POWER AND LIGHTING DISTRIBUTION


         E3902.4  Crawl  space  receptacles  and  lighting  outlets.  cles, the distance shall be measured as the shortest path the
         Where a crawl space is at or below grade level, 125-volt, sin-  cord of an appliance connected to the receptacle would fol-
         gle-phase,  15-  and  20-ampere  receptacles  installed  in  such  low without piercing a floor, wall, ceiling, or fixed barrier, or
         spaces shall have ground-fault circuit-interrupter protection for  passing through a door, doorway or window. [210.8(A)]
         personnel. Lighting outlets not exceeding 120 volts shall have  E3902.15 Location of arc-fault circuit-interrupters. Arc-
         ground-fault  circuit-interrupter  protection.  [210.8(A)(4),  fault circuit-interrupters shall be installed in readily accessi-
         2108(E)]                                             ble locations.
         E3902.5 Unfinished basement receptacles. 125-volt, single-  E3902.16 Arc-fault circuit-interrupter protection. Branch
         phase, 15- and 20-ampere receptacles installed in unfinished  circuits  that  supply  120-volt,  single-phase,  15-  and  20-
         basements shall have ground-fault circuit-interrupter protec-  ampere  outlets  installed  in  kitchens,  family  rooms,  dining
         tion  for personnel. For  purposes of this section,  unfinished  rooms, living rooms, parlors, libraries, dens, bedrooms, sun-
         basements are defined as portions or areas of the basement not  rooms,  recreations  rooms,  closets,  hallways,  laundry  areas
         intended as habitable rooms. [210.8(A)(5)]           and similar rooms or areas shall be protected by any of the
           Exception:  A  receptacle  supplying  only  a  permanently  following: [210.12(A)]
           installed fire alarm or burglar alarm system. Receptacles  1. A listed combination-type arc-fault circuit-interrupter,
           installed  in  accordance  with  this  exception  shall  not  be  installed to provide protection of the entire branch cir-
           considered  as  meeting  the  requirement  of  Section  cuit. [210.12(A)(1)]
           E3901.9. [210.8(A)(5) Exception]
                                                                 2. A listed branch/feeder-type AFCI installed at the origin
         E3902.6  Kitchen  receptacles.  125-volt,  single-phase,  15-  of the branch-circuit in combination with a listed outlet
         and  20-ampere  receptacles  that  serve  countertop  surfaces  branch-circuit-type arc-fault circuit-interrupter installed
         shall have ground-fault circuit-interrupter protection for per-  at the first outlet box on the branch circuit. The first
         sonnel. [210.8(A)(6)]                                     outlet box in the branch circuit shall be marked to indi-
         E3902.7  Sink  receptacles.  125-volt,  single-phase,  15-  and  cate  that  it  is  the  first  outlet  of  the  circuit.
         20-ampere  receptacles  that  are  located  within  6  feet  (1829  [210.12(A)(2)]
         mm) of the top inside edge of the bowl of the sink shall have  3. A  listed  supplemental  arc-protection  circuit  breaker
         ground-fault  circuit-interrupter  protection  for  personnel.  installed at the origin of the branch circuit in combination
         [210.8(A)(7)]                                             with a listed outlet branch-circuit-type arc-fault circuit-
         E3902.8 Bathtub or shower stall receptacles. 125-volt, sin-  interrupter installed at the first outlet box on the branch
         gle  phase,  15-  and  20-ampere  receptacles  that  are  located  circuit where all of the following conditions are met:
         within 6 feet (1829 mm) of the outside edge of a bathtub or  3.1. The  branch-circuit  wiring  shall  be  continuous
         shower  stall  shall  have  ground-fault  circuit-interrupter  pro-  from the branch-circuit overcurrent device to the
         tection for personnel. [210.8(A)(8)]                            outlet branch-circuit arc-fault circuit-interrupter.
         E3902.9 Laundry areas. 125-volt, single-phase, 15- and 20-  3.2. The maximum length of the branch-circuit wir-
         ampere receptacles installed in laundry areas shall have ground-  ing from the branch-circuit overcurrent device to
         fault circuit-interrupter protection for personnel. [210.8(A)(9)]  the first outlet shall not exceed 50 feet (15.2 m)
         E3902.10 Kitchen dishwasher branch circuit. Ground-fault        for 14 AWG conductors and 70 feet (21.3 m) for
         circuit-interrupter protection shall be provided for outlets that  12 AWG conductors.
         supply dishwashers in dwelling unit locations. [210.8(D)]   3.3. The first outlet box on the branch circuit shall
         E3902.11  Boathouse  receptacles.  125-volt,  single-phase,     be marked to indicate that it is the first outlet on
         15-  or  20-ampere  receptacles  installed  in  boathouses  shall  the circuit. [210.12(A)(3)]
         have ground-fault circuit-interrupter protection for personnel.  4. A listed outlet branch-circuit-type arc-fault circuit-inter-
         [210.8(A)(8)]                                             rupter installed at the first outlet on the branch circuit in
         E3902.12 Boat hoists.  Ground-fault circuit-interrupter  pro-  combination with a listed branch-circuit overcurrent pro-
         tection for personnel shall be provided for 240-volt and less  tective device where all of the following conditions are
         outlets that supply boat hoists. [210.8(C)]               met:
         E3902.13  Electrically  heated  floors.  Ground-fault  circuit-  4.1. The  branch-circuit  wiring  shall  be  continuous
         interrupter  protection  for  personnel  shall  be  provided  for  from the branch-circuit overcurrent device to the
         electric  heating  cables  embedded  in  concrete  or  poured   outlet branch-circuit arc-fault circuit-interrupter.
         masonry floors in bathrooms, kitchens and in hydromassage   4.2. The maximum length of the branch-circuit wir-
         bathtub, spa and hot tub locations. Heating cables installed    ing from the branch-circuit overcurrent device to
         under floor coverings shall be provided with ground-fault cir-  the first outlet shall not exceed 50 feet (15.2 m)
         cuit-interrupter  protection  for  personnel.  [424.44(E),      for 14 AWG conductors and 70 feet (21.3 m) for
         424.45(E)]                                                      12 AWG conductors.
         E3902.14  Location  of  ground-fault  circuit-interrupters.  4.3. The first outlet box on the branch circuit shall
         Ground-fault circuit-interrupters shall be installed in a readily  be marked to indicate that it is the first outlet on
         accessible location. When determining distance from recepta-    the circuit.



         730                                                                 2018 INTERNATIONAL RESIDENTIAL CODE  ®