POWER AND LIGHTING DISTRIBUTION
A single common continuous equipment bonding jumper TABLE E3909.2 [Table 400.5(A)(1)]
shall be permitted to connect two or more raceways or cables MAXIMUM AMPERE LOAD FOR FLEXIBLE CORDS
where the bonding jumper is sized in accordance with Table CORD TYPES S, SE, SEO, SJ, SJE, SJEO, SJO, SJOO,
E3908.12 for the largest overcurrent device supplying circuits SJT, SJTO, SJTOO, SO, SOO, SRD, SRDE, SRDT, ST,
STD, SV, SVO, SVOO, SVTO, SVTOO
therein. [250.102(D) and 250.122] CORD SIZE
(AWG) Maximum ampere load
E3908.20 Installation equipment bonding jumper. Bond- Three current-carrying Two current-carrying
ing jumpers or conductors and equipment bonding jumpers conductors conductors
shall be installed either inside or outside of a raceway or an 18 7 10
enclosure in accordance with Sections E3908.20.1 and 16 10 13
E3908.20.2. [250.102(E)] 14 15 18
12 20 25
E3908.20.1 Inside raceway or enclosure. Where
installed inside a raceway or enclosure, equipment bond-
ing jumpers and bonding jumpers or conductors shall com- E3909.3 Splices. Flexible cord shall be used only in continu-
ply with the requirements of Sections E3407.2 and ous lengths without splices or taps. (400.13)
E3908.13. [250.102(E)(1)] E3909.4 Attachment plugs. Where used in accordance with
Section E3909.1, each flexible cord shall be equipped with an
E3908.20.2 Outside raceway or enclosure. Where
installed outside of a raceway or enclosure, the length of attachment plug and shall be energized from a receptacle out-
the bonding jumper or conductor or equipment bonding let. [400.10(B)]
jumper shall not exceed 6 feet (1829 mm) and shall be
routed with the raceway or enclosure. [250.102(E)(2)]
Equipment bonding jumpers and supply-side bonding
jumpers installed for bonding grounding electrodes and
installed at outdoor pole locations for the purpose of bond-
ing or grounding isolated sections of metal raceways or
elbows installed in exposed risers of metal conduit or other
metal raceway, shall not be limited in length and shall not
be required to be routed with a raceway or enclosure.
[250.102(E)(2) Exception]
E3908.20.3 Protection. Bonding jumpers or conductors
and equipment bonding jumpers shall be installed in
accordance with Section E3610.2. [250.102(E)(3)]
SECTION E3909
FLEXIBLE CORDS
E3909.1 Where permitted. Flexible cords shall be used only
for the connection of appliances where the fastening means
and mechanical connections of such appliances are designed
to permit ready removal for maintenance, repair or frequent
interchange and the appliance is listed for flexible cord con-
nection. Flexible cords shall not be installed as a substitute
for the fixed wiring of a structure; shall not be run through
holes in walls, structural ceilings, suspended ceilings,
dropped ceilings or floors; shall not be concealed behind
walls, floors, ceilings or located above suspended or dropped
ceilings; and shall not be attached to building surfaces.
(400.10 and 400.12)
E3909.2 Loading and protection. The ampere load of flexi-
ble cords serving fixed appliances shall be in accordance with
Table E3909.2. This table shall be used in conjunction with
applicable end use product standards to ensure selection of
the proper size and type. Where flexible cord is approved for
and used with a specific listed appliance, it shall be consid-
ered to be protected where applied within the appliance list-
ing requirements. [240.4, 240.5(A), 240.5(B)(1), 400.5, and
400.16]