Planning Instruction 66571758GB0 Fire Detection 7




2.3 FXS 3NET fire detection panel

Main features FXS 3NET standalone panel metrics
The FXS control panel offers the same features as  1 ... 2 addressable detection circuits
the FX and FXL and FXM panels, but in a smaller  159 intelligent detectors + 159 I/O-modules per
format and without any built-in power supply unit. In detection circuit
the FXS panel, there is one card slot for an option  250 detection zones
board.  318 detectors and manual call points
 636 addresses totally

Note! The power supply feed has to be brought
from an FX 3NET, FXL 3NET, or FXM 3NET
panel.


2.4 Networked FX 3NET fire detection system

Application areas FX NET system metrics
 Protectable area up to 500,000 m²  32 FX 3NET, FXL 3NET, FXM 3NET and
 Business and office complexes FXS 3NET panels
 Industrial sites  256 interpanel logical connections
 Hotels (seeing – visible connections)
 Service centres  255 addressable detection circuits
 Hospitals  8,000 detection zones
 Educational buildings  16,384 detectors and manual call points / EN54
regulations
 81,408 addresses totally (32 x FX capacity)
 Properties of the FX panels, see section 2.1, 2.2
and 2.3

Note! When the INFO serial communication is used, the maximum address capacity per detection circuit is
214: lower address range 1...159 + higher address range 201...255.