Page 756 - 2018_IRC
P. 756

POWER AND LIGHTING DISTRIBUTION



                    4.4. The combination of the branch-circuit overcur-  2. Lighting outlets shall be permitted to be controlled by
                        rent device and outlet branch-circuit AFCI shall  occupancy  sensors  that  are  in  addition  to  wall
                        be identified as meeting the requirements for a  switches,  or  that  are  located  at  a  customary  wall
                        system  combination-type  AFCI  and  shall  be   switch location and equipped with a manual override
                        listed as such. [210.12(A)(4)]                   that will allow the sensor to function as a wall switch.
                                                                         [210.70(A)(1) Exception No. 2]
               5. Where metal outlet boxes and junction boxes and RMC,
                  IMC, EMT, Type MC or steel-armored Type AC cables  E3903.3 Additional locations. At least one wall-switch-con-
                  meeting  the  requirements  of  Section  E3908.8,  metal  trolled lighting outlet shall be installed in hallways, stairways,
                  wireways or metal auxiliary gutters are installed for the  attached garages, and detached garages with electric power. At
                  portion of the branch circuit between the branch-circuit  least  one  wall-switch-controlled  lighting  outlet  shall  be
                  overcurrent  device  and  the  first  outlet,  a  listed  outlet  installed to provide illumination on the exterior side of each
                  branch-circuit type AFCI installed at the first outlet shall  outdoor egress door having grade level access, including out-
                  be considered as providing protection for the remaining  door egress doors for attached garages and detached garages
                  portion of the branch circuit. [210.12(A)(5)]   with electric power. A vehicle door in a garage shall not be con-
                                                                  sidered as an outdoor egress door.
               6. Where a listed metal or nonmetallic conduit or tubing
                  or Type MC cable is encased in not less than 2 inches  E3903.3.1 Stairway lighting outlet control. Where one
                  (50.8 mm) of concrete for the portion of the branch cir-  or more lighting outlets are installed for interior stairways,
                  cuit between the branch-circuit overcurrent device and  there shall be a wall switch at each floor level and landing
                  the first outlet, a listed outlet branch-circuit-type AFCI  level that includes an entryway to control the lighting out-
                  installed at the first outlet shall be considered as provid-  lets  where  the  stairway  between  floor  levels  has  six  or
                  ing protection for the remaining portion of the branch  more risers. Lighting outlets installed to meet this require-
                  circuit. [210.12(A)(6)]                            ment shall not be controlled by the use of dimmer switches
               Exception: AFCI protection is not required for an individ-  except where the dimmer switches provide the full range
               ual  branch  circuit  supplying  only  a  fire  alarm  system  of dimming control at each switch location. [210.70(A)(2)]
               where  the  branch  circuit  is  wired  with  metal  outlet  and  Exception:  In  hallways,  stairways,  and  at  outdoor
               junction  boxes  and  RMC,  IMC,  EMT  or  steel-sheathed  egress doors, remote, central, or automatic  control of
               armored cable Type AC or Type MC meeting the require-   lighting shall be permitted. [210.70(A)(2) Exception]
               ments of Section E3908.8.                          E3903.4 Storage or equipment spaces. In attics, under-floor
             E3902.17  Arc-fault  circuit-interrupter  protection  for  spaces, utility rooms and basements, at least one lighting out-
             branch circuit extensions or modifications. Where branch-  let shall be installed where these spaces are used for storage
             circuit wiring is modified, replaced, or extended in any of the  or contain equipment requiring servicing. Such lighting outlet
             areas specified in Section E3902.16, the branch circuit shall  shall be controlled by a wall switch or shall have an integral
             be protected by one of the following:                switch. At least one point of control shall be at the usual point
                                                                  of entry to these spaces. The lighting outlet shall be provided
               1. A combination-type AFCI located at the origin of the  at or near the equipment requiring servicing. [210.70(A)(3)]
                  branch circuit.
               2. An outlet branch-circuit type AFCI located at the first
                  receptacle  outlet  of  the  existing  branch  circuit.          SECTION E3904
                  [210.12(B)]                                         GENERAL INSTALLATION REQUIREMENTS
               Exception: AFCI protection shall not be required where  E3904.1  Electrical  continuity  of  metal  raceways  and
               the extension of the existing conductors is not more than 6  enclosures.  Metal  raceways,  cable  armor  and  other  metal
               feet (1.8 m) in length and does not include any additional  enclosures  for  conductors  shall  be  mechanically  joined
               outlets or devices. [210.12(B) Exception]          together  into  a  continuous  electric  conductor  and  shall  be
                                                                  connected to all boxes, fittings and cabinets so as to provide
                                                                  effective  electrical  continuity.  Raceways  and  cable  assem-
                              SECTION E3903                       blies shall be mechanically secured to boxes, fittings cabinets
                            LIGHTING OUTLETS                      and other enclosures. (300.10)
             E3903.1 General. Lighting outlets shall be provided in accor-
             dance with Sections E3903.2 through E3903.4. [210.70(A)]  Exception:  Short  sections  of  raceway  used  to  provide
                                                                     cable assemblies with support or protection against physi-
             E3903.2  Habitable  rooms.  At  least  one  wall  switch-con-  cal damage. (300.10 Exception No. 1)
             trolled  lighting  outlet  shall  be  installed  in  every  habitable
             room, kitchen and bathroom. [210.70(A)(1)]           E3904.2 Mechanical continuity—raceways and cables. Race-
                                                                  ways, cable armors and cable sheaths shall be continuous between
               Exceptions:                                        cabinets, boxes, fittings or other enclosures or outlets. (300.12)
                  1. In other than kitchens and bathrooms, one or more  Exception:  Short  sections  of  raceway  used  to  provide
                    receptacles controlled by a wall switch shall be con-  cable assemblies with support or protection against physi-
                    sidered  equivalent  to  the  required  lighting  outlet.  cal damage. (300.12 Exception No. 1)
                    [210.70(A)(1) Exception No. 1]




             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               731
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   751   752   753   754   755   756   757   758   759   760   761