Page 774 - 2018_IRC
P. 774

POWER AND LIGHTING DISTRIBUTION



             E3907.2 Damp and wet locations. In damp or wet locations,  3. A fitting is provided on each end of the raceway to
             cabinets and panelboards of the surface type shall be placed  protect  the  cable(s)  from  abrasion  and  the  fittings
             or equipped so as to prevent moisture or water from entering  remain accessible after installation.
             and accumulating within the cabinet, and shall be mounted to  4. The raceway is sealed or plugged at the outer end
                                         1
             provide an air-space not less than  /  inch (6.4 mm) between  using approved means so as to prevent access to the
                                          4
             the enclosure and the wall or other supporting surface. Cabi-  enclosure through the raceway.
             nets  installed  in  wet  locations  shall  be  weatherproof.  For  5. The cable sheath is continuous through the raceway
             enclosures  in  wet  locations,  raceways  and  cables  entering  and extends into the enclosure beyond the fitting not
             above  the  level  of  uninsulated  live  parts  shall  be  installed  less than  /  inch (6.4 mm).
                                                                                 1
             with fittings listed for wet locations. (312.2)                      4
                                                                       6. The raceway is fastened at its outer end and at other
               Exception: Nonmetallic enclosures installed on concrete,  points in accordance with Section E3802.1.
               masonry, tile, or similar surfaces shall not be required to
               be installed with an air space between the enclosure and  7. The allowable cable fill for conduit or tubing shall
               the wall or supporting surface. (312.2 Exception)         not exceed that permitted by Table E3907.8 and shall
                                                                         be considered as a complete conduit or tubing sys-
             E3907.3 Position in wall. In walls of concrete, tile or other  tem. A multiconductor cable having two or more con-
             noncombustible  material,  cabinets  and  panelboards  shall  be  ductors  shall  be  treated  as  a  single  conductor  for
             installed so that the front edge of the cabinet will not set back  calculating the percentage of conduit fill area. For
             of the finished surface more than  /  inch (6.4 mm). In walls  cables that have elliptical cross sections, the cross-
                                         1
                                          4
             constructed of wood or other combustible material, cabinets  sectional area calculation shall be based on the major
             shall be flush with the finished surface or shall project there-  diameter of the ellipse as a circle diameter. [312.5(C)
             from. (312.3)                                               Exception]
             E3907.4 Repairing noncombustible surfaces. Noncombus-           TABLE E3907.8 (Chapter 9, Table 1)
             tible surfaces that are broken or incomplete shall be repaired  PERCENT OF CROSS SECTION OF
                                                            1
             so that there will not be gaps or open spaces greater than  / 8  CONDUIT AND TUBING FOR CONDUCTORS
             inch  (3.2  mm)  at  the  edge  of  the  cabinet  or  cutout  box  NUMBER OF   MAXIMUM PERCENT OF CONDUIT AND
             employing a flush-type cover. (312.4)                   CONDUCTORS      TUBING AREA FILLED BY CONDUCTORS
                                                                          1                       5  3
             E3907.5 Unused openings. Unused openings, other than those
             intended for the operation of equipment, those intended for  2                       3  1
             mounting purposes, and those permitted as part of the design  Over 2                 40
             for listed equipment, shall be closed to afford protection sub-
             stantially equivalent to that of the wall of the equipment. Metal  E3907.9 Wire-bending space within an enclosure contain-
             plugs  and  plates  used  with  nonmetallic  cabinets  shall  be  ing a panelboard. Wire-bending space within an enclosure
                           1
             recessed  at  least  /   inch  (6.4  mm)  from  the  outer  surface.  containing a panelboard shall comply with the requirements
                             4
             Unused  openings  for  circuit  breakers  and  switches  shall  be  of Sections E3907.9.1 through E3907.9.3.
             closed using identified closures, or other approved means that  E3907.9.1 Top and bottom wire-bending space. The top
             provide protection substantially equivalent to the wall of the  and bottom wire-bending space for a panelboard enclosure
             enclosure. (110.12(A)]                                  shall  be  sized  in  accordance  with  Table  E3907.9.1(1)
             E3907.6 Conductors entering cabinets. Conductors enter-  based  on  the  largest  conductor  entering  or  leaving  the
             ing cabinets and panelboards shall be protected from abrasion  enclosure. [408.55 (A)]
             and shall comply with Section E3906.1.1. (312.5)          Exceptions:
             E3907.7  Openings  to  be  closed.  Openings  through  which  1. For a panelboard rated at 225 amperes or less and
             conductors  enter  cabinets,  panelboards  and  meter  sockets  designed to contain not more than 42 overcurrent
             shall be closed in an approved manner. [312.5(A)]              devices,  either  the  top  or  bottom  wire-bending
             E3907.8 Cables. Where cables are used, each cable shall be     space shall be permitted to be sized in accordance
             secured  to  the  cabinet,  panelboard,  cutout  box,  or  meter  with Table E3907.9.1(2). For the purposes of this
             socket enclosure. [312.5(C)]                                   exception, a 2-pole or a 3-pole circuit breaker shall
               Exception: Cables with entirely nonmetallic sheaths shall    be considered as two or three overcurrent devices,
               be permitted to enter the top of a surface-mounted enclo-    respectively. [408.55(A) Exception No. 1]
               sure through one or more sections of rigid raceway not less  2. For  any  panelboard,  either  the  top  or  bottom
               than 18 inches (457 mm) nor more than 10 feet (3048 mm)      wire-bending space shall be permitted to be sized
               in length, provided all the following conditions are met:    in accordance with Table E3907.9.1(2) where the
                  1. Each cable is fastened within 12 inches (305 mm),      wire-bending space on at least one side is sized in
                    measured along the sheath, of the outer end of the      accordance with Table E3907.9.1(1) based on the
                    raceway.                                                largest  conductor  to  be  terminated  in  any  side
                  2. The  raceway  extends  directly  above  the  enclosure  wire-bending space. [408.55(A) Exception No. 2]
                    and does not penetrate a structural ceiling.



             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               749
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   769   770   771   772   773   774   775   776   777   778   779