P. 782

DEVICES AND LUMINAIRES


                              SECTION E4002                       shall be so installed that the mounting yoke or strap is seated
                              RECEPTACLES                         against the box or raised cover. [406.5(A) and (B)]
             E4002.1 Rating and type. Receptacles and cord connectors  E4002.7  Receptacles  mounted  on  covers.  Receptacles
             shall be rated at not less than 15 amperes, 125 volts, or 15  mounted  to  and supported  by  a  cover shall  be  held  rigidly
             amperes,  250  volts,  and  shall  not  be  a  lampholder  type.  against the cover by more than one screw or shall be a device
             Receptacles  shall  be  rated  in  accordance  with  this  section.  assembly or box cover listed and identified for securing by a
             [406.3(B)]                                           single screw. [406.5(C)]
               E4002.1.1 Single receptacle. A single receptacle installed  E4002.8 Damp locations. A receptacle installed outdoors in
               on an individual branch circuit shall have an ampere rating  a location protected from the weather or in other damp loca-
               not less than that of the branch circuit. [210.21(B)(1)]  tions shall have an enclosure for the receptacle that is weath-
               E4002.1.2 Two or more receptacles. Where connected to  erproof  when  the  receptacle  cover(s)  is  closed  and  an
               a branch circuit supplying two or more receptacles or out-  attachment plug cap is not inserted. An installation suitable
               lets, receptacles shall conform to the values listed in Table  for wet locations shall also be considered suitable for damp
               E4002.1.2. [210.21(B)(3)]                          locations. A receptacle shall be considered to be in a location
                                                                  protected from the weather where located under roofed open
                       TABLE E4002.1.2 [Table 210.21(B)(3)]       porches,  canopies  and  similar  structures  and  not  subject  to
                          RECEPTACLE RATINGS FOR
                      VARIOUS SIZE MULTI-OUTLET CIRCUITS          rain or water runoff. Fifteen- and 20-ampere, 125- and 250-
                                                                  volt nonlocking receptacles installed in damp locations shall
               CIRCUIT RATING (amperes)  RECEPTACLE RATING (amperes)
                                                                  be listed a weather-resistant type. [406.9(A)]
                       15                       15
                                                                  E4002.9 Fifteen- and 20-ampere receptacles in wet loca-
                       20                     15 or 20
                                                                  tions. Where installed in a wet location, 15- and 20-ampere,
                       30                       30                125- and 250-volt receptacles shall have an enclosure that is
                       40                     40 or 50            weatherproof  whether  or  not  the  attachment  plug  cap  is
                       50                       50                inserted. An outlet box hood installed for this purpose shall be
                                                                  listed and identified as “extra-duty.”
             E4002.2 Grounding type. Receptacles installed on 15- and  Exception:  15-  and  20-ampere,  125-  through  250-volt
             20-ampere-rated  branch  circuits  shall  be  of  the  grounding  receptacles installed in a wet location and subject to rou-
             type. [406.4(A)]                                        tine high-pressure spray washing need not have an enclo-
             E4002.3  CO/ALR  receptacles.  Receptacles  rated  at  20  sure  that  is  weatherproof  when  the  attachment  plug  is
             amperes or less and directly connected to aluminum conduc-  inserted.
             tors shall be marked CO/ALR. [406.3(C)]                 Fifteen-  and  20-ampere,  125-  and  250-volt  nonlocking
             E4002.4  Faceplates.  Metal  face  plates  shall  be  grounded.  receptacles  installed  in  wet  locations  shall  be  listed and so
             [406.6(B)]                                           identified as the weather-resistant type. [406.9(B)(1)]
             E4002.5  Position  of  receptacle  faces.  After  installation,  E4002.10 Other receptacles in wet locations. Where a recep-
             receptacle faces shall be flush with or project from face plates  tacle other than a 15- or 20-amp, 125- or 250-volt receptacle is
             of insulating material and shall project a minimum of 0.015  installed in a wet location and where the product intended to be
             inch (0.381 mm) from metal face plates. Faceplates shall be  plugged into it is not attended while in use, the receptacle shall
             installed so as to completely cover the opening and seat against  have an enclosure that is weatherproof both when the attach-
             the mounting surface.                                ment plug cap is inserted and when it is removed. Where such
                                                                  receptacle is installed in a wet location and where the product
               Receptacle faceplates mounted inside  of a box  having  a  intended to be plugged into it will be attended while in use, the
             recess-mounted receptacle shall effectively close the opening  receptacle shall have an enclosure that is weatherproof when
             and seat against the mounting surface. [406.5(D), 406.6]  the attachment plug cap is removed. [406.9(B)(2)]
               Exception: Listed kits or assemblies encompassing recep-  E4002.11 Bathtub and shower space. A receptacle shall not
               tacles and nonmetallic faceplates that cover the receptacle  be installed within or directly over a bathtub or shower stall.
               face,  where  the  plate  cannot  be  installed  on  any  other  [406.9(C)]
               receptacle, shall be permitted. [406.5(D) Exception]
                                                                  E4002.12 Flush mounting with faceplate. In damp or wet
             E4002.6 Receptacle mounted in boxes. Receptacles mounted  locations, the enclosure for a receptacle installed in an outlet
             in boxes that are set back from the finished wall surface as per-  box flush-mounted in a finished surface shall be made weath-
             mitted by Section E3906.5 shall be installed so that the mount-  erproof by means of a weatherproof faceplate assembly that
             ing yoke or strap of the receptacle is held rigidly at the finished  provides a water-tight connection between the plate and the
             surface of the wall. Screws used for the purpose of attaching  finished surface. [406.9(E)]
             receptacles to a box shall be of the type provided with a listed
             receptacle, or shall be machine screws having 32 threads per  E4002.13 Exposed terminals. Receptacles shall be enclosed
             inch or part of listed assemblies or systems, in accordance with  so  that  live  wiring  terminals  are  not  exposed  to  contact.
             the  manufacturer’s  instructions.  Receptacles  mounted  in  [406.5(I)]
             boxes that are flush with the wall surface or project therefrom



             2018 INTERNATIONAL RESIDENTIAL CODE ®                                                               757