WATER SUPPLY AND DISTRIBUTION



           transfer fluid shall be permitted to be of single-wall con-  608.17.8 Portable cleaning equipment. Where the porta-
           struction.                                            ble cleaning equipment connects to the water distribution
           608.17.4 Connections to  automatic fire sprinkler sys-  system, the water supply system shall be protected against
           tems and standpipe systems. The potable water supply to  backflow in accordance with Section 608.14.1, 608.14.2,
           automatic fire sprinkler and  standpipe  systems shall be  608.14.3, 608.14.7 or 608.14.8.
           protected  against  backflow by a  double check backflow  608.17.9 Dental pumping equipment. The water supply
           prevention assembly, a double check fire protection back-  connection to each dental pumping equipment system, the
           flow prevention assembly or a reduced pressure principle  water supply system shall be protected against backflow in
           fire protection backflow prevention assembly.         accordance with Section 608.14.1, 608.14.2, 608.14.5,
                                                                 608.14.6 or 608.14.8.
              Exceptions:
                                                                 608.17.10 Humidifiers. The water supply connection to
                1. Where systems are installed as a portion of the
                   water distribution system in accordance with the  humidifiers that do not have internal backflow protection
                   requirements of  this  code and are not provided  shall be protected  against backflow by a  backflow pre-
                   with a  fire department connection, isolation  of  venter conforming to ASSE 1012 or by an air gap.
                   the water supply system shall not be required.  608.18 Protection of individual water supplies. An individ-
                                                              ual water supply shall be located and constructed so as to be
                2. Isolation of the water distribution system is not
                   required for deluge,  preaction or dry pipe sys-  safeguarded against contamination in accordance with Sec-
                   tems.                                      tions 608.18.1 through 608.18.8.
                                                                 608.18.1 Well locations. A potable ground water source
              608.17.4.1 Additives or  nonpotable source.  Where
              systems under continuous pressure contain chemical  or pump suction line shall not be located closer to poten-
              additives or antifreeze, or where systems are connected  tial sources of contamination than the distances shown in
              to a nonpotable secondary water  supply, the potable  Table 608.18.1. In the event the underlying rock structure
              water supply shall be protected against backflow by a  is limestone or fragmented shale, the local or state health
              reduced pressure principle backflow prevention assem-  department shall be consulted on well site location. The
              bly or a reduced pressure principle fire protection back-  distances in  Table 608.18.1 constitute minimum separa-
              flow prevention assembly. Where chemical additives or  tion  and  shall be increased in  areas of creviced  rock or
              antifreeze are added to only a portion of an automatic  limestone, or where the direction of movement of  the
              fire sprinkler or standpipe  system, the reduced pressure  ground water is from sources of contamination toward the
              principle backflow prevention assembly or the reduced  well.
              pressure principle fire protection backflow prevention             TABLE 608.18.1
              assembly shall be permitted to be located so as to iso-   DISTANCE FROM CONTAMINATION TO
                                                                 PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES
              late that portion of the system. Where systems are not
              under continuous pressure, the potable  water supply   SOURCE OF CONTAMINATION      DISTANCE (feet)
              shall be protected against backflow by an air gap or an  Barnyard                       100
              atmospheric  vacuum breaker conforming to  ASSE  Farm silo                               25
              1001 or CSA B64.1.1.
                                                               Pasture                                100
           608.17.5 Connections to lawn irrigation systems.  The
                                                               Pumphouse floor drain of cast iron draining
           potable water supply to lawn irrigation systems shall be    to ground surface               2
           protected against  backflow by an atmospheric vacuum
           breaker, a pressure vacuum breaker assembly or a reduced  Seepage pits                      50
           pressure principle backflow prevention assembly. Valves  Septic tank                        25
           shall not be  installed  downstream from  an atmospheric  Sewer                             10
           vacuum breaker. Where chemicals are introduced into the
                                                               Subsurface disposal fields              50
           system, the potable water supply shall be protected against
           backflow by a reduced pressure principle backflow pre-  Subsurface pits                     50
           vention assembly.                                  For SI:   1 foot = 304.8 mm.
           608.17.6 Connections subject to backpressure. Where a  608.18.2 Elevation. Well sites shall be positively drained
           potable water connection is made to a nonpotable line, fix-  and shall be at higher elevations than potential sources of
           ture, tank, vat, pump or other equipment subject to high-  contamination.
           hazard backpressure, the potable water connection shall be  608.18.3 Depth. Private potable well supplies shall not be
           protected by a reduced pressure principle backflow pre-  developed from a water table less than 10 feet (3048 mm)
           vention assembly.                                     below the ground surface.
           608.17.7 Chemical dispensers. Where chemical dispens-  608.18.4 Water-tight  casings. Each well shall be  pro-
           ers connect to the potable water distribution system, the  vided with a water-tight casing extending to not less than
           water supply system shall be protected against backflow in  10 feet  (3048  mm) below the  ground surface.  Casings
           accordance with  Section 608.14.1,  608.14.2, 608.14.5,  shall  extend not less than 6 inches (152 mm) above the
           608.14.6, 608.14.8 or 608.14.9.                       well platform.  Casings shall be large enough to permit