Page 754 - 2018_IRC
P. 754

POWER AND LIGHTING DISTRIBUTION



               E3901.4.4 Separate spaces. Countertop spaces separated  balcony, deck, or porch. The receptacle shall be located not
               by range tops, refrigerators, or sinks shall be considered as  more than 6 feet, 6 inches (1981 mm) above the balcony, deck,
               separate countertop spaces in applying the requirements of  or porch surface. [210.52(E)]
               Sections E3901.4.1, E3901.4.2 and E3901.4.3.       E3901.8 Laundry areas. Not less than one receptacle outlet
                  Where a range, counter-mounted cooking unit, or sink  shall be installed in areas  designated for the installation of
               is installed in an island or peninsular countertop and the  laundry equipment.
               depth of the countertop behind the range, counter-mounted  E3901.9 Basements, garages and accessory buildings. Not
               cooking unit, or sink is less than 12 inches (305 mm), the  less than one receptacle outlet, in addition to any provided for
               range, counter-mounted cooking unit, or sink has divided  specific equipment, shall be installed in each separate unfin-
               the countertop space into two separate countertop spaces  ished portion of a basement; in each vehicle bay not more than
               as defined in Section E3901.4.4. Each separate countertop  5.5 feet (1676 mm) above the floor in attached garages; in each
               space  shall  comply  with  the  applicable  requirements  of  vehicle bay not more than 5.5 feet (1676 mm) above the floor
               this section. [210.52(C)(4)]                       in detached garages that are provided with electric power and
               E3901.4.5 Receptacle outlet location. Receptacle outlets  in accessory buildings that are provided with electric power.
               shall be located not more than 20 inches (508 mm) above  [210.52(G)(1), (2), and (3)]
               the countertop or work surface. Receptacle outlet assem-  E3901.10 Hallways. Hallways of 10 feet (3048 mm) or more in
               blies installed in countertops and work surfaces shall be  length shall have at least one receptacle outlet. The hall length
               listed for use in countertops or work surfaces. Receptacle  shall be considered the length measured along the centerline of
               outlets rendered not readily accessible by appliances fas-  the hall without passing through a doorway. [210.52(H)]
               tened  in  place,  appliance  garages,  sinks  or  rangetops  as
               addressed in the exception to Section E3901.4.1, or appli-  E3901.11 Foyers. Foyers that are not part of a hallway in accor-
               ances occupying dedicated space shall not be considered  dance  with  Section  E3901.10  and  that  have  an  area  that  is
                                                                                              2
               as these required outlets. [210.52(C)(5)]          greater than 60 square feet (5.57 m ) shall have a receptacle(s)
                                                                  located in each wall space that is 3 feet (914 mm) or more in
                  Exception: Receptacle outlets shall be permitted to be  width. Doorways, door-side windows that extend to the floor,
                  mounted not more than 12 inches (305 mm) below the  and  similar  openings shall not  be  considered as  wall  space.
                  countertop or work surface in construction designed for  [210.52(H)]
                  the  physically  impaired  and  for  island  and  peninsular
                  countertops  or  work  surface  where  the  surface  is  flat  E3901.12 HVAC outlet. A 125-volt, single-phase, 15- or 20-
                  across its entire surface and there are no means to mount  ampere-rated receptacle outlet shall be installed at an accessi-
                  a receptacle within 20 inches (508 mm) above the coun-  ble location for the servicing of heating, air-conditioning and
                  tertop,  such  as  in  an  overhead  cabinet.  Receptacles  refrigeration equipment. The receptacle shall  be located on
                  mounted below the countertop or work surface in accor-  the same level and within 25 feet (7620 mm) of the heating,
                  dance with this exception shall not be located where the  air-conditioning and refrigeration equipment. The receptacle
                  countertop or work surface extends more than 6 inches  outlet shall not be connected to the load side of the HVAC
                  (152 mm) beyond its support base. [210.52(C)(5) Excep-  equipment disconnecting means. (210.63)
                  tion]                                              Exception: A receptacle outlet shall not be required for
             E3901.5 Appliance receptacle outlets. Appliance receptacle  the servicing of evaporative coolers. (210.63 Exception)
             outlets  installed  for  specific  appliances,  such  as  laundry
             equipment, shall be installed within 6 feet (1829 mm) of the
             intended location of the appliance. (210.50(C)]                       SECTION E3902
                                                                          GROUND-FAULT AND ARC-FAULT
             E3901.6 Bathroom. At least one receptacle outlet shall be  CIRCUIT-INTERRUPTER PROTECTION
             installed in bathrooms and such outlet shall be located within
             36 inches (914 mm) of the outside edge of each lavatory basin.  E3902.1 Bathroom receptacles. 125-volt, single-phase, 15-
             The receptacle outlet shall be located on a wall or partition that  and 20-ampere receptacles installed in bathrooms shall have
             is adjacent to the lavatory basin location, located on the coun-  ground-fault  circuit-interrupter  protection  for  personnel.
             tertop, or installed on the side or face of the basin cabinet. The  [210.8(A)(1)]
             receptacle shall be located not more than 12 inches (305 mm)  E3902.2 Garage and accessory building receptacles. 125-
             below the top of the basin or basin countertop.      volt, single-phase, 15- or 20-ampere receptacles installed in
               Receptacle outlet assemblies installed in countertops shall  garages  and  grade-level  portions  of  unfinished  accessory
             be listed for the application. [210.52(D)]           buildings used for storage or work areas shall have ground-
                                                                  fault circuit-interrupter protection for personnel. [210.8(A)(2)]
             E3901.7 Outdoor outlets. Not less than one receptacle outlet
             that is readily accessible from grade level and located not more  E3902.3  Outdoor  receptacles.  125-volt,  single-phase,  15-
             than 6 feet, 6 inches (1981 mm) above grade, shall be installed  and  20-ampere  receptacles  installed  outdoors  shall  have
             outdoors at the front and back of each dwelling unit having  ground-fault  circuit-interrupter  protection  for  personnel.
             direct access to grade level. Balconies, decks, and porches that  [210.8(A)(3)]
             are accessible from inside of the dwelling unit shall have at  Exception:  Receptacles  as  covered  in  Section  E4101.7.
             least one receptacle outlet installed within the perimeter of the  [210.8(A)(3) Exception]



             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               729
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.