DEVICES AND LUMINAIRES



         E4002.14 Tamper-resistant receptacles. In areas specified  2. Thermal protection shall not be required in recessed
         in  Section  E3901.1, 15-  and  20-ampere,  125-  and  250-volt  luminaires having design, construction, and thermal
         nonlocking-type  receptacles  shall  be  listed  tamper-resistant  performance  characteristics  equivalent  to  that  of
         receptacles. [406.12(A)]                                    thermally protected luminaires, and such luminaires
           Exception:  Receptacles  in  the  following  locations  shall  are  identified  as  inherently  protected.  [410.115(C)
           not be required to be tamper resistant:                   Exception No. 2]
              1. Receptacles located more than 5.5 feet (1676 mm)  E4003.6  Thermal  protection.  The  ballast  of  a  fluorescent
                above the floor.                              luminaire installed indoors shall have integral thermal protec-
                                                              tion. Replacement ballasts shall also have thermal protection
              2. Receptacles that are part of a luminaire or appliance.
                                                              integral with the ballast. A simple reactance ballast in a fluo-
              3. A  single  receptacle  for  a  single  appliance  or  a  rescent  luminaire  with  straight  tubular  lamps  shall  not  be
                duplex  receptacle  for  two  appliances  where  such  required to be thermally protected. [410.130(E)(1)]
                receptacles  are  located  in  spaces  dedicated  for  the
                appliances served and, under conditions of normal  E4003.7  High-intensity  discharge  luminaires.  Recessed
                use, the appliances are not easily moved from one  high-intensity luminaires designed to be installed in wall or
                place to another. The appliances shall be cord-and-  ceiling cavities shall have thermal protection and be identi-
                plug-connected  to  such  receptacles  in  accordance  fied as thermally protected. Thermal protection shall not be
                with Section E3909.4. [406.12(A) Exception]   required in recessed high-intensity luminaires having design,
                                                              construction and thermal performance characteristics equiva-
           E4002.15 Receptacles in countertops. Receptacle assem-  lent to that of thermally protected luminaires, and such lumi-
           blies for installation in countertop surfaces shall be listed  naires  are  identified  as  inherently  protected.  Thermal
           for  countertop  applications.  Receptacle  assemblies  and
           GFCI  receptacle  assemblies  installed  in  work  surfaces  protection shall not be required in recessed high-intensity dis-
           shall be listed for work surface or countertop applications.  charge luminaires installed in and identified for use in poured
           [406.5 (E) and (F)]                                concrete. A recessed remote ballast for a high-intensity dis-
                                                             charge luminaire shall have thermal protection that is integral
         E4002.16  Receptacle  position.  Receptacles  shall  not  be  with the ballast and shall be identified as thermally protected.
         installed in a face-up position in or on countertops surfaces or  [410.130(F)(1), (2), (3), and (4)]
         work surfaces except where the receptacles are listed for coun-
         tertop or work surface applications. [406.5 (G)]     E4003.8  Metal halide  lamp  containment.  Luminaires that
                                                              use  a  metal  halide  lamp  other  than  a  thick-glass  parabolic
                                                              reflector lamp (PAR) shall be provided with a containment bar-
                          SECTION E4003                       rier that encloses the lamp, or shall be provided with a physical
                           LUMINAIRES                         means  that  allows  the  use  of  only  a  lamp  that  is  Type  O.
         E4003.1  Energized  parts.  Luminaires,  lampholders,  and  [410.130(F)(5)]
         lamps shall not have energized parts normally exposed to con-  E4003.9 Wet or damp locations. Luminaires installed in wet
         tact. (410.5)                                        or damp locations shall be installed so that water cannot enter
         E4003.2  Luminaires  near  combustible  material.  Lumi-  or accumulate in wiring compartments, lampholders or other
         naires shall be installed or equipped with shades or guards so  electrical parts. All luminaires installed in wet locations shall
         that combustible material will not be subjected to tempera-  be marked “SUITABLE FOR WET LOCATIONS.” All lumi-
         tures in excess of 90°C (194°F). (410.11)            naires  installed  in  damp  locations  shall  be  marked  “SUIT-
         E4003.3  Exposed  conductive  parts.  The  exposed  metal  ABLE  FOR  WET  LOCATIONS”  or  “SUITABLE  FOR
         parts  of  luminaires  shall  be  connected  to  an  equipment  DAMP LOCATIONS.” (410.10)
         grounding conductor or shall be insulated from the equipment  E4003.10 Lampholders in wet or damp locations. Lamp-
         grounding conductor and other conducting surfaces. Lamp tie  holders installed in wet locations shall be listed for use in wet
         wires, mounting screws, clips and decorative bands on glass  locations. Lampholders installed in damp locations shall be
                      1
         spaced at least 1 /  inches (38 mm) from lamp terminals shall  listed for damp locations or shall be listed for wet locations.
                       2
         not be required to be grounded. (410.42)             (410.96)
         E4003.4 Screw-shell type. Lampholders of the screw-shell
         type  shall  be  installed  for  use  as  lampholders  only.  Where  E4003.11 Bathtub and shower areas. Cord-connected lumi-
         supplied  by  a  circuit  having  a  grounded  conductor,  the  naires, chain-, cable-, or cord-suspended-luminaires, lighting
         grounded  conductor  shall  be  connected  to  the  screw  shell.  track, pendants, and ceiling-suspended (paddle) fans shall not
         (410.90)                                             have any parts located within a zone measured 3 feet (914
         E4003.5  Recessed  incandescent  luminaires.  Recessed  mm) horizontally and 8 feet (2438 mm) vertically from the
         incandescent  luminaires  shall  have  thermal  protection  and  top of a bathtub rim or shower stall threshold. This zone is all
         shall be listed as thermally protected. [410.115(C)]  encompassing and includes the space directly over the tub or
                                                              shower.  Luminaires  within  the  actual  outside  dimension  of
           Exceptions:                                        the bathtub or shower to a height of 8 feet (2438 mm) verti-
              1. Thermal protection shall not be required in recessed  cally  from  the  top  of  the  bathtub  rim  or  shower  threshold
                luminaires  listed  for  the  purpose  and  installed  in
                poured concrete. [410.115(C) Exception No. 1]