Page 17 - Simplified Wastewater Treatment Fundamentals / Operators Working With Maintenance
P. 17

Work Order and Job Site Preparation Example cont.





                        Tom made a timely logbook entry regarding the WAS Pump 1 failure and proceeded to the


                        field and did the following:


                        1.     Tom first checked the WAS Pump 1 main breaker, seeing that the breaker was ON and

                               not tripped.


                        2.     Tom proceeded to WAS Pump 1 checking to ensure the local Pump OFF/ON switch was


                               turned ON


                        3.     Tom checked to ensure the WAS Pump 1 valving was correct.


                        4.     Tom contacted his Lead Operator and coordinated locking out WAS Pump 1.



                        5.     Once locked out, Tom attempted to turn WAS Pump 1 shaft.

                               (WAS Pump 1 is a centrifugal pump, so the shaft should turn easily but, in this case, did

                               not)


                        6.     Tom removed the pump inspection plate finding a ball of rags and removed them.



                        7.     Tom replaced the inspection plate, removed the system locks and tested the pump.
   12   13   14   15   16   17   18   19   20   21   22