Page 776 - 2018_IRC
P. 776

POWER AND LIGHTING DISTRIBUTION


                        TABLE E3907.9.1(2) [Table 312.6(A)]       E3908.3  Specific  equipment  fastened  in  place  (fixed)  or
                   MINIMUM WIRE-BENDING SPACE AT TERMINALS        connected  by  permanent  wiring  methods.  Exposed,  nor-
                AND MINIMUM WIDTH OF WIRING GUTTERS (see Note 1)  mally noncurrent-carrying metal parts of the following equip-
                          COMPACT        WIRES PER TERMINAL
                          STRANDED        One          Two        ment  and  enclosures  shall  be  connected  to  an  equipment
               ALL OTHER   AA-8000                                grounding conductor:
              CONDUCTORS  ALUMINUM                                   1. Luminaires as provided in Chapter 40. [250.112(J)]
                            ALLOY
                         CONDUCTORS   inches  mm    inches  mm
                          (see Note 2)                               2. Motor-operated  water  pumps,  including  submersible
                                      Not     Not                      types.Where a submersible pump is used in a metal well
                 14-10      12-8                     —     —           casing, the well casing shall be connected to the pump
                                    specified specified
                                                                       circuit equipment grounding conductor. [250.112(L)]
                                       1
                 8-6         6-4      1 / 2   38.1   —     —
                 4-3         2-1       2      50.8   —     —      E3908.4  Effective  ground-fault  current  path.  Electrical
                                                                  equipment and wiring and other electrically conductive mate-
                  2          1  /  0  2  1 /  63.5   —     —
                                        2                         rial likely to become energized shall be installed in a manner
                  1          2  /  0   3      7  6  .  2  —  —    that creates a low-impedance circuit facilitating the operation
                                       1
                1/0-2/0    3/0-4/0    3 / 2   88.9    5   127     of the overcurrent device or ground detector for high-imped-
                3/0-4/0    250-300     4      102     6   152     ance grounded systems. Such circuit shall be capable of safely
                                                                  carrying  the  maximum  ground-fault  current  likely  to  be
                 250         350      4 / 2   114     6   152     imposed on it from any point on the wiring system where a
                                       1
                300-350    400-500     5      127     8   203     ground  fault  might  occur  to  the  electrical  supply  source.
                400-500    600-750     6      152     8   203     [250.(A)(5)]
                600-700    800-1000    8      203    10   254     E3908.5 Earth as a ground-fault current path. The earth
                750-900      —         8      203    12   305     shall not be considered as an effective ground-fault current
                                                                  path. [250.4(A)(5)]
               1000-1250     —         10     254    —     —
               1500-2000     —         12     305    —     —      E3908.6  Load-side  grounded  conductor  neutral. A
                                                                  grounded conductor shall not be connected to normally non-
             Notes:                                               current-carrying  metal  parts  of  equipment,  to  equipment
             1. Bending space at terminals shall be measured in a straight line from the  grounding conductor(s), or be reconnected to ground on the
               end of the lug or wire connector (in the direction that the wire leaves the  load side of the service disconnecting means. [250.24(A)(5)]
               terminal) to the wall, barrier, or obstruction.
             2. This column shall be permitted to be used to determine the minimum wire-  E3908.7 Load-side equipment. A grounded circuit conduc-
               bending space for compact stranded aluminum conductors in sizes up to  tor shall not be used for grounding noncurrent-carrying metal
               1000  kcmil  and  manufactured  using  AA-8000  series  electrical  grade  parts of equipment on the load side of the service disconnect-
               aluminum alloy conductor material in accordance with 310.106(B). The
               minimum width of the wire gutter space shall be determined using the all  ing means. [250.142(B)]
               other conductors value in this table.
                                                                  E3908.8 Types of equipment grounding conductors. The
                                                                  equipment grounding conductor run with or enclosing the cir-
                  2. Metal  components  that  are  installed  in  an  under-  cuit conductors shall be one or more or a combination of the
                    ground installation of rigid nonmetallic conduit and  following:
                    are  isolated  from  possible  contact  by  a  minimum
                    cover of 18 inches (457 mm) to any part of the metal  1. A  copper,  aluminum  or  copper-clad  conductor.  This
                    components or that are isolated from possible con-  conductor shall be solid or stranded; insulated, covered
                    tact by encasement in not less than 2 inches (51 mm)  or bare; and in the form of a wire or a busbar of any
                    of concrete. (250.86 Exception No. 3)              shape. [250.118(1)]
             E3908.2  Equipment  fastened  in  place  or  connected  by  2. Rigid metal conduit. [250.118(2)]
             permanent wiring methods (fixed). Exposed, normally non-  3. Intermediate metal conduit. [250.118(3)]
             current-carrying metal parts of fixed equipment supplied by
             or  enclosing  conductors  or  components  that  are  likely  to  4. Electrical metallic tubing. [250.118(4)]
             become  energized  shall  be  connected  to  the  equipment  5. Armor of Type AC cable in accordance with Section
             grounding conductor where any of the following conditions  E3908.4. [250.118(8)]
             apply:                                                  6. Type MC cable that provides an effective ground-fault
               1. Where  within  8  feet  (2438  mm)  vertically  or  5  feet  current path in accordance with one or more of the fol-
                  (1524  mm)  horizontally  of  earth  or  grounded  metal  lowing:
                  objects and subject to contact by persons;             6.1. It  contains  an  insulated  or  uninsulated  equip-
               2. Where located in a wet or damp location and not iso-       ment grounding conductor in compliance with
                  lated; or                                                  Item 1 of this section.
               3. Where in electrical contact with metal. (250.110)      6.2. The combined metallic sheath and uninsulated
                                                                             equipment  grounding/bonding  conductor  of





             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               751
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   771   772   773   774   775   776   777   778   779   780   781