P. 779

POWER AND LIGHTING DISTRIBUTION



           A single common continuous equipment bonding jumper            TABLE E3909.2 [Table 400.5(A)(1)]
         shall be permitted to connect two or more raceways or cables  MAXIMUM AMPERE LOAD FOR FLEXIBLE CORDS
         where the bonding jumper is sized in accordance with Table        CORD TYPES S, SE, SEO, SJ, SJE, SJEO, SJO, SJOO,
         E3908.12 for the largest overcurrent device supplying circuits    SJT, SJTO, SJTOO, SO, SOO, SRD, SRDE, SRDT, ST,
                                                                                STD, SV, SVO, SVOO, SVTO, SVTOO
         therein. [250.102(D) and 250.122]                      CORD SIZE
                                                                  (AWG)              Maximum ampere load
         E3908.20 Installation equipment bonding jumper. Bond-              Three current-carrying   Two current-carrying
         ing jumpers or conductors and equipment bonding jumpers               conductors         conductors
         shall be installed either inside or outside of a raceway or an  18        7                 10
         enclosure  in  accordance  with  Sections  E3908.20.1  and  16           10                 13
         E3908.20.2. [250.102(E)]                                  14             15                 18
                                                                   12             20                 25
           E3908.20.1  Inside  raceway  or  enclosure.  Where
           installed inside a raceway or enclosure, equipment bond-
           ing jumpers and bonding jumpers or conductors shall com-  E3909.3 Splices. Flexible cord shall be used only in continu-
           ply  with  the  requirements  of  Sections  E3407.2  and  ous lengths without splices or taps. (400.13)
           E3908.13. [250.102(E)(1)]                          E3909.4 Attachment plugs. Where used in accordance with
                                                              Section E3909.1, each flexible cord shall be equipped with an
           E3908.20.2  Outside  raceway  or  enclosure.  Where
           installed outside of a raceway or enclosure, the length of  attachment plug and shall be energized from a receptacle out-
           the  bonding  jumper  or  conductor  or  equipment  bonding  let. [400.10(B)]
           jumper  shall  not  exceed  6  feet  (1829  mm)  and  shall  be
           routed with the raceway or enclosure. [250.102(E)(2)]
             Equipment  bonding  jumpers  and  supply-side  bonding
           jumpers  installed  for  bonding  grounding  electrodes  and
           installed at outdoor pole locations for the purpose of bond-
           ing  or  grounding  isolated  sections  of metal  raceways  or
           elbows installed in exposed risers of metal conduit or other
           metal raceway, shall not be limited in length and shall not
           be  required  to  be  routed  with  a  raceway  or  enclosure.
           [250.102(E)(2) Exception]
           E3908.20.3  Protection.  Bonding  jumpers  or  conductors
           and  equipment  bonding  jumpers  shall  be  installed  in
           accordance with Section E3610.2. [250.102(E)(3)]


                          SECTION E3909
                         FLEXIBLE CORDS
         E3909.1 Where permitted. Flexible cords shall be used only
         for the connection of appliances where the fastening means
         and mechanical connections of such appliances are designed
         to permit ready removal for maintenance, repair or frequent
         interchange and the appliance is listed for flexible cord con-
         nection. Flexible cords shall not be installed as a substitute
         for the fixed wiring of a structure; shall not be run through
         holes  in  walls,  structural  ceilings,  suspended  ceilings,
         dropped  ceilings  or  floors;  shall  not  be  concealed  behind
         walls, floors, ceilings or located above suspended or dropped
         ceilings;  and  shall  not  be  attached  to  building  surfaces.
         (400.10 and 400.12)
         E3909.2 Loading and protection. The ampere load of flexi-
         ble cords serving fixed appliances shall be in accordance with
         Table E3909.2. This table shall be used in conjunction with
         applicable end use product standards to ensure selection of
         the proper size and type. Where flexible cord is approved for
         and used with a specific listed appliance, it shall be consid-
         ered to be protected where applied within the appliance list-
         ing requirements. [240.4, 240.5(A), 240.5(B)(1), 400.5, and
         400.16]