Planning Instruction 66571758GB0 Fire Detection 6
2. General description of the FX 3NET system
2.1 Standalone FX 3NET or FXL 3NET fire detection system
Main features Application areas
The modular design of the FX 3NET and FXL Protectable area up to 15,000 m²
3NET 2, 4, 6, or 8 loop control panel offers a (512 addresses – EN54)
competitive solution for small and medium sized Business and office buildings
projects. The address capacity of the detection Industrial sites
circuits also offers flexibility for cabling, thus Lodging houses
saving costs in installation work. Service centres
A wide range of intelligent detectors provides Health and nursing centres
solutions for all applications. In addition, Educational buildings
conventional detectors can be connected to
interface modules, making an upgrade of a former
conventional system flexible.
In many tests, the high-sensitive laser detectors FX 3NET and FXL 3NET standalone system
have proved to be even more efficient than the metrics
aspiration detection systems often used in, for 2 ... 8 addressable detection circuits
example, computer rooms. 159 intelligent detectors + 159 I/O-modules per
The I/O-modules are economical and save space detection circuit
in installation, and provide monitoring and control 250 detection zones
functions. 512 detectors and manual call points / EN54
With the extensive configuration software, all regulation
addresses and many control functions of the panel 2,544 addresses totally
can be adopted for the requirements of the 17 Ah (internal in FX), 34 Ah (external), 51 Ah
installation site. (external) or 68 Ah (external) batteries
The communication capability makes it possible to 1.0 A total load in normal condition and 4.0 A total
connect a standard printer and additional alarm load in alarm condition
display panels.
2.2 Standalone FXM 3NET fire detection system
Main features FXM 3NET standalone system metrics
The FXM control panel offers the same features as 1 ... 4 addressable detection circuits
the FX and FXL panels, but in a smaller format, with 159 intelligent detectors + 159 I/O-modules per
a smaller power supply and with less space for I/O detection circuit
controllers. 250 detection zones
512 detectors and manual call points / EN54
Application areas regulation
Protectable area up to 15,000 m² 1272 addresses totally
(512 addresses – EN54) 12 Ah (internal) or 34 Ah (external) battery capacity
Industrial sites 0.5 A total load in normal condition and 2.2 A total
Lodging houses load in alarm condition
Elderly service centres
Day care centres
Educational buildings
© 2009 Schneider Electric. All rights reserved.
Note! When the INFO serial communication is used, the maximum address capacity per detection circuit is
214: lower address range 1...159 + higher address range 201...255.
Schneider Electric Pelco Finland Oy Kalkkipellontie 6, 02650 Espoo, Finland Telephone: +358 10 446 511 Fax: +358 10 446 5103 www.pelco.com/nordic
Document Number 66571758GB0 49 2011