Page 718 - 2018_IRC
P. 718

GENERAL REQUIREMENTS



             E3406.10 Terminals. Connection of conductors to terminal  E3406.14.1  Permitted  methods.  Equipment  grounding
             parts  shall  be  made  without  damaging  the  conductors  and  conductors, grounding electrode conductors, and bonding
             shall be made by means of pressure connectors, including set-  jumpers shall be connected by one or more of the follow-
             screw type, by means of splices to flexible leads, or for con-  ing means:
             ductor sizes of 10 AWG and smaller, by means of wire bind-  1. Listed pressure connectors.
             ing  screws  or  studs  and  nuts  having  upturned  lugs  or  the  2. Terminal bars.
             equivalent. Terminals for more than one conductor and termi-
             nals for connecting aluminum conductors shall be identified  3. Pressure connectors listed as grounding and bonding
             for the application. [110.14(A)]                            equipment.
             E3406.11 Splices. Conductors shall be spliced or joined with  4. Exothermic welding process.
             splicing devices listed for the purpose. Splices and joints and  5. Machine  screw-type  fasteners  that  engage  not  less
             the free ends of conductors shall be covered with an insula-  than two threads or are secured with a nut.
             tion equivalent to that of the conductors or with an insulating  6. Thread-forming machine screws that engage not less
             device  listed  for  the  purpose.  Wire  connectors  or  splicing  than two threads in the enclosure.
             means installed on conductors for direct burial shall be listed
             for such use. [110.14(B)]                                 7. Connections that are part of a listed assembly.
                                                                       8. Other listed means. [250.8 (A)]
               E3406.11.1 Continuity. Conductors in raceways shall be
               continuous between outlets, boxes, and devices and shall  E3406.14.2 Methods not permitted. Connection devices
               be without splices or taps in the raceway.            or fittings that depend solely on solder shall not be used.
                                                                     [250.8 (B)]
                  Exception:  Splices  shall be permitted  within surface-
                  mounted  raceways  that  have  a  removable  cover.
                  [300.13(A)]                                                      SECTION E3407
               E3406.11.2  Device  connections.  The  continuity  of  a  CONDUCTOR AND TERMINAL IDENTIFICATION
               grounded conductor in multiwire branch circuits shall not  E3407.1 Grounded conductors. Insulated grounded conduc-
               be dependent on connection to devices such as receptacles  tors of sizes 6 AWG or smaller shall be identified by a contin-
               and lampholders. The arrangement of grounding connec-  uous white or gray outer finish or by three continuous white or
               tions shall be such that the disconnection or the removal of  gray stripes on other than green insulation along the entire
               a receptacle, luminaire or other device fed from the box  length of the conductors. Conductors of sizes 4 AWG or larger
               does not interfere with or interrupt the grounding continu-  shall be identified either by a continuous white or gray outer
               ity. [300.13(B)]                                   finish or by three continuous white or gray stripes on other
               E3406.11.3 Length of conductor for splice or termina-  than green insulation along its entire length or at the time of
               tion.  Where  conductors  are  to  be  spliced,  terminated  or  installation by a distinctive white or gray marking at its termi-
               connected to fixtures or devices, a minimum length of 6  nations. This marking shall encircle the conductor or insula-
               inches  (152 mm) of free  conductor shall be  provided at  tion. [200.6(A) & (B)]
               each outlet, junction or switch point. The required length  E3407.2  Equipment  grounding  conductors.  Equipment
               shall be measured from the point in the box where the con-  grounding conductors of sizes 6 AWG and smaller shall be iden-
               ductor emerges from its raceway or cable sheath. Where  tified by a continuous green color or a continuous green color
               the opening to an outlet, junction or switch point is less  with one or more yellow stripes on the insulation or covering,
               than 8 inches (200 mm) in any dimension, each conductor  except  where  bare.  Conductors  with  insulation  or  individual
               shall be long enough to extend at least 3 inches (75 mm)  covering that is green, green with one or more yellow stripes, or
               outside of such opening. (300.14)                  otherwise identified as permitted by this section shall not be
             E3406.12  Installation.  Where  a  tightening  torque  is  indi-  used for ungrounded or grounded circuit conductors. (250.119)
             cated  as  a  numeric  value  on  equipment  or  in  installation  Equipment  grounding  conductors  4  AWG  and  larger
             instructions provided by the manufacturer, a calibrated torque  AWG  that  are  not  identified  as  required  for  conductors  of
             tool  shall  be  used  to  achieve  the  indicated  torque  value,  sizes 6 AWG and smaller shall, at the time of installation, be
             except  where  the  equipment  manufacturer  has  provided  permanently identified as an equipment grounding conductor
             installation instructions for an alternative method of achiev-  at each end and at every point where the conductor is accessi-
             ing the required torque. [110.14 (D)]                ble, except where such conductors are bare.
             E3406.13 Grounded conductor continuity. The continuity  The  required  identification  for  conductors  4  AWG  and
             of a grounded conductor shall not depend on connection to a  larger shall encircle the conductor and shall be accomplished
             metallic enclosure, raceway or cable armor. [200.2(B)]  by one of the following:
             E3406.14  Connection  of  grounding  and  bonding  equip-  1. Stripping  the  insulation  or  covering  from  the  entire
             ment.  The  connection  of  equipment  grounding  conductors,  exposed length.
             grounding electrode conductors and bonding jumpers shall be  2. Coloring  the  exposed  insulation  or  covering  green  at
             in accordance with Sections E3406.14.1 and E3406.14.2.    the termination.






             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               693
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   713   714   715   716   717   718   719   720   721   722   723