipment foreign to the
         of  access  to  panelboards  and  live  parts  of  other  equipment  electrical installation shall not be installed in such dedicated
         likely to require examination, adjustment, servicing or mainte-  space. The area above the dedicated space shall be permitted to
         nance while energized shall be not less than 36 inches (914  contain foreign systems, provided that protection is installed to
         mm) in depth. Distances shall be measured from the energized  avoid damage to the electrical equipment from condensation,
         parts where such parts are exposed or from the enclosure front  leaks and breaks in such foreign systems (see Figure E3405.1).
         or opening where such parts are enclosed. In addition to the 36-  Exception: Suspended ceilings with removable panels shall
         inch dimension (914 mm), the work space shall not be less than  be permitted within the 6-foot (1829 mm) dedicated space.
         30 inches (762 mm) wide in front of the electrical equipment  E3405.4  Outdoor  dedicated  panelboard  space.  The  out-
         and not less than the width of such equipment. The work space  door space equal to the width and depth of the panelboard,
         shall be clear and shall extend from the floor or platform to a  and extending from grade to a height of 6 feet (1829 mm)
         height of 6.5 feet (1981 mm) or the height of the equipment,  above  the  panelboard,  shall  be  dedicated  to  the  electrical
         whichever is greater. In all cases, the work space shall allow at  installation. Piping and other equipment foreign to the electri-
         least a 90-degree (1.57 rad) opening of equipment doors or  cal installation shall not be located in this zone.
         hinged panels. Equipment associated with the electrical instal-
         lation located above or below the electrical equipment shall be  E3405.5  Location  of  working  spaces  and  equipment.
         permitted to extend not more than 6 inches (152 mm) beyond  Required working space shall not be designated for storage.
         the front of the electrical equipment.               Panelboards and overcurrent protection devices shall not be
                                                              located in clothes closets, in bathrooms, or over the steps of a
           Where such equipment is required by installation instruc-  stairway. [110.26(B), 240.24(D), (E), (F)]
         tion or function is located in a space with limited access, all
         of the following shall apply:                        E3405.6 Access and entrance to working space. Access shall
                                                              be provided to the required working space. [110.26(C)(1)]
           1. Where the equipment is installed above a lay-in ceiling,
              there shall be an opening not smaller than 22 inches by  E3405.7  Illumination.  Artificial  illumination  shall  be  pro-
              22 inches (559 mm by 559 mm), or in a crawl space,  vided for all working spaces for service equipment and panel-
              there shall be an accessible opening not smaller than 22  boards  installed  indoors  and  shall  not  be  controlled  by
              inches by 30 inches (559 mm by 762 mm).         automatic means only. Additional lighting outlets shall not be
                                                              required where the work space is illuminated by an adjacent
                                                              light  source  or  as  permitted  by  Exception  1  of  Section
                                                              E3903.2 for switched receptacles. [110.26(D)]



         690                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   710   711   712   713   714   715   716   717   718   719   720