                                                     ASPETTI NORMATIVI     REGULATORY ISSUES
                Il trattamento                                                                                  Water treatment







                          dell’                                     acqua










                                                                                      COME DEVE ESSERE L’ACQUA DEL NOSTRO IMPIANTO
                                                                                      DI RISCALDAMENTO Rif. Norma UNI CTI 8065/89
                                                                                      HEATING SYSTEM WATER: ITS NECESSARY CHARACTERISTICS
                                                                                      ref: Standard UNI CTI 8065/89

 KIT C                                                                                Acqua di riempimento e di rabbocco
 TRATTAMENTI                                                                          Filling and make-up water
 Universali Impiani Nuovi e Usai
 Alta e Bassa Temperatura                                                             Aspeto Appearance         limpido / clear
                                                                                      Durezza totale Total hardness  minore di 15 °f / <15 °f
                                                                                      Acqua di caldaia o in circuito
                                                                                      Boiler or circuit water
                                                                                      Aspeto Appearance         Possibilmente limpida / clear, if possible
                                                                                      pH                        Maggiore di 7 (con radiatori di alluminio o leghe
         The most common terms                                                                                  leggere il pH deve essere anche minore di 8)
         of the system's water
         • APPEARANCE                          that the ani-corrosion protecion of the water                    pH > 7 (< 8 in case of aluminium or light alloy radiators)
         Depends on the presence in water of sedimen-  circuit is insuicient.         Condizionani              Preseni entro le concentrazioni prescrite dal fornitore
         ts, suspended and colloidal paricles as well as   • MAGNETITE                 Condiioning components   Present, within the range required by the supplier
         dissolved substances that have detectable cha-  Iron, if not protected, tends to oxidize in various
         racterisics: turbidity, colouring, foam formaion  forms including Magneite, an oxide usually pro-  Ferro (come Fe) Iron (Fe)   < 0,5 mg/kg (valori più elevai di ferro sono do-
         or magneic metal deposits.            tecive  and  magneic,  strongly  bonded  to  iron
         • BACTERIAL LOAD                      surface. Due to changes in temperature and high                  vui a fenomeni corrosivi da eliminare)
         Expresses the total number of bacteria per unit   temperatures, magneite decomposes to ferrous
         of volume. Can be esimated by couning the Co-  oxide powder in nature that oten clogs the heat         < 0.5mg/kg (higher values of iron are due to corrosion,
         lony Forming Units present on the Petri dish (la-  exchangers and pump bodies.                         which must be removed)
         boratory) where was culivated a known volume   • MOLYBDENUM
         of the liquid to be tested.           Chemical  element  acing  as  basic  acive  ingre-  Rame (come Cu) Copper (Cu)  <  0,1  mg/kg  (valori  più  elevai  di  rame  sono
         • CHEMICAL CONDITIONING               dient  of  the  main  chemical  pre-condiioning                  dovui a fenomeni corrosivi da eliminare)
         The chemical condiioning treatment means that   agents in addiives for heaing systems.
         a chemical product is used to prevent the forma-  • pH                                                  < 0.1mg/kg (higher values of copper are due to corrosion, which
         ion of chemical corrosion, which are ampliied   Expresses the degree of acidity or basicity (alka-     must be removed)
         by the increase of temperatures within the sy-  linity) of a soluion, according to a scale ranging
         stems. Various chemicals are used depending on   from 0 to 14. The pH is one of the basic parame-
         the formulaions in heaing and cooling circuits   ters for evaluaing the corrosivity of water. It is
         and also in domesic hot water producion cir-  also a very important factor in the development   TRATTAMENTI DELL’ACQUA NEGLI IMPIANTI
         cuits. They also prevent the adherence of carbo-  and extent of phenomena such as fouling, corro-
         nates in order to protect against oxidaion and   sion and microbiological growth.  TERMICI USO CIVILE - DM 192 del 6 marzo 2009/DPR 59 del 2 aprile 2009
         corrosion,  forming  a  protecive  molecular  ilm   • POLYPHOSPHATES
         on metal walls of thermal plants and eliminaing   Polyphosphates  are  also  chemical  condiioning   HEATING SYSTEM WATER: ITS NECESSARY CHARACTERISTICS - ref: Standard UNI CTI 8065/89
         the frequent gaseous and thermal stresses due   agents used in the producion of domesic hot
         to contact with diferent metals.      water, and combine with the hardness (without   Impianto   Potenza   Durezza acqua  Obblighi
         • DENSITY                             changing  the  value  of  water)  and  prevent  the
         Is deined by the raio between the mass of a   precipitaion  thus  avoiding  fouling,  which  lead   Plant   Power   Water hardness Obligaions
         body and the volume occupied by the same. The  to loss of eiciency of heaing systems and high
         unit of measurement in the internaional system   energy consumpion. They also explain the pro-  Riscaldamento  ≥ 350 kW  ≤ 15 °f   Filtro + ilmante
         is Kg/m ³.                            tecive funcion on pipes with an efecive ani-  Heaing                              Filter + ilming agent
         • HARDNESS                            corrosion acion.
         Expresses  the  sum  of  calcium  and  magnesium   • ALKALINE RESERVE                                   ≥ 15 °f         Filtro + addolcitore +
         salts that are dissolved in it. Is expressed in ppm   Expresses the amount of salts with alkaline pro-
         or mg/l OF CaCO3 or in French degrees (1° f =   peries  dissolved  in  water.  It  could  be  deined                    ilmante/ Filter + sotener
         10 ppm or mg/l of CaCO3). The hardness leads   simply as the opposite of acidity. Actually, it is                       + ilming agent
         to deposit formaion within circuits that are not   the water capacity to “resist” changes induced
         subjected to treatment.               by  external  factors  of  its  own  pH.  The  unit  of   Riscaldamento  ≤ 100 kW  ≥ 25 °f   Condizionante chimico
         • EC                                  measurement  is  expressed  in  ppm  (parts  per
         The electrical conducivity is the ability of a ma-  million). In the case of Anifreeze, an insuicient   Heaing           (ilmante)/Chemical
         terial to enable passage of electrical current. Is   Alkaline  Reserve  indicates  a  poor  protecion
         deined as the reverse value of residual current   against corrosion.                                                    condiioner (ilming)

         and its unit of measurement is Siemens per me-  • TDS                                        ≥ 100 ≤
         ter (S/m).                            Total Dissolved Solids or Fixed Residue is a para-                ≥ 25 °f         Addolcitore + ilmante/
         • SYSTEM AGE                          meter used to classify mineral waters and drin-        350 kW
                                               king water in general. Expressed in mg/l, it indi-                                Sotener + ilming agent
                                               cates the amount of solid substances, perfectly
                                               dried, that remains ater evaporaion by heaing   Sanitario   ≤ 100 kW  ≥ 15 °f     Condizionante chimico uso
                                               in a capsule of plainum, calibrated beforehand,   Sanitary                        alimentare (polifosfai)/
                                               a known quanity of iltered water.
                                               • FREEZING TEMPERATURE                                                            Food use chemical
                                               Expresses the temperature to which a soluion                                      condiioner (polyphosphates)
         • IRON                                can be subjected, before crystallizaion and con-       ≥ 100 ≤
                                               sequent solidiicaion.
         The iron in the circuit can give rise to deposits   • CST TESTER                                        ≥ 15 °f         Addolcitore/Sotener
         and/or secondary corrosion. The iron dissolved   Portable digital instrument for measuring Tempe-      350 kW
         in  water  originates  from  corrosion  and  shows   rature, Electrical Conducivity and Fixed Residue.