POWER AND LIGHTING DISTRIBUTION



                    interlocked  metal  tape-type  MC  cable  that  is  E3908.8.3  Nonmetallic  sheathed  cable  (Type  NM).  In
                    listed and identified as an equipment grounding  addition to the insulated conductors, the cable shall have
                    conductor.                                   an insulated, covered, or bare equipment grounding con-
                6.3. The  metallic  sheath  or  the  combined  metallic  ductor. Equipment grounding conductors shall be sized in
                    sheath and equipment grounding conductors of  accordance with Table E3908.12. (334.108)
                    the  smooth  or  corrugated  tube-type  MC  cable  E3908.9  Equipment  fastened  in  place  or  connected  by
                    that  is  listed  and  identified  as  an  equipment  permanent  wiring  methods.  Noncurrent-carrying  metal
                    grounding conductor. [250.118(10)]        parts  of  equipment,  raceways  and  other  enclosures,  where
           7. Other electrically continuous metal raceways and auxil-  required to be grounded, shall be grounded by one of the fol-
              iary gutters. [250.118(13)]                     lowing methods: (250.134)
           8. Surface  metal  raceways  listed  for  grounding.  1. By any of the equipment grounding conductors permit-
              [250.118(14)]                                        ted  by  Sections  E3908.8  through  E3908.8.3.
           E3908.8.1 Flexible metal conduit. Flexible metal conduit  [250.134(A)]
           shall be permitted as an equipment grounding conductor  2. By  an  equipment  grounding  conductor  contained
           where all of the following conditions are met:          within the same raceway, cable or cord, or otherwise
                                                                   run with the circuit conductors. Equipment grounding
              1. The conduit is terminated in listed fittings.     conductors shall be identified in accordance with Sec-
              2. The circuit conductors contained in the conduit are  tion E3407.2. [250.134(B)]
                protected by overcurrent devices rated at 20 amperes  E3908.10 Methods of equipment grounding. Fixtures and
                or less.                                      equipment shall be considered grounded where mechanically
              3. The size of the conduit does not exceed trade size 1 / .  connected to an equipment grounding conductor as specified
                                                        1
                                                         4
              4. The combined length of flexible metal conduit and  in Sections E3908.8 through E3908.8.3. Wire type equipment
                flexible  metallic  tubing  and  liquid-tight  flexible  grounding conductors shall be sized in accordance with Sec-
                metal conduit in the same ground return path does  tion E3908.12. (250 Part VII)
                not exceed 6 feet (1829 mm).                  E3908.11  Equipment  grounding  conductor  installation.
                                                              Where an equipment grounding conductor consists of a race-
              If used to connect equipment where flexibility is neces-
           sary to minimize the transmission of vibration from equip-  way, cable armor or cable sheath or where such conductor is a
           ment or to provide flexibility for equipment that requires  wire within a raceway or cable, it shall be installed in accor-
           movement after installation, an equipment grounding con-  dance with the provisions of this chapter and Chapters 34 and
           ductor shall be installed. [250.118(5)]            38  using  fittings  for  joints  and  terminations  approved  for
                                                              installation with the type of raceway or cable used. All con-
           E3908.8.2  Liquid-tight  flexible  metal  conduit.  Liquid-  nections, joints and fittings shall be made tight using suitable
           tight flexible metal conduit shall be permitted as an equip-  tools. (250.120)
           ment grounding conductor where all of the following con-
           ditions are met:                                   E3908.12  Equipment  grounding  conductor  size.  Copper,
                                                              aluminum and copper-clad  aluminum  equipment  grounding
              1. The conduit is terminated in listed fittings.  conductors of the wire type shall be not smaller than shown in
                                      1
              2. For trade sizes  /  through  /  (metric designator 12  Table E3908.12, but they shall not be required to be larger
                             3
                                       2
                              8
                through 16), the circuit conductors contained in the  than the circuit conductors supplying the equipment. Where a
                conduit are protected by overcurrent devices rated at  raceway or a cable armor or sheath is used as the equipment
                20 amperes or less.                           grounding conductor, as provided in Section E3908.8, it shall
                             3
                                       1
              3. For trade sizes  /  through 1 /  (metric designator 21  comply with Section E3908.4. Where ungrounded conductors
                                                              are increased in size from the minimum size that has suffi-
                                        4
                              4
                through 35), the circuit conductors contained in the  cient ampacity for the intended installation, wire type equip-
                conduit are protected by overcurrent devices rated at  ment grounding conductors shall be increased proportionally
                not more than 60 amperes and there is no flexible  according to the circular mil area of the ungrounded conduc-
                metal  conduit,  flexible  metallic  tubing,  or  liquid-  tors. [250.122(A) and (B)]
                                                  3
                tight flexible metal conduit in trade sizes  /  inch or
                                                   8
                1 / inch  (9.5  mm  through  12.7  mm)  in  the  ground  E3908.12.1 Multiple circuits. Where a single equipment
                 2
                fault current path.                              grounding conductor  is  run with  multiple  circuits  in the
                                                                 same  raceway  or  cable,  it  shall  be  sized  for  the  largest
              4. The combined length of flexible metal conduit and  overcurrent device protecting conductors in the raceway or
                flexible  metallic  tubing  and  liquid-tight  flexible  cable. [250.122(C)]
                metal conduit in the same ground return path does
                not exceed 6 feet (1829 mm).                  E3908.13  Continuity  and  attachment  of  equipment
                                                              grounding conductors to boxes. Where circuit conductors
              If used to connect equipment where flexibility is neces-  are spliced within a box or terminated on equipment within or
           sary to minimize the transmission of vibration from equip-  supported  by  a  box,  all  equipment  grounding  conductors
           ment or to provide flexibility for equipment that requires  associated with any of those circuit conductors shall be con-
           movement after installation, an equipment grounding con-  nected within the box or to the box with devices suitable for
           ductor shall be installed. [250.118(6)]