CHAPTER 41

                                           APPLIANCE INSTALLATION




             ICC user note:
                About this chapter: Chapter 41 covers appliance installation, which is typically the final stage of construction after all wiring, devices and fix-
                tures are installed. This chapter covers flexible cords, overcurrent protection, disconnecting means and installation provisions.



                              SECTION E4101                          E4101.4.1  Single  nonmotor-operated  appliance.  The
                                 GENERAL                             overcurrent protection for a branch circuit that supplies a
             E4101.1 Scope. This section covers installation requirements  single nonmotor-operated appliance shall not exceed that
             for appliances and fixed heating equipment. (422.1 and 424.1)  marked on the appliance.  Where the overcurrent protec-
                                                                     tion rating is not marked and the appliance is rated at over
             E4101.2  Installation.  Appliances  and  equipment  shall  be  13.3 amperes, the overcurrent protection shall not exceed
             installed  in  accordance  with  the  manufacturer’s  installation  150 percent of the appliance rated current. Where 150 per-
             instructions.  Electrically  heated  appliances  and  equipment  cent of the appliance rating does not correspond to a stan-
             shall be installed with the required clearances to combustible  dard  overcurrent  device  ampere  rating,  the  next  higher
             materials. [110.3(B) and 422.17]                        standard rating shall be permitted. Where the overcurrent
             E4101.3  Flexible  cords.  Cord-and-plug-connected  appli-  protection rating is not marked and the appliance is rated
             ances shall use cords suitable for the environment and physi-  at 13.3  amperes  or less,  the  overcurrent protection  shall
             cal conditions likely to be encountered. Flexible cords shall  not exceed 20 amperes. [422.11(E)]
             be used only where the appliance is listed to be connected  E4101.5 Disconnecting means. Each appliance shall be pro-
             with a flexible cord. The cord shall be identified as suitable in  vided with a means to disconnect all ungrounded supply con-
             the  installation  instructions  of  the  appliance  manufacturer.  ductors.  For  fixed  electric  space-heating  equipment,  means
             Receptacles for cord-and-plug-connected appliances shall be  shall be provided to disconnect the heater and any motor con-
             accessible and shall be located to avoid physical damage to  troller(s) and supplementary overcurrent-protective devices.
             the flexible cord. Except for a listed appliance marked to indi-  Switches and circuit breakers used as a disconnecting means
             cate that it is protected by a system of double-insulation, the  shall be of the indicating type. Disconnecting means shall be
             flexible  cord  supplying  an  appliance  shall  terminate  in  a  as set forth in Table E4101.5. (422.30, 422.35, and 424.19)
             grounding-type attachment plug. The cord lengths specified
             for built-in dishwashers and trash compactors shall be mea-  E4101.6 Support of ceiling-suspended paddle fans. Ceil-
             sured from the face of the attachment plug to the plane of the  ing-suspended fans (paddle) shall be supported independently
             rear of the appliance. A receptacle for a cord-and-plug-con-  of an outlet box; by a listed outlet box or outlet box system
             nected range hood shall be supplied by an individual branch  identified for the use and installed in accordance with Section
             circuit. A receptacle for a built-in dishwasher shall be located  E3905.8;  or  by  a  listed  outlet  box  system,  a  listed  locking
             in a space adjacent to the space occupied by the dishwasher.  support and mounting receptacle, and a compatible factory-
             Specific appliances have additional requirements as specified  installed  attachment  fitting  designed  for  support,  identified
             in Table E4101.3 (see Section E3909). [422.16(B)(1), (B)(2),  for  the  use  and  installed  in  accordance  with  Section
             (B)(4)]                                              E3906.12. (422.18)
                                TABLE E4101.3                     E4101.7 Snow-melting and deicing equipment protection.
                            FLEXIBLE CORD LENGTH                  Outdoor  receptacles  that  are  not  readily  accessible  and  are
                                    MINIMUM CORD   MAXIMUM CORD   supplied from a dedicated branch circuit for electric snow-
                   APPLIANCE
                                   LENGTH (inches)  LENGTH (inches)  melting  or  deicing  equipment  shall  be  permitted  to  be
             Electrically operated      18            36          installed  without  ground-fault  circuit-interrupter  protection
               in-sink waste disposal                             for  personnel.  However,  ground-fault  protection  of  equip-
             Built-in dishwasher        36            78          ment shall be provided for fixed outdoor electric deicing and
                                                                  snow-melting equipment. [210.8(A)(3) Exception, 426.28]
             Trash compactor            36            48
             Range hoods                18            48          E4101.8 Lockable disconnecting means. Where a discon-
                                                                  necting means is required to be lockable, it shall be capable of
             For SI: 1 inch = 25.4 mm.                            being locked in the open position. The provisions for locking
                                                                  shall remain in place with or without the lock installed.
             E4101.4  Overcurrent  protection.  Each  appliance  shall  be
             protected against overcurrent in accordance with the rating of  Exception: Locking provisions for a cord-and-plug con-
             the appliance and its listing. [110.3(B), 422.11(A)]    nection shall not be required to remain in place without the
                                                                     lock installed.