POWER AND LIGHTING DISTRIBUTION


         E3905.4 Minimum depth of boxes for outlets, devices, and  port of luminaires and lampholders and shall be installed as
         utilization equipment. Outlet and device boxes shall have an  required by Section E3904.3. [314.27(A)]
         approved depth to allow equipment installed within them to  E3905.6.1 Vertical surface outlets. Boxes used at lumi-
         be mounted properly and without the likelihood of damage to  naire or lampholder outlets in or on a vertical surface shall
         conductors within the box. (314.24)                     be identified and marked on the interior of the box to indi-
           E3905.4.1 Outlet boxes without enclosed devices or uti-  cate the maximum weight of the luminaire or lamp holder
           lization  equipment.  Outlet  boxes  that  do  not  enclose  that is permitted to be supported by the box if other than
           devices  or  utilization  equipment  shall  have  an  internal  50 pounds (22.7 kg). [314.27(A)(1)]
                             1
           depth of not less than  /  inch (12.7 mm). [314.24(A)]
                              2                                    Exception:  A  vertically  mounted  luminaire  or  lam-
           E3905.4.2  Utilization  equipment.  Outlet  and  device  pholder weighing not more than 6 pounds (2.7 kg) shall
           boxes that enclose devices or utilization equipment shall  be permitted to be supported on other boxes or plaster
           have  a  minimum  internal  depth  that  accommodates  the  rings that are secured to other boxes, provided that the
           rearward projection of the equipment and the size of the  luminaire or its supporting yoke is secured to the box
           conductors that supply the equipment. The internal depth  with  not  fewer  than  two  No.  6  or  larger  screws.
           shall include that of any extension boxes, plaster rings, or  [314.27(A)(1) Exception]
           raised covers. The internal depth shall comply with all of  E3905.6.2  Ceiling  outlets.  For  outlets  used  exclusively
           the applicable provisions that follow. [314.24(B)]    for lighting, the box shall be designed or installed so that a
              Exception:  Utilization  equipment  that  is  listed  to  be  luminaire or lampholder can be attached. Such boxes shall
              installed with specified boxes.                    be capable of supporting a luminaire weighing up to 50
                                                                 pounds (22.7 kg). A luminaire that weighs more than 50
                1. Large equipment. Boxes that enclose devices or
                                                        7
                   utilization equipment that projects more than 1 / 8  pounds (22.7 kg) shall be supported independently of the
                   inches  (48  mm)  rearward  from  the  mounting  outlet box, unless the outlet box is listed for not less than
                   plane of the box shall have a depth that is not less  the weight to be supported. The interior of the box shall be
                                                 1
                   than the depth of the equipment plus  /  inch (6.4  marked  by  the  manufacturer  to  indicate  the  maximum
                                                  4
                   mm). [314.24(B)(1)]                           weight that the box is permitted to support. [314.27(A)(2)]
                                                              E3905.7 Floor boxes. Where outlet boxes for receptacles are
                2. Conductors  larger  than  4  AWG.  Boxes  that
                   enclose devices or utilization equipment supplied  installed in the floor, such boxes shall be listed specifically
                   by conductors larger than 4 AWG shall be identi-  for that application. [314.27(B)]
                   fied for their specific function. [314.24(B)(2)]  E3905.8 Boxes at fan outlets. Outlet boxes and outlet box
                                                              systems  used  as  the sole  support of ceiling-suspended fans
                3. Conductors 8, 6, or 4 AWG. Boxes that enclose
                   devices or utilization equipment supplied by 8, 6,  (paddle) shall be marked by their manufacturer as suitable for
                   or  4  AWG  conductors  shall  have  an  internal  this  purpose  and  shall  not  support  ceiling-suspended  fans
                   depth that is not less than 2 /  inches (52.4 mm).  (paddle) that weigh more than 70 pounds (31.8 kg). For outlet
                                         1
                                          16
                   [314.24(B)(3)]                             boxes and outlet box systems designed to support ceiling-sus-
                                                              pended fans (paddle) that weigh more than 35 pounds (15.9
                4. Conductors 12 or 10 AWG. Boxes that enclose  kg), the required marking shall include the maximum weight
                   devices or utilization equipment supplied by 12 or  to be supported.
                   10 AWG conductors shall have an internal depth
                   that is not less than 1 /  inches (30.2 mm). Where  Where spare, separately switched, ungrounded conductors
                                   3
                                    16
                   the equipment projects rearward from the mount-  are provided to a ceiling-mounted outlet box and such box is
                   ing plane of the box by more than 1 inch (25.4  in a location acceptable for a ceiling-suspended (paddle) fan,
                   mm), the box shall have a depth that is not less  the outlet box or outlet box system shall be listed for sole sup-
                                            1
                   than that of the equipment plus  /  inch (6.4 mm).  port of a ceiling-suspended (paddle) fan. [314.27(C)]
                                             4
                   [314.24(B)(4)]                             E3905.9 Utilization equipment. Boxes used for the support
                                                              of utilization equipment  other than ceiling-suspended (pad-
                5. Conductors  14  AWG  and  smaller.  Boxes  that
                   enclose devices or utilization equipment supplied  dle) fans shall meet the requirements of Sections E3905.6.1
                   by 14 AWG or smaller conductors shall have a  and E3905.6.2 for the support of a luminaire that is the same
                                         15
                   depth that is not less than  /  inch (23.8 mm).  size and weight. [314.27(D)]
                                           16
                   [314.24(B)(5)]                                Exception: Utilization equipment weighing not more than
         E3905.5  Boxes  enclosing  flush-mounted  devices.  Boxes  6 pounds (2.7 kg) shall be permitted to be supported on
         enclosing flush-mounted devices shall be of such design that  other boxes or plaster rings that are secured to other boxes,
         the devices are completely enclosed at the back and all sides  provided  that  the  equipment  or  its  supporting  yoke  is
         and shall provide support for the devices. Screws for support-  secured to the box with not fewer than two No. 6 or larger
         ing the  box  shall  not  be  used for attachment of the  device  screws. [314.27(D) Exception]
         contained therein. (314.19)                          E3905.10  Conduit  bodies  and  junction,  pull  and  outlet
                                                              boxes to be accessible. Conduit bodies and junction, pull and
         E3905.6  Boxes at luminaire  outlets. Outlet boxes  used at
         luminaire or lampholder outlets shall be designed for the sup-  outlet boxes shall be installed so that the wiring therein can
                                                              be  accessed  without  removing  any  part  of  the  building  or