POWER AND LIGHTING DISTRIBUTION



           E3905.12.2 Box fill calculations. The volumes in Section  volume  allowance  in  accordance  with  Table
           E3905.12.2.1 through Section E3905.12.2.5, as applicable,  E3905.12.2.1 shall be made for each type of fitting based
           shall be added together. No allowance shall be required for  on  the  largest  conductor  present  in  the  box.
           small fittings such as locknuts and bushings. Each space  [314.16(B)(3)]
           within  a  box  installed  with  a  barrier  shall  be  calculated  E3905.12.2.4 Device or equipment fill. For each yoke
           separately. [314.16(B)]                                 or strap containing one or more devices or equipment, a
              E3905.12.2.1  Conductor  fill.  Each  conductor  that  double  volume  allowance  in  accordance  with  Table
              originates outside the box and terminates or is spliced  E3905.12.2.1  shall  be  made  for  each  yoke  or  strap
              within the box shall be counted once, and each conduc-  based on the largest conductor connected to a device(s)
              tor that passes through the box without splice or termi-  or  equipment  supported  by  that  yoke  or  strap.  For  a
              nation  shall  be  counted  once.  Each  loop  or  coil  of  device or utilization equipment that is wider than a sin-
              unbroken conductor having a length equal to or greater  gle 2-inch (51 mm) device box as described in Table
              than twice that required for free conductors by Section  E3905.12.1, a double volume allowance shall be made
              E3406.11.3, shall be counted twice. The conductor fill,  for each ganged portion required for mounting of the
              in  cubic  inches,  shall  be  computed  using  Table  device or equipment. [314.16(B)(4)]
              E3905.12.2.1. A conductor, no part of which leaves the  E3905.12.2.5  Equipment  grounding  conductor  fill.
              box, shall not be counted. [314.16(B)(1)]            Where one or more equipment grounding conductors or
                Exception:  An equipment grounding conductor  or   equipment bonding jumpers enters a box, a single vol-
                not more than four fixture wires smaller than No. 14,  ume allowance in accordance with Table E3905.12.2.1
                or both, shall be permitted to be omitted from the  shall be made based on the largest equipment ground-
                calculations where such conductors enter a box from  ing conductor or equipment bonding jumper present in
                a  domed  fixture  or  similar  canopy  and  terminate  the box. [314.16(B)(5)]
                within that box. [314.16(B)(1) Exception]        E3905.12.3 Conduit bodies. Conduit bodies enclosing 6
                   TABLE E3905.12.2.1 [Table 314.16(B)]          AWG conductors or smaller, other than short-radius con-
             VOLUME ALLOWANCE REQUIRED PER CONDUCTOR             duit bodies, shall have a cross-sectional area not less than
                                    FREE SPACE WITHIN BOX        twice the cross-sectional area of the largest conduit or tub-
            SIZE OF CONDUCTOR       FOR EACH CONDUCTOR           ing to which they can be attached. The maximum number
                                        (cubic inches)           of  conductors  permitted  shall  be  the  maximum  number
                18 AWG                     1.50                  permitted by Section E3904.6 for the conduit to which it is
                16 AWG                     1.75                  attached. [314.16(C)(1)]
                14 AWG                     2.00                    E3905.12.3.1 Splices, taps or devices. Only those con-
                12 AWG                     2.25                    duit bodies that are durably and legibly marked by the
                                                                   manufacturer  with  their  cubic  inch  capacity  shall  be
                10 AWG                     2.50
                                                                   permitted to contain splices, taps or devices. The maxi-
                 8 AWG                     3.00                    mum  number  of  conductors shall be calculated  using
                 6 AWG                     5.00                    the same procedure for similar conductors in other than
                                                                   standard boxes. [314.16(C)(2)]
         For SI: 1 cubic inch = 16.4 cm . 3
              E3905.12.2.2 Clamp fill. Where one or more internal  E3905.12.3.2  Short-radius  conduit  bodies.  Conduit
              cable  clamps,  whether  factory  or  field  supplied,  are  bodies  such  as  capped  elbows  and  service-entrance
              present in the box, a single volume allowance in accor-  elbows that enclose conductors 6 AWG or smaller and
              dance with Table E3905.12.2.1 shall be made based on  that are only intended to enable the installation of the
              the largest conductor present in the box. An allowance  raceway and the contained conductors, shall not contain
              shall not be required for a cable connector having its  splices, taps, or devices and shall be of sufficient size to
              clamping mechanism outside of the box.               provide  free  space  for  all  conductors  enclosed  in  the
                                                                   conduit body. [314.16(C)(3)]
                 A clamp assembly that incorporates a cable termina-
              tion for the cable conductors shall be listed and marked
              for  use  with  specific  nonmetallic  boxes.  Conductors        SECTION E3906
              that  originate  within  the  clamp  assembly  shall  be    INSTALLATION OF BOXES,
              included in conductor fill calculations provided in Sec-  CONDUIT BODIES AND FITTINGS
              tion E3905.12.2.1 as though they entered from outside  E3906.1 Conductors entering boxes, conduit bodies or fit-
              of the box. The clamp assembly shall not require a fill  tings. Conductors entering boxes, conduit bodies or fittings
              allowance, but, the volume of the portion of the assem-  shall be protected from abrasion. (314.17)
              bly that remains within the box after installation shall
              be excluded from the box volume as marked in accor-  E3906.1.1 Insulated fittings. Where raceways contain 4
              dance with Section E3905.12.1.2. [314.16(B)(2)]    AWG or larger insulated circuit conductors and these con-
                                                                 ductors  enter  a  cabinet,  box  enclosure,  or  raceway,  the
              E3905.12.2.3 Support fittings fill. Where one or more
              fixture studs or hickeys are present in the box, a single  conductors shall be protected by an identified fitting pro-
                                                                 viding a smoothly rounded insulating surface, unless the