Page 264 - Flipbook_SolidDesignSoutheast2020
P. 264

Default Configuration Table #1 (400 Series Feeders-Continuous Mode)




                            Read Area                                     Write Area
             Data Description            Type   Address     Data Description           Type   Address
             Status #1                    S        0        Commands                    C        0
             Status #2                    S        4        Feed Rate Set Point (Ext Grav)  F    4
             Feed Rate Set Point (Ext Grav)  F     8        Feed Rate Set Point (Int Grav)  F    8
             Feed Rate Set Point (Int Grav)  F     12       Bulk Density                F        12
             Feed Rate                    F        16       High Level                  F        16
             Bulk Density                 F        20       Low Level                   F        20
             High Level                   F        24       Empty Level                 F        24
             Low Level                    F        28       Proportional                F        28
             Empty Level                  F        32       Integral                    B        32
             Hopper Level                 F        36       Max Feed Rate               F        36
             Proportional                 F        40       Total Fed                   F        40
             Integral                     B        44       Total Fed 2                 F        44
             Max Feed Rate                F        48       Total Throughput            F        48
             Total Fed                    F        52       Run Recipe                  B        52
             Total Fed 2                  F        56
             Motor Speed                  F        60
             Motor Current                F        64
             Scale Weight (Lb.)           F        68

                  STATUS (S)         FLOATING POINT (F)        BINARY (B)            COMMAND (C)

        Default Configuration Table #2  (400 Series Feeders-Batch Mode)



                            Read Area                                     Write Area
             Data Description           Type    Address     Data Description           Type   Address
             Status #1                   S         0        Commands                    C        0
             Status #2                   S         4        Feed Rate Set Point (Ext Grav)  F    4
             Feed Rate Set Point (Ext Grav)  F     8        Feed Rate Set Point (Int Grav)  F    8
             Feed Rate Set Point (Int Grav)  F    12        Feed Rate Set Point (Int Vol)  F     12
             Feed Rate Set Point (Int Vol)  F     16        Bulk Density                F        16
             Feed Rate                   F        20        High Level                  F        20
             Bulk Density                F        24        Low Level                   F        24
             High Level                  F        28        Empty Level                 F        28
             Low Level                   F        32        Proportional                F        32
             Empty Level                 F        36        Integral                    B        36
             Hopper Level                F        40        Max Feed Rate               F        40
             Proportional                F        44        Total Fed                   F        44
             Integral                    B        48        Total Fed 2                 F        48
             Max Feed Rate               F        52        Total Throughput            F        52
             Total Fed                   F        56        Run Recipe                  B        56
             Total Fed 2                 F        60        Batch Size Set Point        F        60
             Motor Speed                 F        64        Batch Preact                F        64
             Motor Current               F        68        Batch Deviation             F        68
             Scale Weight (Lb.)          F        72        Dribble Point               F        72
             Batch Fed                   F        76        Dribble Speed               F        76
             Batch Size Set Point        F        80
             Batch Preact                F        84
             Batch Deviation             F        88
             Dribble Point               F        92
             Dribble Speed               F        96
                  STATUS (S)         FLOATING POINT (F)        BINARY (B)            COMMAND (C)







                                                     20 Empire Blvd., Moonachie,  New Jersey 07074
                                                     20 Empire Blvd., Moonachie,  New Jersey 07074
                                                     20 Empire Blvd., Moonachie,  New Jersey 07074  •• Phone: 201-440-8300 Phone: 201-440-8300 •  • Fax: 201-440-4939Fax: 201-440-4939
                                                     20 Empire Blvd., Moonachie,  New Jersey 07074  • Phone: 201-440-8300 • Fax: 201-440-4939
        Copyright 2003 – Acrison, Inc. – all rights reserved.  20 Empire Blvd., Moonachie,  New Jersey 07074  •• Phone: 201-440-8300 Phone: 201-440-8300 •  • Fax: 201-440-4939Fax: 201-440-4939
                                                                          -mail: Informail@acrison.com • Website: www.acrison.com
                                                                          -mail: Informail@acrison.com
                                                                          -mail: Informail@acrison.com •  • WWebsite: wwwebsite: www.acrison.com.acrison.com
        302-0574/D/06-03/7006                                            E E E E E-mail: Informail@acrison.com-mail: Informail@acrison.com •  • WWebsite: wwwebsite: www.acrison.com.acrison.com
   259   260   261   262   263   264   265   266   267   268   269