WATER SUPPLY AND DISTRIBUTION
transfer fluid shall be permitted to be of single-wall con- 608.17.8 Portable cleaning equipment. Where the porta-
struction. ble cleaning equipment connects to the water distribution
608.17.4 Connections to automatic fire sprinkler sys- system, the water supply system shall be protected against
tems and standpipe systems. The potable water supply to backflow in accordance with Section 608.14.1, 608.14.2,
automatic fire sprinkler and standpipe systems shall be 608.14.3, 608.14.7 or 608.14.8.
protected against backflow by a double check backflow 608.17.9 Dental pumping equipment. The water supply
prevention assembly, a double check fire protection back- connection to each dental pumping equipment system, the
flow prevention assembly or a reduced pressure principle water supply system shall be protected against backflow in
fire protection backflow prevention assembly. accordance with Section 608.14.1, 608.14.2, 608.14.5,
608.14.6 or 608.14.8.
Exceptions:
608.17.10 Humidifiers. The water supply connection to
1. Where systems are installed as a portion of the
water distribution system in accordance with the humidifiers that do not have internal backflow protection
requirements of this code and are not provided shall be protected against backflow by a backflow pre-
with a fire department connection, isolation of venter conforming to ASSE 1012 or by an air gap.
the water supply system shall not be required. 608.18 Protection of individual water supplies. An individ-
ual water supply shall be located and constructed so as to be
2. Isolation of the water distribution system is not
required for deluge, preaction or dry pipe sys- safeguarded against contamination in accordance with Sec-
tems. tions 608.18.1 through 608.18.8.
608.18.1 Well locations. A potable ground water source
608.17.4.1 Additives or nonpotable source. Where
systems under continuous pressure contain chemical or pump suction line shall not be located closer to poten-
additives or antifreeze, or where systems are connected tial sources of contamination than the distances shown in
to a nonpotable secondary water supply, the potable Table 608.18.1. In the event the underlying rock structure
water supply shall be protected against backflow by a is limestone or fragmented shale, the local or state health
reduced pressure principle backflow prevention assem- department shall be consulted on well site location. The
bly or a reduced pressure principle fire protection back- distances in Table 608.18.1 constitute minimum separa-
flow prevention assembly. Where chemical additives or tion and shall be increased in areas of creviced rock or
antifreeze are added to only a portion of an automatic limestone, or where the direction of movement of the
fire sprinkler or standpipe system, the reduced pressure ground water is from sources of contamination toward the
principle backflow prevention assembly or the reduced well.
pressure principle fire protection backflow prevention TABLE 608.18.1
assembly shall be permitted to be located so as to iso- DISTANCE FROM CONTAMINATION TO
PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES
late that portion of the system. Where systems are not
under continuous pressure, the potable water supply SOURCE OF CONTAMINATION DISTANCE (feet)
shall be protected against backflow by an air gap or an Barnyard 100
atmospheric vacuum breaker conforming to ASSE Farm silo 25
1001 or CSA B64.1.1.
Pasture 100
608.17.5 Connections to lawn irrigation systems. The
Pumphouse floor drain of cast iron draining
potable water supply to lawn irrigation systems shall be to ground surface 2
protected against backflow by an atmospheric vacuum
breaker, a pressure vacuum breaker assembly or a reduced Seepage pits 50
pressure principle backflow prevention assembly. Valves Septic tank 25
shall not be installed downstream from an atmospheric Sewer 10
vacuum breaker. Where chemicals are introduced into the
Subsurface disposal fields 50
system, the potable water supply shall be protected against
backflow by a reduced pressure principle backflow pre- Subsurface pits 50
vention assembly. For SI: 1 foot = 304.8 mm.
608.17.6 Connections subject to backpressure. Where a 608.18.2 Elevation. Well sites shall be positively drained
potable water connection is made to a nonpotable line, fix- and shall be at higher elevations than potential sources of
ture, tank, vat, pump or other equipment subject to high- contamination.
hazard backpressure, the potable water connection shall be 608.18.3 Depth. Private potable well supplies shall not be
protected by a reduced pressure principle backflow pre- developed from a water table less than 10 feet (3048 mm)
vention assembly. below the ground surface.
608.17.7 Chemical dispensers. Where chemical dispens- 608.18.4 Water-tight casings. Each well shall be pro-
ers connect to the potable water distribution system, the vided with a water-tight casing extending to not less than
water supply system shall be protected against backflow in 10 feet (3048 mm) below the ground surface. Casings
accordance with Section 608.14.1, 608.14.2, 608.14.5, shall extend not less than 6 inches (152 mm) above the
608.14.6, 608.14.8 or 608.14.9. well platform. Casings shall be large enough to permit
56 2018 INTERNATIONAL PLUMBING CODE ®