WATER SUPPLY AND DISTRIBUTION



             building maintenance. In nonresidential  occupancies, hot  607.2.2 Piping for recirculation systems having master
             water  shall be  supplied  for culinary purposes, cleansing,  thermostatic valves. Where a thermostatic mixing valve
             laundry or building maintenance purposes. In nonresidential  is used in a system with a hot water recirculating pump,
             occupancies, hot water or tempered water shall be supplied  the hot water or tempered water return line shall be routed
             for bathing and washing purposes.                       to the cold water inlet pipe of the water heater and the cold
                                                                     water inlet pipe or the hot water return connection of the
               607.1.1 Temperature limiting means. A thermostat con-
               trol for a water heater shall not serve as the temperature  thermostatic mixing valve.
               limiting means for the purposes  of complying with the  607.3 Thermal expansion control. Where a storage water
               requirements of this code for maximum allowable hot or  heater is supplied with cold water that passes through a check
               tempered water delivery temperature at fixtures.   valve, pressure reducing valve or backflow preventer, a ther-
                                                                  mal expansion control device shall be connected to the water
               607.1.2  Tempered water temperature control.  Tem-  heater cold water supply pipe at a point that is downstream of
               pered water shall be supplied through a water temperature  all check valves, pressure reducing valves and backflow pre-
               limiting device that conforms  to ASSE 1070/ASME   venters. Thermal expansion tanks shall be sized in accor-
               A112.1070/CSA B125.70 and shall  limit  the  tempered  dance with the tank manufacturer’s instructions and shall be
               water  to  not greater  than 110ºF (43ºC).  This provision  sized such that the pressure in the water distribution system
               shall not supersede the requirement for protective shower  shall not exceed that required by Section 604.8.
               valves in accordance with Section 412.3.
                                                                  607.4 Flow of hot water to fixtures. Fixture fittings, faucets
             607.2 Hot or tempered water supply to fixtures. The devel-  and diverters shall be installed and adjusted so that the flow
             oped length of hot or tempered water piping, from the source  of hot water  from the fittings corresponds to the  left-hand
             of hot water to the fixtures that require hot or tempered water,  side of the fixture fitting.
             shall not exceed 50 feet (15 240 mm). Recirculating system
             piping  and heat-traced piping shall be considered to be  Exception:  Shower  and tub/shower  mixing valves con-
             sources of hot or tempered water.                       forming to ASSE 1016/ASME A112.1016/CSA B125.16
                                                                     or ASME A112.18.1/CSA B125.1, where the flow of hot
               607.2.1 Circulation systems and heat trace systems for  water corresponds to the markings on the device.
               maintaining heated water temperature in distribution
               systems. For Group R2, R3 and R4 occupancies that are  [E] 607.5 Insulation of piping. For other than Group R2, R3
               three stories or less in height above grade plane, the instal-  and  R4  occupancies that are  three stories or less in height
               lation of heated water circulation and temperature mainte-  above grade plane, piping to the inlet of a water heater and
               nance systems shall  be in  accordance with Section  piping conveying water  heated by a  water heater shall be
               R403.5.1 of the International Energy Conservation Code.  insulated in accordance with Section C404.4 of the Interna-
               For other than Group R2, R3 and R4 occupancies that are  tional Energy Conservation Code. For Group R2, R3 and R4
               three stories or less in height above grade plane, the instal-  occupancies that are three  stories  or  less in height  above
               lation of heated water circulation and heat trace systems  grade plane, piping to the inlet of a water heater and piping
               shall be in accordance with Section C404.6 of the Interna-  conveying water heated by a water heater shall be insulated in
               tional Energy Conservation Code.                   accordance with Section  R403.5.3 of the  International
                                                                  Energy Conservation Code.
                  607.2.1.1 Pump controls for hot water storage sys-
                  tems. The controls on pumps that circulate water
                  between a water heater and a storage tank for heated              SECTION 608
                  water shall limit operation of the pump from heating  PROTECTION OF POTABLE WATER SUPPLY
                  cycle startup to not greater than 5 minutes after the end
                  of the cycle.                                   608.1 General. A potable water supply system  shall be
                                                                  designed, installed and maintained in such a manner so as to
                  607.2.1.2 Demand recirculation controls for distri-  prevent contamination from nonpotable liquids, solids or
                  bution systems. A water  distribution system having  gases being introduced into the potable water supply through
                  one or more recirculation pumps that pump water from  cross connections or any other piping connections to the sys-
                  a heated water  supply pipe back  to  the heated water  tem. Backflow preventer applications shall conform to Table
                  source through a cold water supply pipe shall be  a  608.1, except as specifically stated in Sections 608.2 through
                  demand recirculation water system. Pumps shall have  608.17.10.
                  controls that comply with both of the following:
                                                                  608.2 Plumbing fixtures. The supply lines and fittings for
                    1. The control shall start the pump upon receiving a  plumbing fixtures shall be installed so as to prevent backflow.
                       signal from the action of a user of a fixture or  Plumbing fixture fittings shall provide backflow protection in
                       appliance, sensing the presence of a user of a fix-  accordance with ASME A112.18.1/CSA B125.1.
                       ture, or sensing the flow of hot or tempered water  608.3 Devices, appurtenances, appliances and apparatus.
                       to a fixture fitting or appliance.
                                                                  Devices, appurtenances, appliances and apparatus intended to
                    2. The control shall limit the  temperature of the  serve some special function, such as sterilization, distillation,
                       water entering the cold water  piping to 104°F  processing, cooling, or storage of ice or foods, and that con-
                       (40°C).                                    nect to the water supply system, shall be provided with pro-