Page 26 - ICC IEBC 2018
P. 26

SCOPE AND ADMINISTRATION



                               SECTION 107                                          SECTION 109
                   TEMPORARY STRUCTURES AND USES                                     INSPECTIONS
             [A] 107.1 General. The code official is authorized to issue a  [A] 109.1 General. Construction or work for which a permit
             permit for temporary uses. Such permits shall be limited as to  is required shall be subject to inspection by the code official,
             time of service but shall not be permitted for more than 180  and such construction or work shall remain visible and able to
             days. The code official is authorized to grant extensions for  be accessed for inspection purposes until approved. Approval
             demonstrated cause.                                  as a result of an inspection shall not be construed to be an
             [A] 107.2 Conformance. Temporary uses shall conform to  approval of a violation of the provisions of this code or of
             the structural strength, fire safety, means of egress, accessi-  other ordinances of the jurisdiction. Inspections presuming to
             bility, light, ventilation and sanitary requirements of this code  give authority to violate or cancel the provisions of this code
             as necessary to ensure the public health, safety and general  or of other ordinances of the jurisdiction shall not be valid. It
             welfare.                                             shall be the duty of the permit applicant to cause the work to
             [A] 107.3 Temporary power. The code official is authorized  remain  visible and able to be accessed for inspection pur-
             to give permission to temporarily supply and use power in  poses. Neither the code official nor the jurisdiction shall be
             part of an electric  installation before  such installation  has  liable for expense entailed in the removal or replacement of
             been fully completed and the final certificate of completion  any material required to allow inspection.
             has been issued. The part covered by the temporary certificate  [A] 109.2 Preliminary inspection. Before issuing a permit,
             shall comply with the requirements specified for temporary  the  code official is authorized to examine or  cause to be
             lighting, heat or power in NFPA 70.                  examined buildings and sites  for which an application has
             [A] 107.4 Termination of approval. The  code official is  been filed.
             authorized to terminate such permit for a temporary use and  [A] 109.3 Required inspections. The code official, on notifi-
             to order the temporary use to be discontinued.
                                                                  cation, shall  make the inspections set forth in  Sections
                                                                  109.3.1 through 109.3.10.
                               SECTION 108                           [A] 109.3.1 Footing or foundation inspection. Footing
                                    FEES                             and foundation inspections shall be made after excavations
             [A] 108.1 Payment of fees. A permit shall not be valid until  for footings are  complete  and any required  reinforcing
             the fees prescribed by law have been paid. Nor shall an  steel is in place. For concrete foundations, any required
             amendment to a permit be released until the additional fee, if  forms shall be in place prior to inspection. Materials for
             any, has been paid.                                     the foundation shall be on the job, except where concrete
                                                                     is ready-mixed in accordance with ASTM C94, the con-
             [A] 108.2 Schedule of permit fees. On buildings, electrical,
             gas, mechanical, and plumbing systems or alterations requir-  crete need not be on the job.
             ing a permit, a fee for each permit shall be paid as required in  [A] 109.3.2 Concrete slab  or under-floor inspection.
             accordance with the schedule as established by the applicable  Concrete slab and under-floor inspections shall be made
             governing authority.                                    after in-slab or under-floor reinforcing steel and building
             [A] 108.3 Building permit valuations. The applicant for a  service equipment, conduit, piping accessories, and other
             permit shall provide an estimated permit value at  time  of  ancillary equipment items are in place but before any con-
             application. Permit valuations shall include total value of  crete is placed or floor sheathing installed, including the
             work including materials and labor for which the permit is  subfloor.
             being issued, such as electrical, gas, mechanical, plumbing  [A] 109.3.3 Lowest floor elevation. For  additions and
             equipment, and permanent systems. If, in the opinion of the  substantial improvements to  existing buildings in  flood
             code official, the valuation is underestimated on the applica-  hazard areas, on placement of the lowest floor, including
             tion, the permit shall be denied unless the applicant can show  basement, and prior  to further  vertical construction,  the
             detailed estimates to meet the approval of the code official.  elevation documentation required in the  International
             Final building permit valuation shall be set by the code offi-  Building Code shall be submitted to the code official.
             cial.
                                                                     [A] 109.3.4 Frame inspection. Framing inspections shall
             [A] 108.4 Work commencing before permit issuance. Any
             person who commences any work before obtaining the neces-  be made after  the roof  deck  or sheathing,  framing, fire
             sary permits shall be subject to an additional fee established  blocking, and bracing are  in  place and pipes, chimneys,
             by the code official that shall be in addition to the required  and vents to be concealed are complete and the rough elec-
             permit fees.                                            trical, plumbing, heating wires, pipes, and ducts are
                                                                     approved.
             [A] 108.5 Related fees. The payment of the fee for the con-
             struction, alteration, removal, or demolition of work done in  [A] 109.3.5 Lath or gypsum board inspection. Lath and
             connection to or concurrently with the work authorized by a  gypsum board inspections shall be made after lathing and
             building permit shall not relieve the applicant or holder of the  gypsum board, interior and exterior, is in place but before
             permit from the payment of other fees that are prescribed by  any plastering is applied or before gypsum board joints
             law.                                                    and fasteners are taped and finished.
             [A] 108.6 Refunds. The code official is authorized to estab-  Exception:  Gypsum  board  that is not part of a  fire-
             lish a refund policy.                                     resistance-rated assembly or a shear assembly.

             2018 INTERNATIONAL EXISTING BUILDING CODE ®                                                          7
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   21   22   23   24   25   26   27   28   29   30   31