Page 717 - 2018_IRC
P. 717

GENERAL REQUIREMENTS


                          SECTION E3406                       TW, UF, USE, USE-2, XHHW or XHHW-2. Insulation types
          ELECTRICAL CONDUCTORS AND CONNECTIONS               shall be approved for the application. [310.10(B), (C), 310.104]
         E3406.1  General.  This  section  provides  general  require-  E3406.6 Conductors in parallel. Circuit conductors that are
         ments for conductors, connections and splices. These require-  connected in parallel shall be limited to sizes 1/0 AWG and
         ments do not apply to conductors that form an integral part of  larger. Conductors in parallel shall: be of the same length; con-
         equipment,  such  as  motors,  appliances  and  similar  equip-  sist of the same conductor material; be the same circular mil
         ment, or to conductors specifically provided for elsewhere in  area and have the same insulation type. Conductors in parallel
         Chapters 34 through 43. (310.1)                      shall be terminated in the same manner. Where run in separate
         E3406.2  Conductor  material.  Conductors  used  to  conduct  raceways or cables, the raceway or cables shall have the same
         current shall be of copper or aluminum except as otherwise  physical  characteristics.  Where  conductors  are  in  separate
         provided  in  Chapters  34  through  43.  Where  the  conductor  raceways or cables, the same number of conductors shall be
         material is not specified, the material and the sizes given in  used in each raceway or cable. [310.10(H)]
         these chapters shall apply to copper conductors. Where other  E3406.7 Conductors of the same circuit. All conductors of
         materials  are  used,  the  conductor  sizes  shall  be  changed  the same circuit and, where used, the grounded conductor and
         accordingly. (110.5)                                 all equipment grounding conductors and bonding conductors
         E3406.3 Minimum size of conductors. The minimum size of  shall be contained within the same raceway, cable or cord.
         conductors for feeders and branch circuits shall be 14 AWG  [300.3(B)]
         copper and 12 AWG aluminum. The minimum size of service  E3406.8  Aluminum  and  copper  connections.  Terminals
         conductors shall be as specified in Chapter 36. The minimum  and splicing connectors shall be identified for the material of
         size of Class 2 remote control, signaling and power-limited cir-  the conductors joined. Conductors of dissimilar metals shall
         cuits  conductors  shall  be  as  specified  in  Chapter  43.  not be joined in a terminal or splicing connector where physi-
         [310.106(A)]                                         cal contact occurs between dissimilar conductors such as cop-
         E3406.4 Stranded conductors. Where installed in raceways,  per  and  aluminum,  copper  and  copper-clad  aluminum,  or
         conductors 8 AWG and larger shall be stranded. A solid 8  aluminum  and  copper-clad  aluminum,  except  where  the
         AWG conductor shall be permitted to be installed in a race-  device is listed for the purpose and conditions of application.
         way only to meet the requirements of Sections E3610.2 and  Materials such as inhibitors and compounds shall be suitable
         E4204. [310.106(C)]                                  for  the  application  and  shall  be  of  a  type  that  will  not
                                                              adversely  affect  the  conductors,  installation  or  equipment.
         E3406.5 Individual conductor insulation. Except where oth-  (110.14)
         erwise permitted in Sections E3605.1 and E3908.9, and E4303,
         current-carrying conductors shall be insulated. Insulated con-  E3406.9 Fine stranded conductors. Connectors and termi-
         ductors shall have insulation types identified as RHH, RHW,  nals for conductors that are more finely stranded than Class B
         RHW-2, THHN, THHW, THW, THW-2, THWN, THWN-2,         and Class C stranding as shown in Table E3406.9, shall be
                                                              identified for the specific conductor class or classes. (110.14)


                                              TABLE E3406.9 (Chapter 9, Table 10)
                                                  CONDUCTOR STRANDING c
                                                                         NUMBER OF STRANDS
                       CONDUCTOR SIZE
                                                                    Copper                        Aluminum
               AWG or kcmil           mm 2                Class B             Class C              Class B
                 24-30              0.20-0.05             Note a                —                   —
                  22                  0.32                  7                   —                   —
                  20                  0.52                 10                   —                   —
                  18                  0.82                 16                   —                   —
                  16                   1.3                 26                   —                   —
                  14-2               2.1-33.6               7                   19                   7 b
                 1-4/0               42.4-107              19                   37                  19
                250-500              127-253               37                   61                  37
                600-1000             304-508               61                   91                  61
               1250-1500             635-759               91                  127                  91
               1750-2000            886-1016               127                 271                  127
         a. Number of strands vary.
                              2
         b. Aluminum 14 AWG (2.1 mm ) is not available.
         c. With the permission of Underwriters Laboratories, Inc., this material is reproduced from UL Standard 486A-B, Wire Connectors, which is copyrighted by
           Underwriters Laboratories, Inc., Northbrook, Illinois. While use of this material has been authorized, UL shall not be responsible for the manner in which the
           information is presented, nor for any interpretations thereof.

         692                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   712   713   714   715   716   717   718   719   720   721   722